In new commercial, industrial and public buildings, and when replacing fixtures in existing ones, Glendale allows only lavatory faucets that close automatically after one quart, 2.0 gpm shower heads, 1.28 gallon toilets and 0.5 gallon urinals with no timed flushing. A violation carries a civil penalty of up to $100, then up to $250 for a second or later one.
“Lavatory faucets shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one (1) quart of water.”
- Applies to:
- Owners, tenants, designers and plumbing contractors installing or replacing fixtures in Glendale commercial, industrial or public buildings such as restaurants, offices, schools and hotels
- Official fee:
- none in these sections; civil penalty of up to $100 for a first violation and up to $250 for a second or later one under 9-36(a)
- In force:
- Glendale City Code Art. III (Ord. O25-51, adopted 12-9-25); 2024 IPC as amended, Sec. 9-21
- Last verified:
- October 4, 2026, against the official page
Glendale has two sets of numbers for commercial restrooms, and they do not line up word for word. One is a water-conservation article in Chapter 9. The other is the plumbing code's own Table 604.4, amended by the same ordinance. Most of the time they agree. The one place they may not is a toilet swap on old drain piping.
What does Glendale City Code 9-35 say?
Section 9-35 says that "no person may install any plumbing fixtures for use in this city in any new commercial, industrial or public construction or for replacing plumbing fixtures in existing commercial, industrial or public construction" unless the fixtures meet the listed standards. The ordinance opens with an exception for Arizona Revised Statutes sections 45-315 and 45-319. The standards:
- Lavatory faucets. A mechanism that closes the faucet automatically after delivering no more than one quart of water.
- Shower heads. No more than 2 gallons per minute at 80 psi.
- Water closets. No more than 1.28 gallons per flush.
- Urinals. No more than one-half gallon per flush, and "No urinals may be installed that use a timing device to flush periodically regardless of demand."
- Evaporative cooling systems and decorative fountains. Equipped with water recycling or reuse systems.
Section 9-33 defines commercial, industrial and public construction as buildings used for those purposes, "including restaurants, bars, nightclubs, public buildings, comfort stations, schools, gymnasia, factories, offices, athletic clubs, hotels and motels." Section 9-32 requires the fixtures to be certified by the International Association of Plumbing and Mechanical Officials and to comply with applicable American National Standards Institute standards.
What does the plumbing code add?
Ordinance O25-51 also amends the 2024 IPC in Section 9-21:
- IPC 412.13. "New or replacement faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be provided with automatic faucets in accordance with Table 604.4."
- Table 604.4. Public lavatory: 0.25 gallon per metering cycle, or 0.5 gpm at 60 psi if it is not a metering faucet. Shower heads 2.0 gpm at 80 psi. Sink faucet 1.8 gpm at 60 psi. Flushing urinals 0.5 gallon per flush. Water closet 1.28 gallons per flush.
- Section 604.4 exception. "Replacement of existing fixtures that do not require a permit." Section 9-35 separately names replacements in existing commercial construction, so do not read this exception as removing the 9-35 limits.
- Footnote e. "A 1.6 gallon per flushing cycle is permitted where a water closet is connected to a building's existing sanitary drainage piping."
- Fixture counts, 2902.6. Section 9-17 amends the IBC fixture count provisions, revising 15 to 50 in 2902.6 and footnote e of Table 2902.1 to read 50 or fewer, and adds a footnote that 24 inches of wash sink or 18 inches of a circular wash basin counts as one lavatory. Those amendments also apply to IPC Table 403.1. What the threshold exempts sits in the copyrighted model code, so read 2902.6 itself.
What do the key terms mean?
- Metering faucet. The code uses the phrase "per metering cycle" and the quart rule. A quart is 0.25 gallon, so the two numbers describe the same cycle. That equivalence is arithmetic, not a stated definition.
- Commercial, industrial and public construction. Defined in 9-33 by a list of building uses. Residential construction has its own list and its own section, 9-34.
- Replacing plumbing fixtures. Section 9-33 defines "plumbing fixture" to include lavatory faucets, lavatory faucet replacement aerators, kitchen faucets, shower heads, urinals, water closets, evaporative coolers and decorative fountains, and says it "does not include parts necessary for routine maintenance." Whether a flush-valve rebuild is routine maintenance is a reading the code leaves to the city.
- Automatic faucet. The code does not define it. The reading that fits Table 604.4 is a faucet that shuts off by itself, but that is a reading.
Who does this cover?
Anyone who installs a fixture in a commercial, industrial or public building in Glendale, new or replacement. Section 9-36(a) says that if a noncompliant fixture is installed, "the person who acquired the building or plumbing permit or the person who installed the fixture, or both, are subject to the penalties."
This does not apply to residential buildings. Those fall under 9-34, which has its own faucet limits, and 9-36(c) says the penalty section does not apply to an owner or occupant of a residential dwelling who installs a fixture in the dwelling they occupy.
Quick check: what does your restroom job need?
| Situation | Outcome | Why |
|---|---|---|
| New restaurant, all fixtures new | Meet every 9-35 limit | New commercial construction |
| Replacing a lavatory faucet in an office | Self-closing, one quart, and automatic per 412.13 | 9-35(1), IPC 412.13 |
| Replacing a timed-flush urinal | Not allowed | 9-35(4) bars timing devices |
| New shower head in a gym | 2.0 gpm at 80 psi | 9-35(2) |
| Replacing a 1.6 gpf toilet on existing drain piping | Footnote e permits 1.6, 9-35(3) says 1.28 | The two texts differ |
| Individual unit in an R2 apartment building | Residential rules, not 9-35 | 412.13 excludes it; 9-34 governs residential |
| Evaporative cooler at a shop | Needs water recycling or reuse | 9-35(5) |
What does this look like in real life?
