Buckeye City Code

Buckeye City Code 16-10-2: grease interceptor size, upkeep and records for restaurants

Verified October 4, 2026
In Short

Buckeye City Code 16-10-2(B) requires grease, oil and sand interceptors or traps where the water resources department finds them necessary, and never for private living quarters. Unless the director approves otherwise, an interceptor holds 750 to 2,500 gallons. The owner keeps it working at the owner's expense and keeps cleaning records on site for three years.

Official Source
Buckeye City Code, Chapter 16, Article 16-10, Section 16-10-2: Additional Pretreatment Measures (Municode)
Buckeye City Code 16-10-2(B), Control of Grease, Oil and Solids Discharges
“Unless approved by the director no interceptor installed pursuant to this section shall have a capacity less than 750 gallons nor greater than 2,500 gallons.”
Applies to:
Buckeye restaurants, commercial kitchens and other businesses with greasy or oily wastewater, plus the owners and contractors who install and maintain interceptors; not private living quarters or dwelling units
Official fee:
not published in this section
In force:
Buckeye City Code Chapter 16, Article 16-10 (Ord. No. 07-21, 4-6-2021); sized and installed per the city's building and plumbing code requirements, which is the 2024 IPC as amended in 15-2-4
Last verified:
October 4, 2026, against the official page

Buckeye prints both ends of the interceptor size range in one sentence. The floor is 750 gallons, which is higher than the 500-gallon floor Mesa and Goodyear use, and a kitchen that calculates smaller still needs the director's approval to go under it.

What does Buckeye City Code 16-10-2(B) say?

The section opens with the trigger. Grease, oil and sand interceptors or traps "shall be provided when, in the opinion of the water resources department, they are necessary for the proper handling of liquid wastes containing grease and/or oil in excessive amounts or any flammable wastes, sand and other harmful ingredients." The exception: interceptors are not required for private living quarters or dwelling units.

Then six rules follow:

  • Size and installation. When installed, interceptors or traps "shall be sized and installed in accordance with the city's building and plumbing code requirements" (B)(2).
  • Construction. Impervious material that can handle abrupt and extreme temperature changes, substantial construction, watertight, with easily removable covers that are gastight and watertight when bolted in place (B)(3).
  • Upkeep. The owner maintains the interceptor "in continuously efficient operation at all times," at the owner's expense (B)(4).
  • No dissolving additives. The use of chemicals, bacteria or other agents to dissolve grease or oil, or to clean interceptors or traps, "is specifically prohibited" (B)(4).
  • Capacity. The quote above: 750 to 2,500 gallons unless the director approves otherwise (B)(5).
  • Records. The owner keeps written records of all cleaning, repair, calibration and maintenance needed to show compliance, at the facility for at least three years, available to an authorized employee of the water resources department on request (B)(6).

Section 16-10-1(C) adds a plan step: detailed plans for pretreatment facilities and operating procedures are submitted to the director for review and "shall be acceptable to the director before such facilities are constructed."

What do the key terms mean?

  • Excessive amounts. Not defined. The water resources department's opinion decides whether your kitchen crosses the line.
  • Building and plumbing code requirements. Buckeye adopts the 2024 International Plumbing Code in 15-2-4. The city's amendments to it change Chapters 1, 3, 4 and 6 only (administration and fees, building sewer depth, drinking fountains, and fixture flow rates). None change Chapter 10 of the model code, which is the chapter on traps, interceptors and separators. For interceptor sizing, my reading is that this points to the model code's own chapter plus the 750 to 2,500 gallon limits in 16-10-2.
  • Director. The section uses both "director" and "water resources department." It does not define either term in this section, so ask the department who signs off on an approval.

Who does this cover?

Any Buckeye user whose wastewater carries grease or oil, flammable wastes, sand or other harmful ingredients in excessive amounts, and the department finds an interceptor necessary. In practice that is restaurants and other commercial kitchens. It does not cover private living quarters or dwelling units.

