Under its 2024 amendments, Phoenix caps toilets at 1.28 gallons per flush, urinals at 0.5, private lavatory and sink faucets at 1.5 gpm and showerheads at 2.0 gpm. Buildings that meet exceptions 6 through 12 in the IPC and UPC, such as care facilities, tall buildings and some apartment buildings, use a second table with higher limits.
“Situations meeting exceptions 6 through 12 shall comply with Table 604.4(2).”
- Applies to:
- Designers, contractors, owner-builders and owners installing new or relocated fixtures under a Phoenix permit, residential and commercial
- Official fee:
- not applicable
- In force:
- 2024 IPC, 2024 UPC and 2024 IRC with Phoenix amendments, Ordinance G-7397, since August 1, 2025
- Last verified:
- October 4, 2026, against the official page
Phoenix wrote its water-saving fixture limits into all three plumbing codes it enforces, and the city's justification says the numbers are "consistent with the current EPA Water Sense standards." The twist is in the IPC and UPC versions: a set of buildings where Phoenix allows more water per minute, because its justification links slow-moving water in long piping, and some vulnerable occupants, to a higher risk of waterborne pathogens.
What does the Phoenix amendment say?
Phoenix adopted these changes with the rest of the 2024 codes under Ordinance G-7397, effective August 1, 2025. The IPC amendment splits Section 604.4 into two tables. Most buildings use Table 604.4(1). The exception text says exceptions 1 through 5 (blowout toilets up to 3 1/2 gallons, vegetable sprays, clinical sinks up to 4 1/2 gallons, service sinks and emergency showers) are not required to comply with either table, and "Situations meeting exceptions 6 through 12 shall comply with Table 604.4(2)."
| Fixture | Table 604.4(1), most buildings | Table 604.4(2), exceptions 6 to 12 |
|---|---|---|
| Lavatory, private | 1.5 gpm at 60 psi | 2.2 gpm at 60 psi |
| Lavatory, public (metering) | 0.25 gallon per cycle | 0.25 gallon per cycle |
| Lavatory, public (other) | 0.5 gpm at 60 psi | 0.5 gpm at 60 psi |
| Shower head | 2.0 gpm at 80 psi | 2.0 gpm at 80 psi |
| Sink faucet | 1.5 gpm at 60 psi | 2.2 gpm at 60 psi |
| Urinal | 0.5 gallon per flush | 1.0 gallon per flush |
| Water closet | 1.28 gallons per flush | 1.6 gallons per flush |
The UPC amendment carries the same split through Sections 401.3, 407.2.1, 408.3, 411.2, 412.1 and 420.2, with one difference: where exceptions 6 through 12 apply, UPC 408.3.1 lets showerheads and body sprays run up to 2.5 gpm at 80 psi.
The IRC amendment, for one- and two-family homes, has one table and no exceptions: lavatory faucets 1.5 gpm, shower heads 2.0 gpm, sink faucets 1.5 gpm and toilets 1.28 gallons per flushing cycle. It adds that "A hand-held shower shall be considered to be a shower head."
Which buildings get the higher limits?
Exceptions 6 through 12, in the city's words, cover:
- A building that "does not have a demand recirculation water system and includes one or more centralized potable water-heater systems serving two or more dwelling units or sleeping units."
- A building more than six stories above grade plane or more than ten stories.
- A building larger than 50,000 square feet with one or more potable water booster pumps.
- A facility where 5 or more people, excluding staff, receive custodial or medical care on a 24-hour basis.
- Buildings with surgery areas, or areas housing or treating people for burns, chemotherapy or organ or bone marrow transplants.
- Areas housing or treating people who are immunocompromised, on immune-suppressing drugs, or have renal disease, diabetes or chronic lung disease.
- Spaces whose primary purpose is housing occupants under 2 or over 65.
The UPC justification explains the reason: some situations "could potentially be at higher risk of waterborne pathogens," and "Higher flow rates help move this water through the system faster."
What do the key terms mean?
- gpm and gpf: gallons per minute for faucets and showers; gallons per flush (or flushing cycle) for toilets and urinals.
- Demand recirculation system: a hot water loop pump that runs on demand to bring hot water to fixtures. A central water heater serving several units without one is exception 6.
- Grade plane: the reference ground level used to count stories.
- Metering faucet: a self-closing faucet that delivers a set amount per push.
Who does this cover?
New and relocated fixtures installed under a Phoenix plumbing permit, in homes (IRC or the plumbing code the plans use) and in commercial buildings (IPC or UPC). Phoenix's Section 101.4.3 says the UPC or the IPC, as amended, applies to plumbing installations, so the code the plans follow decides which wording applies.
This does not apply to fixtures already in place. And the city's permit exemption in Section 105.2 for replacing toilets, valves or fixtures is limited to "new valves or fixtures complying with the water conservation requirements of this Code," so a swap still has to meet these limits.
Quick check: which limit applies?
| Situation | Limit | Why |
|---|---|---|
| New house, toilet | 1.28 gpf | IRC Table P2903.2 as amended |
| Office tenant improvement, kitchenette sink | 1.5 gpm | IPC Table 604.4(1) |
| 12-story apartment tower, private lavatories | 2.2 gpm | Exception 7, Table 604.4(2) |
| Group home where 6 residents receive 24-hour custodial care | Higher table | Exception 9, 5 or more people in 24-hour care |
| UPC-designed hotel with a central water heater and no demand recirculation, showers | Up to 2.5 gpm | Exception 6 with UPC 408.3.1 |
| Restaurant mop sink | Not covered by either table | Service sinks are exception 4 |
What does this look like in real life?
