It depends on the city. Phoenix, Chandler and Buckeye test new gas piping at 1.5 times working pressure, never under 3 psig. Mesa, Gilbert and Queen Creek require at least 10 psi, and 60 psi for welded pipe or gas above 14 inches water column (Mesa 4-7-2, Gilbert 10-35-2, Queen Creek 7.2.6).
“The test pressure to be used shall be not less than 10 pounds per square inch (68.9 kPa) gauge pressure”
- Applies to:
- Gas contractors, plumbers, restaurant and building owners, and homeowners with new or altered natural gas or propane piping
- In force:
- International Fuel Gas Code: 2024 edition in Phoenix (Ord. G-7397, effective August 1, 2025), Chandler (Ord. 5108, effective July 1, 2025), Mesa (applications from January 8, 2026), Cave Creek (applications from January 1, 2026) and Buckeye; 2021 in Queen Creek; 2018 in Gilbert and unincorporated Maricopa County
- Last verified:
- September 29, 2026, against the official page
What Does Each Valley City Require?
| Where | What applies | Source |
|---|---|---|
| Phoenix | Phoenix amends Chapter 1 and Section 403.11 (flanges) of the 2024 IFGC but not Section 406, so the base test applies: 1.5 times working pressure, not under 3 psig; 10 minutes in a single-family home or under 10 cubic feet, otherwise half an hour per 500 cubic feet; mechanical gauges no more than five times the test pressure. | Phoenix 2024 IFGC amendments (Ord. G-7397) Verified September 29, 2026 |
| Mesa | At least 10 psi gauge, or 6 inches of mercury if the building official approves. Welded pipe and gas above 14 inches water column test at 60 psi or more. Dial gauges read in 0.1 psi steps up to 10 psi and top out at no more than twice the test pressure. 2024 IFGC. | Mesa City Code 4-7-2, IFGC 406.4.1, 406.4.3 Verified September 29, 2026 |
| Chandler | At least 1.5 times the maximum working pressure and never under 3 psig, held for 10 minutes or more. The test runs through the open valve and flex line, capped at the appliance connection. 2024 IFGC. | Chandler Homeowner Building Permit Manual, Gas Permits Verified September 29, 2026 |
| Gilbert | Air, CO2 or nitrogen at 10 psi or more, held at least 15 minutes with no perceptible drop, on a gauge in 0.10 psi steps. Welded pipe and gas above 14 inches water column: 60 psi for at least 30 minutes. Inspected before and after concealment. 2018 IFGC. | Gilbert Town Code 10-35-2, IFGC 406.4 as amended Verified September 29, 2026 |
| Queen Creek | Air, CO2 or nitrogen at 10 psi or more for at least 15 minutes, or 6 inches of mercury at the inspector's discretion. Welded pipe and gas above 14 inches water column: 60 psi for at least 30 minutes. Tests run in the inspector's presence. 2021 IFGC. | Queen Creek Town Code 7.2.6, IFGC 406.4 as amended Verified September 29, 2026 |
| Buckeye | At least 1.5 times the maximum working pressure and never under 3 psig, for 10 minutes, on an air gauge calibrated in 1/10 pound increments. 2024 IFGC. | Buckeye City Code 15-2-6, IFGC 406.4.1 as amended Verified September 29, 2026 |
| Cave Creek | The town's gas inspection checklist tests propane piping at 1.5 times operating pressure or more, not under 3 psi, for 10 minutes, never with oxygen, and tests only new pipe and additions. The checklist cites the 2021 IRC; the town applies the 2024 codes to permit applications from January 1, 2026. | Cave Creek Inspection Checklist: Fuel Gas Piping; Building and Fire Code Compliance page Verified September 29, 2026 |
| Maricopa County | Unincorporated areas: the installer keeps the system on a pressure test through the inspection or as the code prescribes. A permit and pressure test are needed for a utility clearance even when no new work was done. 2018 IFGC. | Maricopa County Inspection Services Guide, Gas Line Verified September 29, 2026 |
New gas piping has to hold air under pressure before an inspector signs off, but the Valley uses two different tests. Phoenix, Chandler and Buckeye use the 3 psig floor, as does Cave Creek's propane checklist. Mesa, Gilbert and Queen Creek start at 10 psi and jump to 60 psi for welded pipe or gas above about half a pound of pressure, which catches many commercial kitchens.
Where do these rules come from?