It does not tell you how often to pump. This section has no calendar, only "continuously efficient operation at all times."

Quick check: what applies to your interceptor?

SituationWhat 16-10-2 saysSource
New restaurant kitchen with heavy greaseInterceptor or trap required if the department finds it necessary(B)(1)
Home kitchenNot required for private living quarters or dwelling units(B)(1)
Calculated size is under 750 gallonsNeeds the director's approval to go below 750(B)(5)
Calculated size is over 2,500 gallonsNeeds the director's approval to go above 2,500(B)(5)
Enzyme or bacteria product added to cut pumpingSpecifically prohibited(B)(4)
Interceptor is overdue for cleaningMust stay in continuously efficient operation at all times(B)(4)
Inspector asks for service historyWritten records, kept at the facility three years, produced on request(B)(6)
Replacing or changing pretreatment equipmentPlans reviewed and acceptable to the director before construction16-10-1(C)

What does this look like in real life?

A new restaurant in a Buckeye strip center. The department decides an interceptor is necessary. The size comes from the plumbing code requirements, and it still has to fall in the 750 to 2,500 gallon range unless the director approves a different one.

A small bakery. Its kitchen calculates well under 750 gallons. The text of (B)(5) still sets 750 as the minimum, so the owner would need the director's approval for anything smaller.

The edge case. An owner starts dosing the interceptor with a bacteria product to stretch the time between cleanouts. In Buckeye that is the one thing the section bans by name, so the dosing stops even if the interceptor looks clean.

What should you do next?

  1. 1Ask Buckeye's water resources department whether it has found an interceptor necessary for your kitchen (B)(1).
  2. 2Get the size from the plumbing code requirements and confirm it sits between 750 and 2,500 gallons, or ask the director for approval in writing before you build.
  3. 3Submit the detailed plans and wait for the director's acceptance before construction (16-10-1(C)). The city's main line at City Hall, 530 E. Monroe Ave., is 623-349-6000, and The Landing office at 945 N. 215th Ave. Suite 137 is 623-349-6200.
  4. 4After startup, set a cleaning schedule that keeps the interceptor working at all times. The code gives no day count, and neighboring cities do (180 days in Goodyear and Glendale, for example).
  5. 5Start the record file on day one: date, what was cleaned or repaired, and who did it, kept at the facility for at least three years.

HQ Plumbing & Air repairs and inspects grease interceptors, and a separate pumper empties them first.

What do people get wrong?

  • Myth: the code sets a pumping schedule. It does not. It sets an outcome (continuous efficient operation) and a record rule.
  • Myth: enzyme dosing is a legal substitute for cleaning. Section 16-10-2(B)(4) prohibits the product use outright.
  • Myth: bigger is always safer. The 2,500 gallon ceiling applies unless the director approves otherwise.
  • Myth: the 500-gallon floor used in Mesa and Goodyear applies here. Buckeye's floor is 750.

Full text and source

The text above comes from Buckeye City Code 16-10-1, 16-10-2 and 15-2-4 on Municode, read on 2026-10-04. This page explains those sections, and the official text governs.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
GoodyearGoodyear sets a lower floor: a minimum 500-gallon and maximum 2,500-gallon interceptor sized by drainage fixture units, with a pump-out or clean-out at least once every 180 days unless the director authorizes otherwise in writing, and records kept at least three years.Goodyear City Code Article 12A-3
Verified October 4, 2026
MesaMesa also uses a 500 to 2,500 gallon range and a drainage fixture unit formula, and names laundries, restaurants, service stations, auto repair shops and carwashes as facilities that can be required to have an interceptor.Mesa City Code 8-4-22
Verified October 4, 2026
GlendaleGlendale requires every grease trap and interceptor to be pumped out or cleaned out completely at least once every 180 days, or more often if the city requires, unless the city directs otherwise in writing.Glendale City Code 33-238
Verified October 4, 2026

This page explains the rule. The official text at the source above governs.