Valley cities on the 2024 IPC require cleanouts every 100 feet on building sewers under 8 inches, at the building drain and sewer junction, and at turns over 45 degrees. Sewers 8 inches and larger need manholes instead. Phoenix adds a two-way cleanout on the outlet of grease interceptors.
“A two-way cleanout shall be installed on the discharge side of all hydromechanical grease interceptors.”
- Applies to:
- Owners, property managers, tenants, designers and contractors of restaurants, retail centers, offices, warehouses and multifamily buildings with a private building sewer
- In force:
- 2024 International Plumbing Code as adopted by Phoenix (Ord. G-7397, with the 2024 UPC as an alternative), Mesa, Chandler, Glendale, Surprise and Tempe; other cities on earlier editions; local rules from each city or district
- Last verified:
- October 4, 2026, against the official page
What Does Each Valley City Require?
| Where | What applies | Source |
|---|---|---|
| Phoenix | Plans may follow the 2024 IPC or the 2024 UPC, both amended. The IPC amendment requires a two-way cleanout on the discharge side of all hydromechanical grease interceptors. The UPC amendments require one on separators, interceptors and clarifiers too, and a vented one on gravity grease interceptors. | Phoenix amendments to 2024 IPC 1003.3.5.3 and 2024 UPC 1014.2.3, 1014.3.5; Ord. G-7397 Verified October 4, 2026 |
| Mesa | Owners clean, unstop, maintain and repair the building connection to the public sewer, except that the city repairs a damaged or broken section located off-property in a street or alley. For a city blockage check, the form says the owner must provide access by a cleanout or an exposed service line. | Mesa City Code 8-4-8(E), (F); Sewer Blockage Inspection and Removal form (Rev. 6/2024) Verified October 4, 2026 |
| Chandler | On its pool-drainage page, the stormwater program says the city does not keep records of where sewer cleanouts sit on private property. It points owners who cannot find theirs to a plumber. | Chandler Stormwater Program, Pool Maintenance page (Sanitary Sewer Cleanout) Verified October 4, 2026 |
| Avondale | The engineering permit fees in the FY2026 schedule list sanitary sewer cleanouts, mains and service lines at $50.00 each for all users, under Resolution 3321-616. | Avondale FY2026 Rates and Fee Schedule, Sanitary Sewer Verified October 4, 2026 |
| Cave Creek | The under-slab inspection checklist calls for a cleanout every 100 feet and at each change of direction over 45 degrees, sewer pipe at least 12 inches deep, and an #18 gauge minimum tracer wire from the cleanout at the building drain and building sewer connection to the sewer tap. | Cave Creek Inspection Tutorial: Underslab Plumbing Verified October 4, 2026 |
| Fountain Hills | Before fill goes over under-slab plumbing, the builder calls the Fountain Hills Sanitary District for a sticker on the cleanout for the sewer tie-in, with all piping under test. The district also says cleanouts should keep a removable cap in place to contain odors. | Fountain Hills Minimum Required Inspections (2024); FHSD Odors, Backups, Roaches page Verified October 4, 2026 |
| Litchfield Park | Every new pool needs a sewer cleanout within 50 feet of the pool pumping equipment so an emptied pool can drain to the sewer. | Litchfield Park City Code 7-2-2(A)(1) Verified October 4, 2026 |
A commercial building sewer without enough cleanouts is a line nobody can clear without digging or pulling a toilet. The plumbing code each city adopts sets where cleanouts go. A few Valley cities and sewer districts add their own rules on top: a grease interceptor cleanout, a fee, a tracer wire or an inspection sticker.
Quick check: does your situation need a cleanout?
| Situation | Outcome | Why |
|---|---|---|
| Phoenix restaurant replaces a hydromechanical grease interceptor | Two-way cleanout on the outlet side | Phoenix IPC 1003.3.5.3 and UPC 1014.2.3 amendments |
| Phoenix restaurant installs a gravity interceptor, UPC design | Vented two-way cleanout on the outlet side | Phoenix UPC 1014.3.5 amendment |
| Private building sewer 6 inches, 230 feet long | Cleanouts at no more than 100-foot intervals | IPC 708.1.2 |
| Private building sewer 8 inches, same run | Manhole within 200 feet of the junction, then every 400 feet | IPC 708.1.2 |
| Two 60-degree turns 25 feet apart | One cleanout at the first turn serves both | IPC 708.1.4, 40-foot rule |
| Tenant improvement adds a sink off a threaded cleanout | Not allowed unless an equal cleanout is installed elsewhere | IPC 708.1.12 |
| Parking lot repaved over a sewer cleanout | Bring it to grade in a traffic-rated assembly | IPC 708.1.11, 708.1.11.2 |
| New casework built in front of a cleanout | Keep 18 inches clear (6-inch pipe or smaller) | IPC 708.1.10 |
Who does this apply to?