Section 406 of the International Fuel Gas Code (IFGC) sets the test, and each city can rewrite it. Phoenix's 2024 amendments change Chapter 1 and Section 403.11 (flanges) and leave Section 406 alone, so Phoenix runs the published test, the same one Chandler's permit manual prints: "no less than 1-1/2 times the proposed maximum working pressure, but no less than 3 psig."
Two more base rules apply wherever a city didn't replace them. Mechanical gauges need a scale "not greater than five times the test pressure." The hold is "not less than 1/2 hour for each 500 cubic feet (14 m3) of pipe volume or fraction thereof," dropping to 10 minutes for a system under 10 cubic feet or in a single-family dwelling. A large commercial system can need a much longer hold than a house.
Mesa, Gilbert and Queen Creek replaced that rule. Mesa's amendment reads: "The test pressure to be used shall be not less than 10 pounds per square inch (68.9 kPa) gauge pressure." Buckeye kept the 3 psig floor but wrote the 10 minute hold and gauge rule into its own amendment.
Editions differ too. Phoenix, Mesa, Chandler, Buckeye and Cave Creek (for applications from January 1, 2026) enforce the 2024 IFGC, Queen Creek the 2021, and Gilbert and unincorporated Maricopa County the 2018, each with local amendments.
What do the terms mean?
Five terms decide which test applies and how it is read.
- psig. Pounds per square inch on the gauge, above the air around it.
- Working pressure. The pressure the gas runs at in the building. A home runs a fraction of a pound; some commercial systems run at 2 psi or more.
- Inches of water column. A small pressure unit used for gas. Fourteen inches is about half a psi, the line where Mesa, Gilbert and Queen Creek switch to the 60 psi test.
- Manometer or slope gauge. A liquid gauge that reads very small pressure changes, used for the inches-of-mercury option.
- Concealment. Burying the pipe or closing it in a wall. The test happens before that.
Who do these rules cover?
Anyone installing or altering gas piping that needs a permit, natural gas or propane, home or business. Cave Creek's checklist limits the test to "new pipe and added to an existing system," so untouched pipe is not retested when a branch is added. The county adds a case people miss: "A permit and pressure test is needed to obtain a utility clearance, even if no new work was performed."
Quick check: what test will your job face?
The table shows each jurisdiction's floor; a plumber can always test higher or longer.
| Jurisdiction | Standard test | Hold time | High-pressure or welded pipe |
|---|---|---|---|
| Phoenix, Chandler | 1.5 times working pressure, 3 psig minimum | 10 minutes for a home or under 10 cubic feet; otherwise half an hour per 500 cubic feet | Same formula |
| Buckeye | 1.5 times working pressure, 3 psig minimum | 10 minutes (Buckeye amendment) | Same formula |
| Cave Creek (propane checklist) | 1.5 times operating pressure, 3 psi minimum | 10 minutes | Same formula |
| Mesa | 10 psi, or 6 inches of mercury if approved | Base rule: 10 minutes for a home or under 10 cubic feet, otherwise half an hour per 500 cubic feet | 60 psi |
| Gilbert | 10 psi, air, CO2 or nitrogen | 15 minutes, no perceptible drop | 60 psi for 30 minutes |
| Queen Creek | 10 psi, or 6 inches of mercury at the inspector's discretion | 15 minutes | 60 psi for 30 minutes |
| Unincorporated county | Pressure test through the inspection or as the code prescribes | Through the inspection | Per code |
Which gauge will the inspector accept?
The gauge has to be able to show a small drop. The base code caps a mechanical gauge at five times the test pressure, which is what Phoenix and Chandler use. Gilbert wants increments of 0.10 psi or less on the 10 psi test and 1 psi or less on the 60 psi test. Buckeye wants an air gauge "calibrated in 1/10 lb. increments." Mesa sets the steps by test pressure (one-tenth of a pound up to 10 psi, 1 pound up to 100 psi) and says test gauges "shall have a pressure range not greater than twice the test pressure applied." A 0 to 100 psi gauge fails a 10 psi test in Mesa and a 3 psig test under the base code.
In Gilbert and Queen Creek, "All necessary apparatus for conducting tests shall be furnished by the permit holder."
What does this look like in real life?
The working pressure and the address decide the test, as these three jobs show.
A restaurant in Mesa adds a fryer line on a 2 psi system. The gas runs above 14 inches water column, so the new piping tests at 60 psi, not 3 psig. The same job in Chandler tests at 1.5 times 2 psi, which is 3 psig.
