City Code 28-15 requires the user to keep a Phoenix interceptor working. Grease traps are pumped at least every 30 days and never go past 90. Food service gravity interceptors are pumped at least every three months, and any gravity interceptor when it is over 25 percent full and at least yearly. Keep records on site three years.
“Records and documentation must be available at the facility or site for a minimum of 3 years from the date created and be made available to the Director upon request.”
- Applies to:
- Restaurant and food service owners, tenants, property managers of shared interceptors, and the pumpers who serve them in the City of Phoenix
- Official fee:
- not applicable
- In force:
- Phoenix City Code Chapter 28 (Ord. G-6740, 2020); FOG Best Management Practices Manual, June 2024
- Last verified:
- October 4, 2026, against the official page
A grease interceptor in Phoenix is not an install-it-and-forget-it device. The user has to keep it working, and the city checks how well that is going by reading the pumping records. City Code 28-15 sets the rules, and the Water Services FOG manual restates them for kitchens.
What does the Phoenix code say?
Section 28-15 requires interceptors to be "maintained by the user in continuously effective operating condition at all times." At minimum that means periodic removal of all accumulated grease, lint, oil, sand, sludge, solids, wastewater and other materials, thorough cleaning of the interior, and necessary repairs to internal structures. The code then sets the schedule:
- Hydromechanical interceptors (grease traps): "must fully pump out and clean the interceptor at a frequency of not less than once every 30 days unless granted a variance by the Director. No hydromechanical interceptor may be allowed to go more than 90 days without maintenance."
- Gravity interceptors at food service establishments: pumped out and cleaned "not less than once every three months" unless the Director grants a variance.
- All gravity interceptors: a full cleaning once fats, oils and solids pass 25 percent of capacity, and at least once every 12 months unless the Director grants a variance. The 12-month floor is what reaches gravity interceptors at laundries, car washes and other non-food businesses.
- No chemical shortcuts: enzymes, bacteria, solvents and emulsifiers may not be used in lieu of physical cleaning, and a pumper may not put removed contents back into the interceptor.
- Records: they must be available at the facility or site for a minimum of three years from the date created and be made available to the Director on request. The code says they cover all cleaning, the volume of waste removed, device capacity, waste disposal, repair, replacement and maintenance.
The city's FOG manual restates the schedule in kitchen terms. It adds that a licensed pumper must do the cleaning, that the interceptor must be left completely empty, and that a new kitchen should watch how fast grease builds during its first months with its pumper or an Environmental Services inspector and adjust the interval. The manual says the interceptor "may need to be pumped more frequently." Maintenance is "the sole responsibility of the user, or in the case of multiple user interceptors, the property owner."
What do the key terms mean?
- User: the business that operates the kitchen. For an interceptor shared by several tenants, the manual makes the property owner responsible.
- Variance: permission from the Director for a different interval. Neither the code nor the manual promises one.
- Records: the manual counts pumping invoices from third-party contractors as maintenance records.
Who does this cover?
Any user of a grease trap or gravity interceptor in the City of Phoenix. The 30-day and 90-day trap rule covers every hydromechanical user, and the three-month rule is written for food service establishments. Section 28-12 also reaches laundries, service stations, auto repair shops, car washes and commissaries when the Director requires an interceptor, and those gravity interceptors fall under the 25 percent and 12-month rules.
Quick check: is my schedule legal?
| Situation | What the city expects |
|---|---|
| Grease trap last pumped 45 days ago | Overdue under the standard 30-day interval unless the Director granted a variance |
| Grease trap last pumped 100 days ago | Past the 90-day cap, which no trap may exceed |
| Food service gravity interceptor pumped every 4 months | Late unless the Director granted a variance |
| Car wash gravity interceptor last pumped 14 months ago | Past the 12-month floor unless the Director granted a variance |
| Gravity interceptor 30 percent full at 2 months | Full cleaning required now |
| Invoices only in the pumper's office | Not enough. Records must be at the facility |
| Enzyme treatment used between pumpings | Prohibited as a substitute for cleaning |
What does this look like in real life?
- A taqueria pumps its trap once a quarter because nothing smells. Without a variance, quarterly does not meet the 30-day standard and can run past the 90-day cap.