These rules cover the private drain and sewer piping a business owns: from the fixtures, through the building drain, out to where the building sewer meets the public main. They matter most when that piping is new, replaced, rerouted or added to, and when a tenant improvement moves fixtures or covers existing cleanouts.
Key terms
- Building drain: the lowest piping inside the building that collects waste and carries it to the building sewer just outside the wall.
- Building sewer: the private pipe from the end of the building drain to the public sewer or a private disposal system.
- Developed length: distance measured along the centerline of the pipe and fittings, not in a straight line across the lot.
- Two-way cleanout: a fitting that opens both upstream and downstream, so a cable or jetter can go either way.
- Hydromechanical grease interceptor: a compact, engineered interceptor that uses flow control and baffles to separate grease, often under a sink or in a small pit. A gravity grease interceptor is a large in-ground tank.
- Manhole: a large access structure that replaces cleanouts on sewers 8 inches and larger.
Which code sets the cleanout rules?
Phoenix lets plumbing plans follow either the 2024 International Plumbing Code (IPC) or the 2024 Uniform Plumbing Code (UPC). Mesa, Chandler, Glendale, Surprise and Tempe are on the 2024 IPC. Scottsdale and Queen Creek use the 2021 edition, and Gilbert and unincorporated Maricopa County are on 2018 editions. The numbers below come from the 2024 IPC, Section 708. The UPC counts turns differently; our cleanout code FAQ covers that version.
Where does the IPC require cleanouts?
Inside the building. Horizontal drains need cleanouts "at intervals of not more than 100 feet." A building drain may use manholes instead, spaced up to 400 feet apart.
Building sewers under 8 inches. A cleanout at least every 100 feet, measured along the pipe.
Building sewers 8 inches and larger. The code switches to manholes: "a manhole located not more than 200 feet" from the building drain junction "and at intervals of not more than 400 feet." This catches large retail centers, hospitals and warehouses with a long private main.
The junction. A cleanout "at the junction or within 10 feet" upstream of where the building drain becomes the building sewer. Removing a water closet does not count as access.
Turns. A change of direction over 45 degrees needs a cleanout, but one cleanout covers every such turn within 40 feet of developed length.
Size, clearance and access. A cleanout matches the pipe size but never needs to exceed 4 inches. It needs 18 inches of clearance in front for 6-inch and smaller pipe and 36 inches for 8-inch and larger. It cannot sit in a plenum, wall, floor/ceiling assembly or low crawl space. Below-grade cleanouts are extended up to grade, assemblies to ASME A112.36.2M go where vehicles drive, and indoor manholes need gas-tight covers that take tools to open.
What do Valley cities add?
Phoenix and interceptors. The IPC amendment requires a two-way cleanout "on the discharge side of all hydromechanical grease interceptors." The UPC amendment goes further, covering "all separators, interceptors, (clarifiers) and hydromechanical grease interceptors," and requires gravity interceptors to have "a vented two-way cleanout on the discharge side." Phoenix's stated purpose is "to provide an entry point to clean the line downstream of the device and back to the device."
Mesa and city crews. Owners maintain the building connection to the public sewer. The exception is a damaged or broken section "located off-property in a street or alley," which the city repairs. When the city checks a blockage, its form says "The Homeowner has to provide access to the service line, by clean out or exposed service only."
Chandler and records. Chandler "does not keep or maintain records detailing location information for a sewer cleanout on private property." On an older commercial site with no as-builts, a camera and locator are often the way to find the line.
Cave Creek and Fountain Hills inspections. Cave Creek's under-slab checklist wants a tracer wire from the junction cleanout "run with the piping to the sewer tap." In Fountain Hills, the builder calls the sanitary district for a sticker on the cleanout before fill goes in.
Avondale and Litchfield Park. Avondale's engineering permit fees list sewer cleanouts at $50.00 each. Litchfield Park requires a sewer cleanout within 50 feet of the pumping equipment on any new pool.
What does this look like in real life?
Same restaurant, two designs. A Phoenix restaurant replaces a failed hydromechanical interceptor. Under either code path it needs a two-way cleanout on the outlet. Its neighbor installs a new 1,000-gallon gravity interceptor. If the plans follow the UPC, Phoenix's amendment requires a vented two-way cleanout on the outlet. If they follow the IPC, the Phoenix amendment we reviewed names only hydromechanical interceptors, so the outlet line follows the general Section 708 rules.
