What can a Mesa business not put down the drain? City Code 8-4-15 prohibited discharges and limits

Verified September 29, 2026
In Short

Mesa bans wastewater below pH 5.0 or above 10.5, hotter than 150 degrees F, with a flashpoint under 140 degrees F, or carrying enough fats, oils, grease or solids to block or damage the sewer. It also bars unapproved cooling water, condensate and stormwater. Class I industrial users face added metal limits.

Official Source
Mesa City Code, Title 8, Chapter 4, Section 8-4-15: Prohibited Substances and Discharge Limitations (Municode)
Mesa City Code 8-4-15, Prohibited Substances and Discharge Limitations
“Wastewater with a pH less than five (5.0) standard units (SU) or greater than ten and one-half (10.5) SU.”
Applies to:
Restaurants, car washes, labs, manufacturers, building owners, designers and plumbers on Mesa's sanitary sewer
Official fee:
not published in this section
In force:
Mesa City Code Title 8, Chapter 4 as amended by Ord. 5959 (8-25-25)
Last verified:
September 29, 2026, against the official page

Most drain problems come from what goes down them, and Mesa's code puts numbers on it. The list in 8-4-15 is short enough to post in a mechanical room, and a few of the limits are easy to break without noticing.

What does Mesa City Code 8-4-15 say?

Subsection (A) says no person may discharge into the public sewer any of the following:

  • Interference or pass-through. Wastewater that could disrupt the treatment plant or pass through it untreated.
  • Clear water. Storm water, surface water, groundwater, roof runoff, subsurface drainage, single-pass cooling water or condensate that may constitute inflow, unless the City Manager or Water Resources Director approves it.
  • Fire and explosion hazards. Pollutants with a closed cup flashpoint below 140 degrees F, or that push the sewer past 10 percent of the Lower Explosive Limit on any single reading.
  • Solids and grease. Solid or viscous pollutants, animal fats, oils and grease, petroleum oil or nonbiodegradable cutting oil "in amounts that will cause" interference, pass-through or obstruction.
  • Toxic or corrosive waters. Substances that injure the plant, cause corrosive structural damage, endanger people or produce toxic gases that threaten workers.
  • pH. Below 5.0 or above 10.5 standard units.
  • Heat. Above 150 degrees F, or in amounts that inhibit biological treatment. In no case may the temperature at the plant headworks exceed 104 degrees F.
  • Dilution. Wastewater diluted in place of pretreatment to meet a standard.
  • Hazardous waste. A non-domestic discharge with a hazardous waste characteristic, unless the city approves it in writing on request.
  • Named chemicals. Benzene above 35 micrograms per liter and chloroform above 2,000 in a grab sample, and zero for DDT, DDE, aldrin, lindane, heptachlor, PCBs and similar compounds.

Subsection (B) adds daily average limits for Class I industrial users, and for a Class II user the city names in writing: arsenic 0.13, cadmium 0.047, copper 1.5, cyanide 2.0, lead 0.41, mercury 0.0023, selenium 0.10, silver 1.2 and zinc 3.5 milligrams per liter. Subsections (C) through (E) add city-set limits, best management practices and mass limits set in permits.

What do the key terms mean?

  • POTW. The publicly owned treatment works, the city's sewers and treatment plants.
  • Interference and pass-through. Disrupting the plant's process, or letting pollutants through it.
  • Closed cup flashpoint. The temperature at which a liquid's vapors can ignite in a lab test. Lower means more flammable.
  • Class I, II, III. Mesa's industrial user classes. See the discharge permit page.

Who does this cover?

Every person discharging to Mesa's sewer, not only factories. The clear-water, temperature, pH and grease rules reach restaurants, car washes and any commercial building. The metal limits in (B) apply to Class I users, and to a Class II user only after a written city determination.

Quick check: is the discharge allowed?

SituationAllowed?Why
Wastewater leaving the site at 160 degrees FNoOver 150 degrees F (A)(7)
Floor drain receiving roof runoffNo, unless approved(A)(2)
Plating shop with 2.5 mg/L copper, Class INo(B)(3)(c) sets 1.5
Acid rinse at pH 4NoBelow 5.0
Grease reaching the sewer in amounts that block itNo(A)(4)
Single-pass cooling water into the sewerNo, unless approved(A)(2)

What does this look like in real life?

A steam kettle line. A kitchen drains hot condensate to the sewer. The limit is 150 degrees F at the point of entry, so the designer looks at cooling or tempering that flow before it leaves the building.

A car wash. If a cleaning product drives the wastewater below pH 5.0, the discharge is prohibited no matter how small the site is.

The edge case. A shop discharges very little, but one batch dumps a solvent with a low flashpoint. The rule says "in no case," with no minimum volume.

What should you do next?

  1. 1Walk the building's drains and list what each one receives: hot water, steam condensate, cooling water, rinses, oils.
  2. 2Check temperature and pH against the 150 degrees F and 5.0 to 10.5 limits.
  3. 3Send roof, cooling or condensate flows to an approved outlet, or ask the city for written approval.
  4. 4If you are in a regulated class, get the permit and its limits. See the discharge permit page.
  5. 5For a kitchen, size and maintain the grease interceptor.

What do people get wrong?

  • "Only industrial sites are covered." Subsection (A) says "no person."
  • "Hot water is harmless." Above 150 degrees F it is prohibited.
  • "The grease rule has a number." Mesa's text ties it to obstruction and interference, not a concentration.
  • "Chandler's pH limit applies." Mesa's window is 5.0 to 10.5.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
GilbertGilbert uses nearly the same numbers: pH between 5.0 and 10.5, a 140 degree F closed cup flashpoint floor, a 150 degree F wastewater ceiling and 104 degrees F at the treatment plant headworks.Gilbert Town Code 66-231
Verified September 29, 2026
ChandlerChandler's program page sets the pH window wider, 5.0 to 12.5, and adds a numeric grease limit: vegetable fats, oils and grease over 100 mg/L must not be discharged. Mesa's section limits grease by what it does to the sewer, not by a concentration.City of Chandler: Industrial Pretreatment Program
Verified September 29, 2026

This page explains the rule. The official text at the source above governs.