Scottsdale requires at least 500 gallons for a gravity grease interceptor. Its sizing formula uses DFU × 3 gpm × 12 or 17 minutes, while its gravity-interceptor definition specifies at least 30 minutes retention. Have plan review resolve that difference for the design. Small traps require four or fewer food-prep fixtures and no dishwasher.
“Gravity. Plumbing appurtenances of not less than 500 gallons (1892 L) capacity that are installed in the sanitary drainage system to intercept free-floating fats, oils and grease from waste water discharge.”
- Applies to:
- Restaurant designers, plumbing contractors and kitchen owners in Scottsdale, new builds and remodels
- Official fee:
- not applicable; see Scottsdale plan review fee schedules
- In force:
- 2021 IPC as amended by Scottsdale (Ord. 4550, Res. 12501); guidelines last modified 1/24/2023, since January 1, 2023
- Last verified:
- October 4, 2026, against the official page
Scottsdale does not size grease interceptors from a lookup chart. It amended the 2021 International Plumbing Code, deleted the model code's capacity table, and replaced it with a short formula. The published definition and the sizing formula use different retention times. A designer needs the city's approval of the sizing basis, as well as the correct fixture count and interceptor type.
What does Scottsdale's sizing rule say?
Two passages in the city's own published material use different numbers. The gravity-interceptor definition specifies at least 500 gallons and separation by gravity over a retention time of not less than 30 minutes. Section 31-85, IPC 1003.3.7, and the guidelines' sizing formula instead use total drainage fixture units (DFU) × 3 gallons per minute × 12 minutes without a garbage disposal, or × 17 minutes with one.
The sources do not explain how the 12/17-minute calculation meets the 30-minute definition. This page reports both passages; it does not invent an engineering explanation or treat the smaller calculation as approved. Include both requirements in the plan-review question and obtain the city's accepted sizing basis before selecting the tank.
For small units, IPC 1003.3.5.1 as amended says hydromechanical grease interceptors (grease traps) are allowed only when four or fewer fixtures are used for food preparation. The only size allowed is a 50 gallon, 100 pound unit. Any facility installing a dishwasher must install a gravity interceptor.
What do the key terms mean?
- Drainage fixture unit (DFU): the plumbing code's number for how much drain load a fixture puts on the system. The city worksheet lists a DFU for each fixture type.
- Retention time: how long wastewater stays in the tank so grease can float. The code sets 12 or 17 minutes for the formula and the definition requires at least 30 minutes.
- Fixture, for a trap: the code says the entire unit counts, so a three-compartment sink is one fixture, not three.
- Flow restriction valve: a valve upstream of a trap that limits flow. It must be vented, and if the trap sits below floor level it must be installed so it can be inspected and maintained.
Who does this cover?
It covers anyone designing or replacing a grease interceptor in Scottsdale: designers, plumbing contractors and the restaurant owner who pays for it. It does not apply to the kitchen of a private home, and it does not cover sand and oil interceptors at car washes, which follow a different rule on our car wash page.
How do you work out the size?
The city's worksheet prints DFU values by fixture. As printed, a three-compartment sink is 9, a two-compartment sink 6, a pre-rinse sink 3, a prep sink 3, a mop sink 3, a floor sink 3, a trench drain 6 and a standard floor drain 2. A hand sink is 2. Dishwashers and glasswashers take their values from the equipment cut sheet, which the city wants included with the plumbing drawings.
Here is the arithmetic for a sample kitchen with no dishwasher and no disposal: one three-compartment sink (9), one prep sink (3), one pre-rinse sink (3), one mop sink (3) and one floor drain (2) add up to 20 DFU. Twenty times 3 gpm is 60 gpm, and 60 times 12 minutes is 720 gallons. With a garbage disposal the same kitchen uses 17 minutes and comes to 1,020 gallons. Those numbers show the printed formula only. They do not establish that either tank meets the separate 30-minute definition or that the city will approve it.
Quick check: what type do you need?
| Kitchen | Trap allowed? | Why |
|---|---|---|
| Three-compartment sink, prep sink, mop sink | Yes, 50 gal / 100 lb only | Three fixtures, under the four-fixture limit |
| Same kitchen plus one more food-prep unit | Yes, at four fixtures | Four or fewer is allowed |
| Five food-prep fixtures | No | Over four fixtures |
| Any kitchen installing a dishwasher | No | A dishwasher forces a gravity interceptor |
| Calculated size under 500 gallons | At least 500; confirm accepted design | 500 gallons is the floor, and the retention-time difference still needs review |
| Calculated size over 2,500 gallons | Gravity, but costly to pump | City guidelines say standard pump trucks top out at 2,500 gallons |
What does this look like in real life?