- A restaurant's gravity interceptor is pumped every three months on the dot, but the kitchen fries a lot. The schedule is a minimum. If the inspector finds grease and solids over 25 percent, the interceptor needs a full cleaning sooner.
- A strip center shares one interceptor among four tenants. The property owner is responsible, so the owner needs the pumping invoices, not just each tenant.
- The same taqueria switches to an enzyme product to stretch its pumping schedule. The answer flips: the manual prohibits enzymes and bacteria used to dissolve grease, and the pumping frequency still applies.
What should you do next?
- 1Find your device type (trap or gravity interceptor) and put its next pump date on the calendar.
- 2Book a licensed pumper and ask for a written invoice every visit.
- 3Keep a folder at the restaurant with every invoice and log for the last three years.
- 4Watch the first months of a new kitchen and shorten the interval if grease builds fast.
- 5If you want a longer interval, ask the Director for a variance before you stretch the schedule. Questions about interceptors go to the Water Services Environmental Services Division, which schedules interceptor plan review appointments at 602-495-0278.
What do people get wrong?
- "Quarterly is the rule for everything." That is the food service gravity interceptor minimum. Traps are every 30 days, and gravity interceptors at non-food businesses have a 12-month floor.
- "My pumper keeps the records." The code says the records must be available at the facility or site.
- "Pumping out the liquid is enough." The interceptor must be completely emptied and cleaned, and the removed material may not go back in.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | Mesa's code sets the duty but not a calendar. The owner must keep the interceptor in continuously efficient operation at the owner's expense, and must keep records at the facility for at least three years for the city. The code has no pumping interval, no 25 percent rule and no additive ban. | Mesa City Code 8-4-22(D) Verified September 29, 2026 |
| Scottsdale | Scottsdale writes the calendar into its plumbing amendments. Interceptors of 100 gpm and 200 pounds or less are cleaned at least every 30 calendar days and larger ones every 90 calendar days, and cleaning is also required once fats, oil, grease and solids fill more than 25 percent of the volume. Logs are kept at the facility for three years. | Scottsdale City Code 31-85 (IPC 1005.1, 1005.2, 1005.5) Verified September 29, 2026 |
| Chandler | Chandler's city page sets no fixed calendar. Cleaning frequency depends on the device size and the kitchen's practices, but as a rule of thumb the combined grease and solids should not exceed 25 percent of capacity, and records go on site for three years. | Chandler Industrial Pretreatment Program, Food Service Establishments Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Commercial Plumbing in Other Cities
- GilbertHow often must a Gilbert restaurant pump its grease trap? Town Code 66-244(d) and (e)
- GilbertGilbert Town Code 66-244: grease removal devices for restaurants and food service
- GilbertGilbert Town Code 66-245: floor drains and wash racks at auto shops and car washes
- GlendaleGlendale City Code 33-238: grease interceptors must be pumped every 180 days
- MesaWhat can a Mesa business not put down the drain? City Code 8-4-15 prohibited discharges and limits
- MesaKeeping Mesa pretreatment equipment running: City Code 8-4-21 records and bypass rules
More Phoenix Codes and Permits
- Commercial PlumbingCan a Phoenix business get an annual permit for plumbing alterations?
- Commercial PlumbingPhoenix City Code 28-12: Which businesses must install a grease or oil interceptor?
- Commercial PlumbingWhich minor commercial plumbing jobs can be permitted online in Phoenix?
- Commercial PlumbingWhat permit does a Phoenix business need for a plumbing remodel or tenant improvement?
- Commercial PlumbingWho approves a fire line connection in Phoenix?
- Commercial PlumbingWhat happens during a Phoenix commercial grease (FOG) inspection?
Related Rules and Questions
- PhoenixPhoenix restaurants: When do you need an outdoor gravity grease interceptor instead of a grease trap?
- PhoenixDo you need plan review to replace a grease interceptor in Phoenix?
- Valley-WideGrease Trap and Interceptor Rules by Valley City
- FAQHow often should a restaurant grease trap be pumped?
- FAQWhat is the 25 percent rule for grease traps?
- FAQWhat grease pumping records must a Phoenix restaurant keep?
- Commercial Plumbing