Same warehouse, two pipe sizes. A Mesa warehouse runs a 6-inch private sewer 300 feet to the street: cleanouts at no more than 100-foot intervals. If the engineer upsizes to 8 inches for future tenants, the answer flips to manholes, the first within 200 feet of the junction.
A repaved lot. A Tempe retail center repaves its parking lot. Cleanouts in the drive aisle come up to the new grade in traffic-rated assemblies, not plastic caps paved over.
What do people get wrong?
- "The city knows where my cleanout is." Chandler states that it keeps no such records for private property. Ask your own city before you count on it.
- "A cleanout is a cleanout." Size and clearance scale with the pipe, and an 8-inch sewer needs manholes outside the building.
- "I can tie the new sink into that cleanout." The IPC prohibits using a threaded cleanout opening to add a fixture unless another cleanout of equal size is installed.
What should you do next?
- 1In Phoenix, file through the Planning and Development Department. The FOG manual says "all grease interceptors installed and replaced in the City of Phoenix must go through plan review." Like-for-like interceptor replacements can be reviewed over the counter by appointment. A new interceptor or major plumbing change goes through electronic plan review. Show the two-way cleanout on the drawings.
- 2In other cities, pull the plumbing permit before work starts. The permit holder schedules the inspection that covers the building sewer before it is covered. Cave Creek checks cleanouts, slope, depth and tracer wire at its under-slab inspection, and Fountain Hills needs the district's cleanout sticker first.
- 3Count the cleanouts against the run. Walk the building sewer from the building to the tap. Look for one at the junction, one at least every 100 feet, and one at each sharp turn.
- 4Check what sits on top of them. Pavers, planters, racks and new millwork are the usual reasons a required cleanout becomes unusable.
- 5Cap them. The Fountain Hills Sanitary District says cleanouts "should have a removable cap installed, to contain odors." A missing or cracked cap also lets debris in.
HQ Plumbing and Air installs and repairs cleanouts on commercial building sewers, and handles line clearing, camera inspection, and grease interceptor inspection and repair.
This page explains the rule. The official text at the source above governs.
- 2024 International Plumbing Code, Chapter 7, Section 708 Cleanouts (ICC)
- City of Phoenix amendments to the 2024 International Plumbing Code (Section 1003.3.5.3)
- Phoenix Construction Code History (TRT 00550), Ordinance G-7397
- Town of Cave Creek, Inspection Tutorial: Underslab Plumbing
- City of Phoenix amendments to the 2024 Uniform Plumbing Code (Sections 1014.2.3 and 1014.3.5)
- City of Phoenix Water Services: FOG Best Management Practices Manual (June 2024), Installation and Replacement of Interceptors
- City of Mesa Sewer Blockage Inspection and Removal form, quoting City Code 8-4-8(E) and (F)
- Fountain Hills Sanitary District: Odors, Backups, Roaches
- City of Avondale FY2026 Rates and Fee Schedule (Engineering Services permits)
Sewer Lines in Other Cities
- ChandlerDo you have to connect to Chandler city sewer if you have a septic tank? City Code 51-3
- ChandlerChandler sewer line responsibility: who repairs the pipe to the main
- ChandlerChandler sewer tap permit: what 51-7 and the street permit require
- Fountain HillsWhen does Fountain Hills require a sewer easement encroachment permit?
- GlendaleGlendale City Code 33-126 to 33-129: sewer tap permit and who digs
- GlendaleGlendale City Code 33-217: who repairs the sewer line from the building to the street
More Valley-Wide Codes and Permits
- Sewer LinesPrivate Sewer Lift Station and Ejector Rules by Valley City
- Sewer LinesWho Owns the Sewer Line From the Building to the Main, by City
- Commercial PlumbingWhich Businesses Need a Backflow Assembly in Each Valley City
- Gas LinesGas Line Permits in Each Valley City
- Gas LinesGas Line Burial Depth Rules in Each Valley City
- Gas LinesGas Line Pressure Test Rules in Each Valley City
Related Rules and Questions
- PhoenixWhich building and plumbing codes does Phoenix enforce?
- Valley-WideGrease Trap and Interceptor Rules by Valley City
- Valley-WideGrease Interceptor Records and Inspections by Valley City
- FAQWhere are sewer cleanouts required by code?
- FAQWhat is a sewer cleanout and where is it located?
- FAQCan a drain be hydro jetted when the property has no accessible cleanout?
- FAQCan a sewer line be camera inspected without a cleanout?
- FAQWhat should I do if sewage is coming out of the cleanout in my yard?
- FAQWhy is there a sewer smell outside near the cleanout?
- Commercial Plumbing