- A homeowner swaps an old 3.5-gallon toilet in the same spot. Section 105.2 says "Permits shall not be required for the following," and lists replacing water closets with fixtures "complying with the water conservation requirements of this Code." So the exemption only works if the new toilet meets 1.28 gallons per flush, and moving it needs a permit.
- A developer designs a 4-story apartment building with a central boiler. If it has no demand recirculation system, exception 6 applies and the fixtures follow the higher table. Add a demand recirculation loop and the answer flips back to Table 604.4(1).
- A senior living community. Exception 12 covers spaces whose primary purpose is housing people over 65, so 1.6-gallon toilets and 2.2 gpm faucets are allowed there.
What should you do next?
- 1Confirm which code the plans use: IRC for a house, or UPC or IPC for other buildings.
- 2Walk the seven exceptions against the building before you pick fixtures.
- 3Put the ratings on the plumbing sheets. The city's Commercial Building Permit Submittal Checklist lists, under "Plumbing Plan," "Plumbing fixture specifications," a "Plumbing fixture connection schedule" and a "Minimum plumbing fixture analysis." Put each fixture's gpm or gpf rating next to those entries; the checklist does not prescribe a ratings column.
- 4File through Phoenix Planning & Development (PDD). The checklist asks for owner or applicant information (name, address, phone and a contact person who is the owner or the owner's representative) and for contractor information (name, address, phone, license number and state privilege tax number), which it says is "Required for most projects by Arizona State Law." Commercial and multifamily plan review and permits are in the SHAPE PHX portal, which PDD says opened for them on April 27, 2026. House plans go through the portal's residential applications. The checklist gives PDD's address as 200 West Washington Street, 2nd Floor, Phoenix, AZ 85003, and (602) 262-7811 for questions.
- 5Buy fixtures rated at or below the limit for the table that applies.
- 6Keep the fixture spec sheets on site through the final inspection.
What do people get wrong?
- "1.6-gallon toilets are still the standard." In Phoenix, 1.6 is now only for buildings meeting exceptions 6 through 12; everywhere else it's 1.28.
- "The UPC and IPC limits match exactly." They match for most buildings, but under the exceptions the UPC allows showerheads up to 2.5 gpm while IPC Table 604.4(2) stays at 2.0.
- "Replacement fixtures don't have to comply." The permit exemption itself requires replacements that comply with the code's water conservation requirements.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | Mesa's amended IPC Table 604.4 sets the same main numbers: private lavatory and sink faucets 1.5 gpm at 60 psi, showerheads 2.0 gpm at 80 psi, urinals 0.5 gallon and toilets 1.28 gallons per flushing cycle. | Mesa City Code 4-5-2, IPC Table 604.4 as amended Verified October 4, 2026 |
| Glendale | Glendale's amended IPC 604.4 allows a little more at the kitchen sink, 1.8 gpm at 60 psi, with 1.5 gpm private lavatories, 2.0 gpm showerheads, 0.5 gallon urinals and 1.28 gallon toilets, and it excepts replacement of existing fixtures that do not require a permit. | Glendale City Code 9-21, IPC 604.4 as amended Verified October 4, 2026 |
This page explains the rule. The official text at the source above governs.
- City of Phoenix: 2024 IPC amendments, Section 604.4 (PDF)
- City of Phoenix: 2024 UPC amendments, Sections 401.3, 407.2.1, 408.3, 411.2, 412.1 and 420.2 (PDF)
- City of Phoenix: 2024 IRC amendments, Section P2903.2 (PDF)
- City of Phoenix: 2024 IBC Chapter 1 amendments, Sections 101.4.3 and 105.2 (PDF)
- City of Phoenix PDD: Commercial Building Permit Submittal Checklist (PDF, Rev. 06/25)
- City of Phoenix PDD: Commercial and Multifamily Building
Fixtures in Other Cities
- ChandlerChandler drinking fountain rules: when a water dispenser can replace one
- MesaWhat flow rates does Mesa allow for commercial faucets, toilets and urinals?
- ScottsdaleScottsdale Code 31-83: Bottle Fillers at Every Fountain and Water at Every Urinal
- GlendaleGlendale commercial restroom fixtures: City Code 9-35 flow limits, automatic faucets and the 1.6 gallon footnote
- Maricopa CountyHow many hand sinks and mop sinks does a Maricopa County restaurant need, and where?
More Phoenix Codes and Permits
- Permits and InspectionsWhich building and plumbing codes does Phoenix enforce?
- Commercial PlumbingCan a Phoenix business get an annual permit for plumbing alterations?
- Backflow PreventionDo you need a permit to install or replace a backflow preventer in Phoenix?
- Commercial PlumbingPhoenix City Code 28-12: Which businesses must install a grease or oil interceptor?
- Commercial PlumbingHow often must a Phoenix restaurant pump its grease interceptor, and what records must it keep?
- Sewer LinesWho pays to extend a sewer main in Phoenix?
Related Rules and Questions
- PhoenixWhat permit does a Phoenix business need for a plumbing remodel or tenant improvement?
- PhoenixPBCC 110.3.10.1: Which plumbing inspections does Phoenix require?
- FAQDoes code require low-flow toilets and fixtures in Arizona?
- FAQDo dual flush toilets really save water?
- FAQAre low-flow showerheads worth it?
- /services/toilet-repair