A Gilbert homeowner runs a line to a fire pit. The installer puts 10 psi on the new pipe before the trench is backfilled and holds it at least 15 minutes, and the inspector comes back after the pipe is covered.
A county property gets its gas back after a shutoff. No pipe changed, but the county still wants a permit and a pressure test before it sends the utility clearance.
What should you do next?
Settle the test before the trench is dug, because the pipe has to stay open until it passes. The test itself is the licensed installer's job; never open or pressurize a live gas line yourself.
- 1Find who inspects the address. City limits decide it; unincorporated addresses go to Maricopa County.
- 2Pull the gas permit first. The gas line permit rules by city page shows each city's channel. The permit holder schedules the test inspection.
- 3Find the working pressure. Ask the gas utility what it delivers at the meter, or read the regulator's tag on an elevated-pressure system. It decides whether the 3 psig or the 60 psi rule applies.
- 4Make sure your installer's gauge fits the test (fine increments, a range no more than five times the test pressure, twice in Mesa) and that equipment left out of the test is "disconnected or isolated by blanks, blind flanges, or caps," as Cave Creek puts it.
- 5Request the inspection with the pipe exposed and the test on. Chandler takes requests by text to 844-281-3520 or online. Mesa takes them online, by phone or by text, weekdays 6:30 a.m. to 5:00 p.m. In unincorporated county, requests made online by 3:30 PM are inspected the next business day, or call 602-506-3301; only a listed contact on the permit can schedule.
What do people get wrong?
Most failed inspections trace back to one of these assumptions.
- "3 psi is the test everywhere." Mesa, Gilbert and Queen Creek start at 10 psi.
- "A commercial line tests like a house." Above 14 inches water column, those three towns want 60 psi.
- "Any gauge will do." The base code caps the scale at five times the test pressure, Mesa tightens that to twice, and Mesa, Gilbert and Buckeye set the increments.
- "No new pipe, no test." The county wants a pressure test for a clearance even with no new work.
- "Test it with gas." Gilbert and Queen Creek name air, CO2 or nitrogen; Cave Creek says oxygen is not allowed.
What happens if the test fails or is skipped?
The county is direct: gas "shall not be introduced into a piping system or appliance without first being tested, inspected and approved." Cave Creek's checklist says defective piping "shall be replaced and not repaired."
This page explains the rules; each city's adopted code and inspectors govern. HQ runs, repairs and pressure tests gas lines for homes and businesses across the Valley, with free estimates and 24/7 service.
This page explains the rule. The official text at the source above governs.
- Mesa City Code 4-7-2, 2024 IFGC amendments (406.4.1, 406.4.3)
- Technical Codes of the Town of Gilbert, Town Code 10-35 (IFGC 406.4 as amended)
- Queen Creek 2021 Building Code Amendments, Town Code 7.2.6 (IFGC 406.4 as amended)
- Chandler Homeowner Building Permit Manual, Gas Permits
- Maricopa County Planning and Development, Inspection Services Guide
- Phoenix Fuel Gas Code 2024 (IFGC 2024), Chapter 4, Sections 406.4 and 406.4.2 base text (UpCodes)
- Chandler Development Services, Inspections (text scheduling)
- Mesa Development Services, Residential Construction (inspection scheduling and hours)
- Cave Creek Building and Fire Code Compliance (2024 codes from January 1, 2026)
Gas Lines in Other Cities
More Valley-Wide Codes and Permits
- Gas LinesGas Line Permits in Each Valley City
- Gas LinesGas Line Burial Depth Rules in Each Valley City
- Gas LinesGetting Gas Turned On After Inspection in Each Valley City
- Commercial PlumbingWhich Businesses Need a Backflow Assembly in Each Valley City
- Commercial PlumbingGrease Interceptor Records and Inspections by Valley City
- Commercial PlumbingGrease Trap and Interceptor Rules by Valley City
Related Rules and Questions
- ChandlerWhich plumbing and gas codes does Chandler enforce?
- PhoenixWhich building and plumbing codes does Phoenix enforce?
- FAQHow does a gas line pressure test work?
- FAQDo I need a permit to install a gas line in Arizona, and who can do it?
- FAQWhat does a Southwest Gas red tag mean?
- FAQHow do I detect a gas leak, and what does repair involve?
- FAQCSST vs black iron gas pipe: which is better?
- Gas Line Repair & Installation
- Commercial Plumbing
