Which backflow device does a Chandler business need?

Verified October 4, 2026
In Short

Chandler picks the backflow device by hazard, not by business type. Health hazards, auxiliary water supplies and uncontrolled cross-connections need an air gap or a reduced pressure principle (RP) assembly. A substance that is objectionable but not hazardous to health needs a double check valve assembly. City Code 52-36(D) sets the rules.

Official Source
Chandler City Code 52-36: Policy (Cross-Connection Control, Municode)
Chandler City Code 52-36(C) to (F) and 52-1
“the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention device.”
Applies to:
Commercial and industrial owners, tenants, designers and plumbing contractors on Chandler water service
Official fee:
not applicable
In force:
Chandler City Code 52-36 (last amended Ord. 4802, 2018) and 52-1
Last verified:
October 4, 2026, against the official page

Most cities hand you a list of businesses and the device each one needs. Chandler does not. Section 52-36 sorts premises by how dangerous the water could be if it flowed backward, and then names the device for each hazard.

What does Chandler City Code 52-36 say about which device to use?

Subsection (D) opens with "The type of protective device required shall depend upon the degree of hazard which exists." The first rule is the one quoted above: where a premises has an auxiliary water supply and no other rule below applies, the city system is protected by an approved air gap or an approved reduced pressure principle device. The other five rules:

  • Objectionable, not hazardous (D2): water or a substance that would be objectionable but not hazardous to health, if it got into the public system, needs an approved double check valve assembly.
  • Dangerous to health (D3): any material dangerous to health that is handled in a way that creates an actual or potential hazard needs an air gap or RP device. The code's examples are chemical manufacturing plants, hospitals, mortuaries, plating plants, sewage treatment plants and sewage pumping stations.
  • Uncontrolled cross-connections (D4): actual or potential ones need an air gap or RP device at the service connection.
  • Cannot be surveyed (D5): where security or other restrictions make a complete in-plant survey impossible or impracticable, the code requires maximum protection, an air gap or RP device on each service.
  • Tankers and spray tanks (D6): an air gap or RP device.

Subsection (C) is the trigger. A device goes on each service line before the first branch line when the premises has an auxiliary supply that may not be safe, handles industrial fluids or another objectionable substance in a way that creates an actual or potential hazard, or has internal cross-connections that cannot be permanently corrected and controlled, or plumbing too intricate to inspect.

What do the key terms mean?

Chandler defines most of them in 52-1, so you do not have to guess.

  • Air gap: an unobstructed vertical distance through free air. The approved gap is at least double the diameter of the supply pipe, measured above the vessel's overflow rim, and never less than one inch.
  • Reduced pressure principle (RP) device: two check valves with a differential relief valve between them, shutoff valves on each side and test cocks.
  • Double check valve assembly: two check valves with a shutoff valve at each end. Chandler also defines a double check-detector check assembly, and says it protects only against a nonhealth hazard.
  • Atmospheric vacuum breaker: protects against a health hazard under back-siphonage only.
  • Auxiliary water supply: any supply on the premises other than the city's approved potable supply, such as a well, spring, treated effluent or "industrial fluids."
  • "Objectionable but not hazardous": the code does not define the phrase beyond 52-1's "pollutant" hazard, a nuisance or aesthetically objectionable condition that is not dangerous to health. Treat any example you hear as a reading, not the code.

Who does this cover, and who does it not?

Section 52-36 speaks of premises, not of commercial buildings. Chandler 52-1 defines residential as single-family homes, duplexes and triplexes. The rule does not apply the same way to an older device that was approved when installed and has been properly maintained. Subsection (I) lets it stay, except for the inspection and maintenance requirements, so long as the Director is assured it will protect the utility system. If the device is moved, needs more than minimum maintenance or the Director finds the maintenance a health hazard, it must be replaced with one that meets the section.

Quick check: which rule fits the premises?

SituationDeviceWhy
Well or other auxiliary supply the Director does not acceptAir gap or RP52-36(C)(1) and (D)(1)
Substance objectionable but not hazardous to healthDouble check valve assembly52-36(D)(2)
Plating plant, hospital, mortuary, chemical plantAir gap or RP52-36(D)(3), named examples
Uncontrolled cross-connection, actual or potentialAir gap or RP at the service connection52-36(D)(4)
Secure site the city cannot surveyAir gap or RP on each service52-36(D)(5)
Plumbing too intricate or inaccessible to inspectA device in the service line52-36(C)(3)
Water cannot be shut off for testingTwo sets of assemblies in parallel52-36(E)
Fire line assemblyAlso needs UL-FM approval52-36(F)

What does this look like in real life?

A plating shop in a new industrial unit. Plating plants are named in (D)(3). The plans show an air gap or RP device, and the model and size have to be approved by the Director.

A tenant with an objectionable-but-harmless process. If the Director finds a substance that would spoil the water without endangering health, (D)(2) calls for the double check assembly, not the RP. The code leaves it to the city to decide which side of that line a process falls on.

A plant that cannot go dry. A facility that needs water around the clock cannot shut down for the annual test. Subsection (E) requires two sets of assemblies in parallel there, and each must be at least the cross-sectional area of the service or meter.

The edge case: the grandfathered device. A building has a device installed under an older standard. It stays under (I) until it is moved or needs more than minimum maintenance, and then it comes out. Glendale's 33-97(b) works the other way and requires non-complying devices to be replaced.

What should you do next?

  1. 1Ask for the city's approved assemblies list. Section 52-36(F) says it is made available on written request to the department, and 52-36(J) says the city furnishes the list to any customer required to install an assembly.
  2. 2Choose the device by the hazard rule above and size it to at least the water service or meter.
  3. 3Show the assembly on the plans (see our page on 52-36(H) backflow assemblies on building plans). Questions go to the Plan Reviewer of the Day at 480-782-3078.
  4. 4After it is installed, book the annual test with a tester from the city's list and send the passing report to Chandler Backflow Reports, 480-782-3665.

What do people get wrong?

  • Myth: Chandler has a list of businesses like Scottsdale. It does not. Scottsdale's 49-62(a) lists activities and the assembly for each. Chandler decides by hazard and names only examples.
  • Myth: Every device in a commercial building is an RP. A double check valve assembly is the rule for an objectionable, non-health substance.
  • Myth: Any gap counts as an air gap. Chandler's 52-1 sets the measure at double the supply pipe diameter, and never under one inch.
  • Myth: Fire line devices follow the same approval. They also need UL-FM approval under 52-36(F).

This page explains the code. The adopted text on Municode governs.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
ScottsdaleScottsdale lists activities and names the assembly for each, such as RP for restaurants, car wash facilities and beauty shops. Chandler's 52-36 names no business types except as examples of premises with a health hazard.Scottsdale Revised Code 49-62(a)
Verified October 4, 2026
MesaMesa publishes a table by hazard class and flow direction. Only an air gap or RPA covers a health hazard with backpressure, and a double check valve (DCVA) covers a non-health hazard. For sewage or reclaimed water the table shows an air gap only.Mesa City Code 8-1-4
Verified October 4, 2026
GlendaleGlendale defines an air gap as at least double the supply pipe diameter and never less than one inch, the same measure Chandler's 52-1 uses, and keeps a business-by-business list in 33-90.Glendale City Code 33-89 and 33-90
Verified October 4, 2026

This page explains the rule. The official text at the source above governs.