Avondale City Code 24-6 and 24-7: which backflow assembly you need and where it goes

Verified October 4, 2026
In Short

Avondale's code has no list of business types that need backflow assemblies. Under City Code 24-6, the city decides the method from the activities on the premises: an air gap for hazardous activities, a reduced-pressure assembly on every domestic connection near the meter, and double check assemblies on water-only fire sprinkler lines.

Official Source
Avondale City Code, Chapter 24, Article I, Section 24-6: Backflow prevention methods; approved (Municode)
Avondale City Code 24-4 to 24-8 (backflow method, installation and fire sprinkler connections)
“A reduced-pressure assembly is required at all direct connections to the public potable water supply for domestic use as close to the meter as feasible.”
Applies to:
Avondale property owners, contractors and tenants installing or replacing a backflow assembly on a city water service
Official fee:
Backflow Permit Fee $50.00 each (Avondale FY 2026 Rates & Fees Schedule, effective 9/1/2025); separate public works permit lines also exist, see below
In force:
Avondale City Code Chapter 24, Article I, enacted by Ord. No. 1572-315 (3-16-15); a local ordinance, not a model plumbing code section
Last verified:
October 4, 2026, against the official page

Most Valley cities hand you a table of business types and the assembly each one needs. Avondale does it differently. The code names the method for each kind of hazard, and the city decides which hazard your property has.

What do Avondale City Code 24-4, 24-6 and 24-7 say?

Section 24-4(a) starts the process: "An approved backflow prevention method shall be utilized or installed at every water service connection to a customer's water system when the director determines" that the public water could be contaminated by conditions inside the customer's system. Section 24-4(b) then says the department decides the method, sized to the hazard.

Section 24-6 ranks the approved methods from most to least restrictive:

"A reduced-pressure assembly is required at all direct connections to the public potable water supply for domestic use as close to the meter as feasible."

That is item (2). The full ladder in 24-6(b):

  1. 1Air gap. Required when hazardous activities are conducted and served by the same water service connection or by multiple connections.
  2. 2Reduced-pressure assembly (RPA). Required at all direct domestic connections, as close to the meter as feasible.
  3. 3Reduced-pressure detector assembly (RPDA). Required on all fire systems that use chemical additives for fire suppression.
  4. 4Double check valve assembly (DCVA). Required on all fire systems supplying water only to fire sprinkler systems.

If several activities share one premises, 24-6(a) applies the most restrictive method required for any of them to each water service connection. Section 24-7 covers installation: the customer installs the assembly at the customer's expense, in an accessible location the department approves, "as close to the water service connection as possible."

What do the key terms mean?

  • Direct connection for domestic use. The code does not define it. The practical reading is the ordinary service line that feeds a building's sinks, toilets and water heater. That is a reading, not a definition.
  • Hazardous activities. Not defined by a list. Section 24-5 sorts hazards into four factors (health, plumbing, pollution and system), and ties the health factor to "the judgment of the director."
  • Department and director. Section 24-1 defines the department as the Avondale Public Works Department and the director as the person in charge of it or a designee.

Who does this cover?

Section 24-3 says the article applies to all new and existing customers, and that backflow assemblies installed before the article that do not comply "shall be replaced with approved backflow prevention assemblies." That puts old, non-conforming assemblies in scope, not just new installs.

It does not make every property need an assembly. The trigger in 24-4 is the director's determination about a hazard.

Quick check: which assembly and where?

SituationWhat 24-6 and 24-7 point toSource
Domestic service line to a restaurant, shop or officeRPA, as close to the meter as feasible24-6(b)(2)
Hazardous activities on the premisesAir gap24-6(b)(1)
Several activities on one premisesThe most restrictive method required for any of them24-6(a)
Fire system with chemical additivesRPDA24-6(b)(3)
Fire system that supplies only sprinklersDCVA24-6(b)(4)
RPA or pressure vacuum breaker installationAbove grade level, between 12 and 24 inches24-7(c)
DCVA installationMay go below ground, at the customer's option, in a vault that meets city standards24-7(c)
Water supply that cannot be interrupted for testingTwo or more assemblies in parallel; the sum of their diameter areas must at least equal the service connection's24-7(e)
Assembly sizeDiameter at least equal to the water service connection24-7(d)

What does this look like in real life?

A new restaurant space. The domestic line gets an RPA near the meter. Section 24-7(f) says that after installation the customer must have an initial test on the assembly and have it inspected by the department "before the certificate of occupancy can be issued." The assembly is on the critical path to opening day.

A replacement. The old assembly was installed before the article took effect and does not meet it. Section 24-3(b) says non-complying assemblies "shall be replaced with approved backflow prevention assemblies."

The edge case. A buried-vault layout looks tidy, but 24-7(c) puts RPAs and pressure vacuum breakers above grade between 12 and 24 inches. Only the double check assembly gets the option of a below-ground vault, so a vault layout works for a double check assembly and not for an RPA.

What should you do next?

  1. 1Ask the Public Works Department which method it has determined for your connection (24-4(b)).
  2. 2Ask for its list of approved assemblies by type and manufacturer. Section 24-6(d) says the department furnishes it to any customer required to install one.
  3. 3Get the city backflow permit before work starts: 24-7(a) allows installation "only upon receipt of the necessary city backflow permit." Avondale's Development Services Department takes development applications online through the Accela Citizen Access portal and answers questions at (623) 333-4000, so start there to confirm the record type for a backflow permit.
  4. 4Check the fee on the city's FY 2026 Rates & Fees Schedule, which lists a Backflow Permit Fee of $50.00 each (Municipal Code 24-04). The same schedule also lists "Water - Backflow Preventer" lines of $75.00 (up to 3 inches) and $120.00 (3 inches and greater) and a Landscape Backflow Preventer line of $125.00. It does not say which line fits your assembly, so ask which one applies.
  5. 5Request the initial test and the department's inspection once the assembly is in, and do it early if a certificate of occupancy depends on it.

HQ Plumbing & Air installs, tests and replaces domestic backflow assemblies. Fire-line assemblies are outside what we do.

What do people get wrong?

  • Myth: only restaurants and factories need one. Section 24-6(b)(2) puts an RPA on every direct domestic connection, and 24-4 turns on the director's determination, not on a list of business types.
  • Myth: any location near the meter works. The RPA and pressure vacuum breaker rule is above grade, 12 to 24 inches.
  • Myth: the assembly is the end of it. Annual testing starts right after, and the Avondale annual testing page covers it.
  • Myth: a bypass is a shortcut. Section 24-7(h) makes bypassing a backflow prevention method unlawful and a misdemeanor, with an exception in 24-13(b).

Full text and source

The text comes from Avondale City Code 24-3 to 24-8 on Municode and the city's FY 2026 Rates & Fees Schedule, read on 2026-10-04. This page explains them, and the official text governs.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
MesaMesa works from a list of uses and facilities, each tied to the protection required. Buildings with booster pumps, commercial laundries and car washes are listed as RPA, and a fire sprinkler system with a direct connection and no additives is listed as DCVA.Mesa City Code 8-1-8
Verified October 4, 2026
TempeTempe lists premises (hospitals, shopping centers, mobile home parks and others) and says the type of assembly in its table is the minimum installation at each service connection to those premises.Tempe City Code 33-105
Verified October 4, 2026
ScottsdaleScottsdale presumes a potential hazard when any listed item or activity is on the premises and requires the listed assembly type at each service connection. Most listed items call for an RP assembly.Scottsdale City Code 49-62
Verified October 4, 2026

This page explains the rule. The official text at the source above governs.