Mesa matches the device to the hazard: an RPA or air gap for health hazards and backpressure, a DCVA only for non-health hazards, and PVB or SVB for backsiphonage only. Install the service assembly at or near the point of delivery and before the first branch line, at least as large as the service, at the customer's cost.
“the Department reserves the right to require backflow protection, based on the degree of hazard, to the public water system from a customer water system, regardless of the nature of the customer's end use.”
- Applies to:
- Designers, plumbers, property managers and owners choosing or installing backflow assemblies in Mesa
- Official fee:
- not published in these sections
- In force:
- Mesa City Code Title 8, Chapter 1 (Ord. 5909, 12-9-24)
- Last verified:
- September 29, 2026, against the official page
Choosing a backflow device is a matching game, and Mesa publishes the answer key. The hazard decides the device, and the installation rules decide where it goes and how big it is.
What do Mesa City Code 8-1-4 and 8-1-5 say?
Section 8-1-4 says that, in addition to the lists in 8-1-8 and 8-1-9, the Department may require protection "based on the degree of hazard," using three factors: health, non-health, and plumbing hazard within the customer's system. Its table shows what each assembly protects against:
| Assembly | Non-health hazard | Health hazard | Sewage or reclaimed water |
|---|---|---|---|
| Air gap | Backsiphonage and backpressure | Backsiphonage and backpressure | Backsiphonage and backpressure |
| RPA | Backsiphonage and backpressure | Backsiphonage and backpressure | Not listed |
| DCVA | Backsiphonage and backpressure | Not listed | Not listed |
| PVB | Backsiphonage only | Backsiphonage only | Not listed |
| SVB | Backsiphonage only | Backsiphonage only | Not listed |
The Department may approve an alternative assembly that holds a Certificate of Approval from the USC Foundation for Cross-Connection Control and Hydraulic Research or another certifying body unrelated to the manufacturer and accepted in the industry (B). An air gap may be used inside a customer system if it is unmodified and matches the definition in 8-1-1 (C).
Section 8-1-5 sets the install rules:
- Who pays (A). The customer, at their own expense, to the Mesa Building, Plumbing and Fire Code standards.
- Where (B). "At, or as close as possible to, the point of delivery," and always before the first branch line that splits the customer water system.
- How big (C). At least the cross-sectional diameter of the service connection, unless the Department approves otherwise in writing.
What do the key terms mean?
- Backsiphonage. Water pulled backward by low pressure in the supply.
- Backpressure. Pressure in the customer's system higher than the city's, pushing water back.
- Health hazard. A condition that could contaminate the water, versus a non-health hazard that could only pollute it.
- Point of delivery. Defined in 8-1-1 as the downstream end of the water meter, where the city-owned system ends. For an unmetered service such as a fire line, it is just downstream of the valve separating the city-owned part.
Who does this cover?
Anyone choosing an assembly in Mesa. It applies to service protection and, with 8-1-9, to devices at equipment. The table's "not listed" cells mean the code does not credit that assembly with that protection.
Quick check: which device for which hazard?
| Situation | Device | Why |
|---|---|---|
| Non-health hazard, possible backpressure | DCVA, RPA or air gap | DCVA covers both for non-health |
| Health hazard, possible backpressure | RPA or air gap | DCVA is not listed for health |
| Health hazard, backsiphonage only | RPA, air gap, PVB or SVB | Vacuum breakers cover backsiphonage |
| Sewage or reclaimed water | Air gap only | Only column with just the air gap |
| Service assembly location | At the meter, before the first branch | 8-1-5(B) |
| Assembly smaller than the service | Needs written approval | 8-1-5(C) |
What does this look like in real life?
A restaurant. Its service qualifies for an RPA under 8-1-8. The plumber sets it at the meter, before any branch feeds the kitchen, and sizes it to match the service line.
A landscape line. A PVB works where only backsiphonage is a risk and the assembly can sit above the downstream piping. See the 8-1-8 use list.
The edge case. A contractor proposes a smaller RPA to save money on a 2 inch service. Section 8-1-5(C) says the assembly must be at least as large as the service unless the Department approves in writing.
What should you do next?
- 1Identify the hazard level and the kind of backflow risk for each connection.
- 2Pick from the 8-1-4 table, or the assembly named for your use in 8-1-8 or 8-1-9.
- 3Locate the service assembly at the point of delivery, ahead of the first branch.
- 4Match its size to the service, or get written approval for a smaller one.
- 5Show the make, model and size on the plans and have a recognized tester test it.
What do people get wrong?
- "A DCVA is fine for anything that is not sewage." It is not listed for health hazards.
- "Put it wherever there is room." The rule is at the point of delivery and before the first branch.
- "Downsizing the device is a value engineering win." It needs written approval.
- "Any certified device works." The Department approves assemblies, and alternatives need an independent certificate.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Phoenix | Phoenix requires a permit from Planning and Development for the installation of any backflow assembly, testing at least once a year by a certified tester, and repair by a certified repairer to the ASSE 5130 standard. Assemblies are installed at the customer's expense to the city's adopted standards. | Phoenix City Code 37-141 Verified September 29, 2026 |
| Chandler | Chandler's Director may order a customer in writing to install an approved device at each service connection, and the customer must do so at once and at their own expense. Where reclaimed water is available as an auxiliary supply, an RP device is the approved one. | Chandler City Code 52-34.2 and 52-34.3 Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- PhoenixCan you connect city water to a well or other water source in Phoenix?
More Mesa Codes and Permits
- Backflow PreventionMesa City Code 8-1-10: backflow rules for fire sprinkler systems
- Backflow PreventionMesa City Code 8-1-11: annual backflow testing, repair deadlines and who can test
- Backflow PreventionWho can test backflow assemblies in Mesa? City Code 8-1-12 recognized testers
- Backflow PreventionCan Mesa shut off your water for backflow violations? City Code 8-1-13
- Backflow PreventionMesa backflow assemblies on building plans, and new inspections when you add equipment: City Code 8-1-6 and 8-1-7
- Backflow PreventionWhich Mesa businesses must have a backflow assembly? City Code 8-1-8