Gilbert Town Code 10-92 requires an approved backflow assembly on each water service line, except single-family homes, before a certificate of occupancy issues. Subsection (c) lists 40 facility types: mostly reduced pressure (RP) assemblies, with double checks for tall buildings, laundries, food processing and medical and dental buildings.
“Buildings greater than three stories or greater than 34 feet in height from curb level”
- Applies to:
- Owners, tenants, designers, plumbing contractors and testers for commercial, industrial and institutional properties served by Gilbert water
- Official fee:
- not applicable
- In force:
- Gilbert Town Code Ch. 10, Art. III, Div. 2 (Ord. 869, 1994, Municode Supp. 103)
- Last verified:
- September 29, 2026, against the official page
Gilbert's backflow rule is a list. Section 10-92 says every water service line to a customer's system needs an approved assembly, then names 40 kinds of property and the type each one gets. The list is old (1994), and it does not read like Tempe's or Mesa's.
What does Gilbert Town Code 10-92 say?
The rule. Subsection (a) requires a backflow prevention assembly approved by the department on each water service line to a customer's water system, except single-family residences exempt under the state administrative code, section R18-4-115(C), which the state has since renumbered R18-4-215. For new service, the assembly goes in before a certificate of occupancy is issued for the structure.
The conditions. Subsection (b) adds when one is required regardless of type: premises with an auxiliary water system, premises with substances that can create a health hazard to the public supply, internal cross connections the officer judges not correctable, premises where a full cross connection survey is impossible or impractical, and premises with a repeated history of cross connections.
The list. Subsection (c) sets the types for facilities "including but not limited to" a list of 40 entries, "unless the officer determines an alternate type of protection is either required or adequate to protect the public water supply or that no actual or potential hazard to the public water supply system exists."
What do the key terms mean?
- RP (reduced pressure) assembly: two check valves with a relief valve between them. The strongest testable assembly.
- DC (double check) assembly: two check valves. Used where the hazard is lower.
- AG (air gap): a physical gap between the outlet and the water level. Listed as an alternative for water trucks and hydrant connections.
- Officer: the town's backflow officer, who can require a different type than the list shows.
Who does this cover?
Nearly every commercial, industrial and institutional customer. Single-family homes that state rules exempt are the only carve-out in (a). The list itself names the facility types, and the catch-all entry, "any premises where a cross connection is maintained", is RP.
Quick check: what does Gilbert list for this property?
| Property type | Assembly listed | Item |
|---|---|---|
| Hospital or mortuary | RP | (21) |
| Car wash with water reclamation | RP | (10) |
| Brewery | RP | (6) |
| Separate irrigation system (parks, schools, golf courses) | RP | (24) |
| Chemically treated water system | RP | (13) |
| Building over three stories or 34 feet | DC | (7) |
| Building with house pumps or a potable water storage tank | DC | (8) |
| Commercial laundry | DC | (14) |
| Food processing plant | DC | (18) |
| Medical or dental building, rest or convalescent home | DC | (22) |
| High school or college | DC | (19) |
| Water truck or hydrant connection | RP or AG | (38), (40) |
| Restaurant | Not named | Falls under the catch-all only if a cross connection is maintained |
What does this look like in real life?
A dental office in a strip center. Item (22) lists medical and dental buildings as DC. That is the minimum type. The officer can still require a stronger assembly if the plumbing calls for it.
A four-story office. Over three stories or 34 feet from curb level gets a DC. If the building also has house pumps or a storage tank, item (8) lists DC for that too.
The edge case: a restaurant. Gilbert's list does not name restaurants, and food processing plants are DC. A restaurant is not automatically exempt: the catch-all and subsection (b) apply where there is a cross connection or a health hazard, and the officer can require a type. Ask the backflow program before you finalize the plans.
What should you do next?
- 1Find your property type in the list. If it is not there, ask the backflow program which type the officer expects.
- 2Put the assembly on the plans for a new service and get it approved by the department.
- 3Plan for the assembly to be in, and inspected, before the certificate of occupancy.
- 4Hire a Town-recognized tester (the Backflow Prevention Department keeps the list) for the first test and the annual tests that follow. Gilbert's backflow program is on the town's website and at 480-503-6826.
- 5If you add a booster pump, tank, irrigation system or auxiliary water source later, recheck the list.
What do people get wrong?
- "RP and DC are interchangeable." The list names the type for each property, and the officer can require a different one.
- "If it is not on the list, I am exempt." The list says "including but not limited to", and the catch-all covers any cross connection.
- "Every Valley city lists the same properties." Tempe puts laundries and medical and dental buildings at RP where Gilbert lists DC, and Mesa and Scottsdale name restaurants where Gilbert does not.
- "A dental office is low hazard, so nothing is needed." It is on the list as DC.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Tempe | Commercial laundries and medical and dental buildings get a reduced pressure assembly where Gilbert allows a double check, and shopping centers are named. Restaurants are not named in either city. | Tempe City Code 33-105 Verified September 29, 2026 |
| Mesa | Restaurants and convenience stores are named and need a reduced pressure assembly; so does any commercial building where one service feeds several tenants. | Mesa City Code 8-1-8 Verified September 29, 2026 |
| Scottsdale | Restaurants and beauty shops are named on the list and get a reduced pressure assembly, as do buildings with sewage ejectors and cooling towers. | Scottsdale Revised Code 49-62 Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- MesaMesa City Code 8-1-10: backflow rules for fire sprinkler systems
- MesaMesa City Code 8-1-11: annual backflow testing, repair deadlines and who can test
More Gilbert Codes and Permits
- Commercial PlumbingHow often must a Gilbert restaurant pump its grease trap? Town Code 66-244(d) and (e)
- Commercial PlumbingGilbert Town Code 66-244: grease removal devices for restaurants and food service
- Commercial PlumbingGilbert Town Code 66-245: floor drains and wash racks at auto shops and car washes
- Permits and InspectionsGilbert Town Code 66-8: the permit to dig a street or alley for a water or sewer connection
Related Rules and Questions
- Valley-WideWhich Businesses Need a Backflow Assembly in Each Valley City
- ChandlerChandler backflow testing: annual test, notices and water shutoff
- FAQHow often does a commercial backflow preventer need testing in Arizona?
- FAQRPZ vs double-check backflow assembly: what's the difference?
- FAQWhat is a cross-connection and why is it dangerous?
- Commercial Plumbing