Mesa requires every backflow assembly to be tested and serviced once a year before the city's compliance date, by a Mesa-recognized tester, at the customer's cost. A defect found between tests must be repaired within 15 days, a repaired assembly retested within 24 hours, and each test record filed within 7 days.
“The customer must cause all backflow prevention assemblies to be tested and serviced at least once each year prior to the compliance due date.”
- Applies to:
- Owners, tenants, property managers and testers for any backflow assembly on Mesa's water system, commercial or residential
- Official fee:
- The backflow compliance late fee is set in Mesa's Utility Service Fees schedule
- In force:
- Mesa City Code Title 8, Chapter 1 (Ord. 5909, 12-9-24); test procedure per USC Manual of Cross-Connection Control, 10th ed.
- Last verified:
- September 29, 2026, against the official page
Mesa's testing rule puts the duty on the customer and the clock on the calendar. A test, a repair, a retest and a report each have their own deadline, and any one of them can trigger the city's late fee.
What does Mesa City Code 8-1-11 say?
The customer is "the responsible party" to make sure the assembly works, is tested by the compliance date and that the city has the report. The section then sets the sequence:
- Yearly. Test and service every assembly at least once a year before the compliance due date, at the customer's expense (C, D).
- Recognized tester only. A tester on the city's list, following section 9 of the USC Manual of Cross-Connection Control, 10th edition (E, F).
- Failed at the annual test. Repair or replace by the compliance due date (G).
- Found defective between tests. Repair within 15 calendar days of discovery (H).
- After any overhaul, repair or replacement. Retest within 24 hours (I).
- Report. Submit the testing record within seven calendar days, or by the compliance due date if that comes sooner. Missing it means the backflow compliance late fee and possible civil sanction under 8-1-16 (J).
What do the key terms mean?
- Compliance due date. Not defined in the section. The city sends notices telling regulated customers when their annual test is due, so treat the notice date as yours.
- Recognized tester. Under 8-1-12, a certified tester who has filed Mesa's tester application, signed the City of Mesa Backflow Assembly Tester Agreement, and submitted a current gauge calibration report. Testers who lose certification, or whose equipment report is over a year old, are removed from the list.
- Serviced. The code pairs "tested and serviced," and doesn't spell out what service means beyond keeping the assembly working as the manufacturer designed it (B).
Who does this cover?
Every customer with a backflow assembly on Mesa's water system, residential or commercial, including landscape-only meters. It doesn't cover a property with no assembly. Whether you need one is the 8-1-8 list.
Quick check: which deadline are you on?
| Situation | Deadline | Why |
|---|---|---|
| Annual notice arrives | Test before the compliance due date | 8-1-11(C) |
| Assembly fails the annual test | Repair by the compliance due date | 8-1-11(G) |
| You spot a leaking relief valve in July | Repair within 15 calendar days | 8-1-11(H) |
| A tester rebuilds the assembly | Retest within 24 hours | 8-1-11(I) |
| Test completed | Record filed within 7 days | 8-1-11(J) |
| You add equipment that could create a cross-connection | New city inspection within 30 days | 8-1-7(C) |
| City inspection notice lists deficiencies | Correct within 60 days | 8-1-7(B) |
What does this look like in real life?
A restaurant with an RPA. The notice lands in spring. The tester runs the test, the relief valve fails, and the owner has until the compliance due date to repair it. The repair triggers the 24 hour retest.
A landscape meter at an HOA. The test passes in March. The tester submits the record to Mesa's backflow portal within seven days. The board still owns the duty to confirm Mesa received it.
The edge case. A property manager finds a dripping assembly in August, well before any test is due. The 15 day clock starts on discovery, not on the next notice.
What should you do next?
- 1Watch for the city's annual test notice and note the compliance due date on it.
- 2Pick a tester from Mesa's lists, general or fire contractor, linked on the city's backflow page. Anyone not on the list can't test in the city.
- 3Schedule the test early enough to leave room for repair and the 24 hour retest.
- 4Confirm the tester files the record on the city's backflow portal within seven days, and keep your own copy.
- 5Questions: backflow@mesaaz.gov or 480-644-6462, Monday to Thursday 6:00 am to 4:30 pm.
What do people get wrong?
- "The tester filed it, so I'm covered." 8-1-11(A) makes the customer responsible for the city receiving the report.
- "Any certified tester will do." 8-1-12 says anyone performing backflow maintenance and testing within the City must be recognized by Mesa.
- "I wait for the notice." The yearly duty is in the code. The notice is a reminder, and a defect between tests has its own 15 day clock.
- "A repaired assembly can wait for next year's test." It needs a retest within 24 hours.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Scottsdale | Scottsdale also tests yearly, but on a notice from the city, and gives 45 days from that notice to repair or replace a failed assembly. Records go to the city within 7 days, and only certified, approved testers may install, test, repair or replace. | Scottsdale City Code 49-65 Verified September 29, 2026 |
| Tempe | Tempe tests at installation and at least yearly on the anniversary of the first inspection. The user must give the city 15 days notice before each annual test so it can witness. After any repair, overhaul or relocation, the city inspects and a certified tester retests. | Tempe City Code 33-107 Verified September 29, 2026 |
| Gilbert | Gilbert tests at installation and at least annually. Double check assemblies get required service within 15 days, and any defective assembly must be repaired or replaced within 45 days. Testers need written approval from the town. | Gilbert Town Code 10-95 Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- PhoenixCan you connect city water to a well or other water source in Phoenix?
More Mesa Codes and Permits
- Backflow PreventionMesa City Code 8-1-10: backflow rules for fire sprinkler systems
- Backflow PreventionWho can test backflow assemblies in Mesa? City Code 8-1-12 recognized testers
- Backflow PreventionCan Mesa shut off your water for backflow violations? City Code 8-1-13
- Backflow PreventionWhich backflow device fits which hazard in Mesa, and where does it go? City Code 8-1-4 and 8-1-5
- Backflow PreventionMesa backflow assemblies on building plans, and new inspections when you add equipment: City Code 8-1-6 and 8-1-7
- Backflow PreventionWhich Mesa businesses must have a backflow assembly? City Code 8-1-8
Related Rules and Questions
- ArizonaArizona Administrative Code R18-4-215: Backflow Prevention and Annual Testing
- ArizonaPhoenix City Code Ch. 37: Backflow and Cross-Connection Control
- FAQHow often does a commercial backflow preventer need testing in Arizona?
- FAQRPZ vs double-check backflow assembly: what's the difference?
- FAQWhat is backflow in plumbing?
- Commercial Plumbing