A taco stand with a three-compartment sink and one prep sink. Two fixtures, no dishwasher, so a 50 gallon, 100 pound trap is allowed.
A sit-down restaurant in a strip mall. It has a pot sink, pre-rinse sink, two prep sinks, a mop sink and a dish machine. The dishwasher alone forces a gravity interceptor, and the designer must submit a size the city accepts after resolving the retention-time difference.
The edge case: no space for a new tank. IPC 1003.3.1 as amended lets one or more interceptors go on or above the floor and upstream of an existing interceptor when space or other constraints stop a new or replacement tank. That changes a retrofit answer from "dig up the parking lot" to a design review.
What should you do next?
- 1List every fixture on the drawings and note which drain to the interceptor.
- 2Look up each fixture on the city's worksheet and add the DFUs. Include hand sinks in food prep areas unless your plumbing sheet carries the city's exclusion note.
- 3Calculate the printed DFU × 3 × 12/17 formula, then ask plan review how the separate 30-minute gravity-interceptor definition applies. Obtain that clarification before specifying the tank.
- 4If the result is over 2,500 gallons, consider two interceptors serving separate zones. The guidelines suggest zones over series or parallel connection so they can be pumped on separate cycles.
- 5Attach the worksheet and any dishwasher cut sheet to the permit submittal.
What do people get wrong?
- "Any interceptor over 500 gallons is fine." The size comes from the formula. Five hundred gallons is only the floor.
- "A hand sink can be left off the count." The guidelines count hand sinks in food prep areas unless a note on the plumbing sheet excludes them. A floor sink that receives a fixture's discharge is not counted separately.
- "A trap saves money on a busy kitchen." With a dishwasher or more than four fixtures a trap is not allowed, regardless of the volume.
This page summarizes the code. The adopted text on Municode governs.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Phoenix | Same arithmetic: DFUs of grease-bearing fixtures times 3 gpm times 12 or 17 minutes, 500 gallon minimum. Phoenix takes DFU values from its amended plumbing code rather than a city worksheet. | Phoenix FOG Best Management Practices Manual (June 2024), Gravity Grease Interceptor Sizing Verified October 4, 2026 |
| Mesa | 500 gallon minimum and a 2,500 gallon maximum. Fixture units come from trap size at 7.5 gpm each, dishwashers count double, the total is multiplied by 3 gpm and 12 minutes, and 750 gallons or more needs three chambers. | Mesa City Code 8-4-22(E) Verified October 4, 2026 |
This page explains the rule. The official text at the source above governs.
Commercial Plumbing in Other Cities
- GilbertHow often must a Gilbert restaurant pump its grease trap? Town Code 66-244(d) and (e)
- GilbertGilbert Town Code 66-244: grease removal devices for restaurants and food service
- GilbertGilbert Town Code 66-245: floor drains and wash racks at auto shops and car washes
- GlendaleGlendale City Code 33-238: grease interceptors must be pumped every 180 days
- MesaWhat can a Mesa business not put down the drain? City Code 8-4-15 prohibited discharges and limits
- MesaKeeping Mesa pretreatment equipment running: City Code 8-4-21 records and bypass rules
More Scottsdale Codes and Permits
- Commercial PlumbingHow often must a Scottsdale car wash or repair shop pump its interceptor?
- Commercial PlumbingWhen does Scottsdale require a grease interceptor?
- Commercial PlumbingWhat does Scottsdale require to submit a grease interceptor for permit?
- Commercial PlumbingHow does Scottsdale inspect restaurant grease traps?
- Backflow PreventionHow often must a Scottsdale backflow assembly be tested, and by whom?
- Backflow PreventionWhich backflow assembly types does Scottsdale recognize, and how does it rate hazards?
Related Rules and Questions
- UPCUPC Grease Interceptor Sizing: How Code Sizes a Grease Trap
- ArizonaPhoenix City Code Chapter 28: The FOG (Grease) Program for Food-Service Businesses
- FAQHow often should a restaurant grease trap be pumped?
- FAQWhat's the difference between a floor sink, floor drain, and mop sink?
- Commercial Drain Cleaning
- Commercial Plumbing