A restaurant restroom refresh. The owner replaces two lavatory faucets and a urinal. The faucets must be self-closing and metering to Table 604.4, and the urinal must be 0.5 gallon with no timer. A timed-flush unit left over from the old build is the item that fails.
A new shower at a Glendale gym. The shower head must be 2.0 gpm at 80 psi, the same figure used for residential construction in 9-34(3).
The edge case, where the answer flips. A strip-mall tenant replaces a toilet that sits on 1990s drain piping. The plumbing code's footnote e lets a water closet use 1.6 gallons per flush when it connects to existing sanitary drainage piping. Section 9-35(3) says "no more than one and twenty-eight hundredths (1.28) gallons of water per flush" for replacing fixtures in existing commercial construction and has no 1.6 exception. The texts are in the same ordinance and do not reconcile on their face. Ask the plan reviewer which one the city applies before you buy the fixture.
What should you do next?
- 1List every fixture the job touches and mark each as new or replacement.
- 2Check each against the 9-35 list and Table 604.4: one quart for lavatories, 2.0 gpm showers, 1.28 gallon toilets, 0.5 gallon urinals, no timers.
- 3For a toilet on existing drain piping, ask the city whether 1.6 gpf under footnote e or 1.28 gpf under 9-35(3) applies, and get the answer in writing with the permit.
- 4Buy fixtures that carry IAPMO certification and meet ANSI standards, which 9-32 requires.
- 5Apply for the plumbing permit through the Development Services Center, which handles Glendale building permits.
What do people get wrong?
- Myth: commercial and residential limits are the same. Lavatory faucets are not. Residential allows 1.5 gpm at 60 psi in 9-34(1), while commercial requires a self-closing mechanism that stops after one quart.
- Myth: a timed-flush urinal is fine if it flushes low. Section 9-35(4) bans urinals that flush periodically regardless of demand.
- Myth: a replacement is exempt. Section 9-35 names "replacing plumbing fixtures in existing commercial, industrial or public construction."
- Myth: only the installer is on the hook. Under 9-36(a), the person who acquired the permit, the installer, or both can be penalized.
What happens if you skip it?
Section 9-36(a) sets a civil penalty of "not more than one hundred dollars ($100.00) for the first violation" and not more than $250 for a second or later one, and says each noncomplying fixture is a separate violation. Section 9-38 lets the director send a notice of a hearing at least 30 days out and then issue a decision that may include a cease and desist order, and the city may seek an injunction if the violation continues.
Full text and source
The text is on Municode under Chapter 9, Articles II and III. This page explains the code and the official text governs.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Scottsdale | Scottsdale's amended Table 604.4 sets the same public lavatory (0.25 gallon per metering cycle), urinal (0.5 gallon) and water closet (1.28 gallons) limits, with the same 1.6 gallon allowance where a water closet connects to existing drainage piping. It adds a water supply at every waterless urinal rough-in. | Scottsdale Revised Code 31-84(b) and 31-83(c) Verified October 4, 2026 |
| Peoria | Peoria amends the 2018 IPC so drinking fountains are not required for an occupant load of 50 or fewer, and separate-sex facilities are not required in business occupancies with a maximum occupant load of 50 or fewer. | Peoria City Code 18-44 (IPC 410.2 and 403.2 as amended) Verified October 4, 2026 |
This page explains the rule. The official text at the source above governs.
- Glendale 9-33 to 9-38: Water Conservation Plumbing Requirements (Municode)
- Glendale 9-21: Amendments to the International Plumbing Code (Municode)
- Glendale 9-17: Amendments to the 2024 International Building Code (Municode)
- Scottsdale 31-83 and 31-84: IPC Chapters 4 and 6 amendments (Municode)
- Peoria 18-44: International Plumbing Code adopted and amended (American Legal)
Fixtures in Other Cities
- Maricopa CountyHow many hand sinks and mop sinks does a Maricopa County restaurant need, and where?
- ChandlerChandler drinking fountain rules: when a water dispenser can replace one
- MesaWhat flow rates does Mesa allow for commercial faucets, toilets and urinals?
- PhoenixIPC 604.4, UPC 401.3 and IRC P2903.2 as amended by Phoenix: What flow rates are fixtures allowed?
- ScottsdaleScottsdale Code 31-83: Bottle Fillers at Every Fountain and Water at Every Urinal
More Glendale Codes and Permits
- Permits and InspectionsWhat plumbing and gas code does Glendale use?
- Backflow PreventionDo you need a permit to install or replace a backflow preventer in Glendale?
- Sewer LinesGlendale City Code 33-126 to 33-129: sewer tap permit and who digs
- Sewer LinesGlendale City Code 33-217: who repairs the sewer line from the building to the street
- Commercial PlumbingGlendale City Code 33-238: grease interceptors must be pumped every 180 days
- Water Supply and PipesWho pays for a water leak on your side of the meter in Glendale? City Code 33-28
Related Rules and Questions
- ScottsdaleWhich plumbing code does Scottsdale use?
- ChandlerWhat does Chandler City Code 29-4 change in the International Plumbing Code?
- UPCUPC 422: How Many Plumbing Fixtures a Building Must Have
- FAQWhat are the ADA plumbing requirements for a commercial restroom?
- FAQWhy does a commercial flushometer toilet not flush fully?
- FAQCan replacing a commercial sink or toilet affect accessibility compliance?
- Commercial Plumbing