Mesa City Code 8-1-8 lists the uses that need a backflow assembly at the service connection, and most commercial ones need a reduced pressure assembly (RPA). Restaurants, medical and dental buildings, car washes, laundries, buildings over three stories and multi-tenant buildings on one service all appear. Two or more listed uses on one service mean an RPA.
“a potential hazard to the public water system exists and the customer must insure that the backflow protection specified below, is in place and operating as designed at each service connection.”
- Applies to:
- Commercial and industrial property owners, tenants, property managers and contractors on Mesa's water system
- Official fee:
- not published in this section
- In force:
- Mesa City Code Title 8, Chapter 1 (Ord. 5909, 12-9-24); 2024 IPC Section 608 with Mesa amendments
- Last verified:
- September 29, 2026, against the official page
Mesa doesn't ask whether your business "seems risky." It hands you a list. Find your use on it and the required assembly is written next to it. The surprise is how much lands on the strictest device, the reduced pressure assembly.
What do Mesa City Code 8-1-3 and 8-1-8 say?
Section 8-1-3 is the rule: a backflow assembly "is required at every service connection" where the customer's water system poses a health, non-health or plumbing hazard, or where access is so restricted the city can't inspect. Dedicated landscape connections need one "regardless of classification as residential or commercial." Potable water can never connect directly to sewer-connected waste. Where it drains, it must go through an air gap.
Section 8-1-8 is the list. Uses that call for a reduced pressure assembly (RPA) include:
- restaurants and convenience stores
- medical and dental buildings, hospitals and assisted care
- car washes and commercial laundries
- buildings over three stories or 34 feet
- commercial or industrial buildings where one service feeds several tenants
- shell buildings, shopping centers on master meters and apartment complexes on master meters
- buildings with booster pumps, potable storage tanks, fountains or sewage ejectors
- cooling towers, boilers and chillers
- schools, colleges and veterinary clinics
Other rows use a lighter or different device: a dedicated landscape meter takes a pressure vacuum breaker (PVB), a fire sprinkler fed only by the city takes a double check (DCVA), and water trucks and tanks take an RPA or an air gap.
What do the key terms mean?
- RPA. A reduced pressure principle assembly, the heavy-duty device with a relief valve. It protects against both backpressure and backsiphonage.
- PVB and DCVA. Lighter assemblies for lower hazards. A PVB has to sit at least 12 inches above the downstream plumbing.
- Service connection. The point where Mesa's water meets the customer's system, so protection is generally at the meter, not at each fixture.
- Point-of-use protection. Extra protection at equipment inside the building. 8-1-3(D) lets the city require it on top of the service device.
Who does this cover?
Commercial and industrial customers on Mesa's water system, plus any home with a dedicated landscape meter. It also covers properties outside city limits that Mesa serves. It does not reach a single-family home with a standard domestic meter, unless something else on the property creates a cross-connection.
Quick check: which assembly for which use?
| Situation | Assembly | Why |
|---|---|---|
| Restaurant in a multi-tenant plaza | RPA | Restaurants are listed, and so is one service feeding several tenants |
| Office building, four stories | RPA | Over three stories or 34 feet |
| Dental or medical suite | RPA | Medical and dental buildings are listed |
| Landscape-only meter | PVB | Dedicated landscape meter |
| Landscape meter, PVB can't sit 12 inches above the downstream plumbing | RPA | Height rule in the table |
| Fire sprinkler on city water only, no additives | DCVA | Fire sprinkler row (see the fire line page) |
| Two or more listed uses on one service | RPA | The table's closing rule |
What does this look like in real life?
A dental office in a strip center. Medical and dental buildings are listed, so the service needs an RPA even if the suite is small.
A car wash. Car washes are listed, so the service gets an RPA at the meter. If the site also has an irrigation line, that line is protected too.
The edge case. A church has a dedicated irrigation meter. On flat ground a PVB works. On a berm where the PVB can't sit 12 inches above every downstream sprinkler line, the same customer needs an RPA.
What should you do next?
- 1Match every use on the property to the 8-1-8 table, or to the city's "Customers Requiring a Backflow Prevention Assembly" list linked from its backflow page.
- 2If two or more listed uses share one service connection, plan on an RPA.
- 3Show the assembly on the plumbing plans. The checklist requires backflow devices to be "reviewed and approved before installation": backflow@mesaaz.gov or 480-644-6462.
- 4Pull the permit through Development Services before installing a commercial or industrial assembly, as the city's backflow page requires.
- 5Have a Mesa-recognized tester test it and file the report. See annual testing.
What do people get wrong?
- "Our building is small, so a DCVA is fine." Size isn't the test. Use decides, and most listed commercial uses are RPA.
- "The landscape meter is covered by the building's device." Dual-use meters need the landscape line isolated with an RPA or PVB in addition to the service protection.
- "The city's page says 2006 IPC." That page still mentions it. Mesa Code 4-5-1 adopts the 2024 IPC, and 8-1 is the local chapter that governs this list.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Glendale | Glendale also lists activities and presumes a hazard, but assigns a lighter double check (DC) to shopping centers, dairies and buildings with house pumps or potable storage tanks. Restaurants and bakeries, multi-family and hotels get an RP. | Glendale City Code 33-90 Verified September 29, 2026 |
| Tempe | Tempe's table names car washes, laundries, food processing, hospitals, medical and dental buildings, shopping centers, mobile home parks and buildings over three stories or 34 feet, among others. It sets the assembly type row by row and splits tall buildings and pump buildings into low and high hazard. | Tempe City Code 33-105 Verified September 29, 2026 |
| Surprise | Surprise skips the by-use list for commercial: an approved backflow device is required on all commercial and industrial connections, and the city can require one anywhere it judges necessary. | Surprise City Code 58-260 Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- PhoenixCan you connect city water to a well or other water source in Phoenix?
More Mesa Codes and Permits
- Backflow PreventionMesa City Code 8-1-10: backflow rules for fire sprinkler systems
- Backflow PreventionMesa City Code 8-1-11: annual backflow testing, repair deadlines and who can test
- Backflow PreventionWho can test backflow assemblies in Mesa? City Code 8-1-12 recognized testers
- Backflow PreventionCan Mesa shut off your water for backflow violations? City Code 8-1-13
- Backflow PreventionWhich backflow device fits which hazard in Mesa, and where does it go? City Code 8-1-4 and 8-1-5
- Backflow PreventionMesa backflow assemblies on building plans, and new inspections when you add equipment: City Code 8-1-6 and 8-1-7
Related Rules and Questions
- ArizonaArizona Administrative Code R18-4-215: Backflow Prevention and Annual Testing
- UPCUPC Section 603: Cross-Connection Control and Backflow Protection
- ArizonaPhoenix City Code Ch. 37: Backflow and Cross-Connection Control
- FAQHow often does a commercial backflow preventer need testing in Arizona?
- FAQRPZ vs double-check backflow assembly: what's the difference?
- FAQWhat is backflow in plumbing?
- FAQDo I need a backflow preventer and annual test for my sprinklers in Arizona?
- Commercial Plumbing