Phoenix lists the uses that need a city backflow assembly. Restaurants, supermarkets and car washes need an air gap or reduced pressure (RP) assembly. Retail shell buildings with several tenants on one service need an RP. Single-family homes are exempt unless a cross connection is found. The assembly goes as close as practicable to the water meter.
“An approved backflow prevention method is required for the activities or facilities listed in this subsection that are connected to the public water system.”
- Applies to:
- Owners, tenants, property managers, designers and contractors of Phoenix commercial, industrial, multifamily and institutional properties on city water
- Official fee:
- Plumbing permit for the assembly plus inspection: $195 for the first backflow device and $98 for each additional (PDD Fee Schedule, eff. 2026-01-20)
- In force:
- Phoenix City Code Chapter 37, Article XII (Ord. G-6741, 2020)
- Last verified:
- September 29, 2026, against the official page
Phoenix does not leave backflow protection to guesswork. City Code 37-144 is a list. If your use is on it, you need a city backflow assembly at the water service, on top of whatever the plumbing code requires inside the building. If your use is not on it, the Planning and Development director decides case by case.
What does the Phoenix code say?
The subsection opens with the rule: "An approved backflow prevention method is required for the activities or facilities listed in this subsection that are connected to the public water system." The list is grouped, and each entry names the allowed methods:
- Commercial and educational: restaurants, supermarkets and butcher shops (air gap or RP); car washes (air gap or RP); retail and wholesale nurseries and equestrian properties (air gap or RP); schools and colleges with laboratories (air gap or RP); multi-story buildings with booster pumps or above-ground storage tanks (air gap, RP or double check); interconnected multiple services (air gap, RP or double check); mobile home and RV parks (RP or double check).
- Shopping centers and shells: retail shopping centers, strip malls, and retail or industrial shell buildings "when one service supplies more than one tenant" (RP only).
- Medical: hospitals, medical buildings, clinics, morgues, mortuaries, nursing homes, research laboratories, veterinary and animal grooming shops (air gap or RP).
- Industrial: plating, chemical, laundry, food processing, breweries, semiconductor plants and similar (air gap or RP, with a double check allowed for a few, such as bottling, dairies and metal fabrication).
- Portable and temporary: construction water services and mobile equipment such as water trucks and street sweepers (air gap or RP).
- Fire systems: Class 1 or 2 need a backflow prevention assembly, with no type named. Class 3, 4, 5 or 6 need an RP.
- Irrigation: a system with chemical injection needs an RP. One with elevated areas higher than six inches below the vacuum breaker, or with multiple services, needs an RP. One not subject to backpressure can use a pressure vacuum breaker. Solar heating (direct and auxiliary) needs an RP.
Anything not listed is decided by the director "on a case-by-case basis."
What do the key terms mean?
- Air gap: a physical open space between the supply pipe and the receiving tank, at least double the pipe diameter and never less than one inch.
- RP (reduced pressure principle assembly): two check valves with a relief valve between them. It is the strongest of the mechanical assemblies.
- Double check (DC): two independently acting check valves, allowed only where the hazard is lower.
- PVB (pressure vacuum breaker): protects against backsiphonage on irrigation and must sit above ground.
- Point of service delivery: the customer's side of the water meter.
Who does this cover?
Any customer on Phoenix city water with a listed use. The code says the requirements "do not apply to single-family residences used solely for residential purposes" unless a cross connection problem is specifically identified. Duplexes, apartments, offices and every other property type are not covered by that exemption.
Quick check: which assembly does my business need?
| Use | Allowed assemblies |
|---|---|
| Restaurant, supermarket, butcher shop | Air gap or RP |
| Car wash | Air gap or RP |
| Strip mall or shell building, one service, several tenants | RP |
| Multi-story building with booster pump or roof tank | Air gap, RP or DC |
| Hospital, medical building, clinic, animal grooming | Air gap or RP |
| Construction water, water truck, hydro-vac | Air gap or RP |
| Irrigation with chemical injection | RP |
| Irrigation with no backpressure | PVB, above ground |
| Not on the list | Set by the director case by case |
What does this look like in real life?
- A restaurant opens in a former retail space. Restaurants are on the list, so the tenant improvement plans need an air gap or RP at the service. Under 37-143 the Planning and Development director requires the right backflow protection as a condition of issuing the building permit, and the assembly is tested every year afterward.
- A landlord splits a shell building into three tenants on one meter. The shell building rule applies the moment one service feeds more than one tenant, and it names only the RP.
- A single-family home adds a dedicated irrigation line with fertilizer injection. Homes are exempt unless the city identifies a cross connection problem, and that call is the city's. If it does, the irrigation entry in the list applies, and it names an RP for systems using chemical injection.
- A contractor fills a water truck at a hydrant. Mobile equipment using public potable water is on the list. The truck needs an air gap or RP.
What should you do next?
- 1Find your use in the list above and note the allowed assemblies.
- 2Check whether the property already has an assembly near the meter. If it does, look up its last test date.
- 3Have a licensed plumber pull the Planning and Development plumbing permit for the assembly and place it as close as practicable to the meter.
- 4Schedule the city inspection ($195 for the first device, $98 for each additional).
- 5Hire a certified tester for the first test and every annual test afterward. See the customer duties page for what has to be filed.
What do people get wrong?
- "The plumbing code inside my building already covers this." The city code adds secondary protection at the service, on top of the plumbing code's primary protection.
- "A double check is cheaper, so I will use it." For restaurants, supermarkets, car washes and shopping centers, the code allows only an air gap or an RP.
- "My tenant space is small, so it does not count." For strip malls and shells the trigger is one service feeding more than one tenant, not size.
- "Single-family means no rules." The exemption ends where a cross connection problem is found.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | Mesa also lists uses, and its list is longer and stricter. Restaurants and convenience stores, shopping centers on master meters, buildings over three stories, and any commercial building where one service feeds several tenants all need a reduced pressure assembly (RPA), and a dedicated landscape meter needs at least a pressure vacuum breaker. Mesa also requires service protection at every connection where the city cannot inspect the property. | Mesa City Code 8-1-3 and 8-1-8 Verified September 29, 2026 |
| Chandler | Chandler has no list of business types. The city decides by hazard: an air gap or RP where a material is dangerous to health, a double check assembly where it is only objectionable, and a device on any service with an auxiliary supply, industrial fluids or plumbing too tangled to inspect. | Chandler City Code 52-36(C) and (D) Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- MesaMesa City Code 8-1-10: backflow rules for fire sprinkler systems
More Phoenix Codes and Permits
- Backflow PreventionDo you need a permit to install or replace a backflow preventer in Phoenix?
- Backflow PreventionCan you connect city water to a well or other water source in Phoenix?
- Backflow PreventionWhat backflow duties does a Phoenix property owner have?
- Backflow PreventionWhere must a backflow preventer be installed at a Phoenix property?
- Backflow PreventionWhat happens if you skip your backflow test in Phoenix?
- Permits and InspectionsWhich building and plumbing codes does Phoenix enforce?
Related Rules and Questions
- Valley-WideWhich Businesses Need a Backflow Assembly in Each Valley City
- FAQDo I have to register my backflow assembly with the City of Phoenix?
- FAQHow often does a commercial backflow preventer need testing in Arizona?
- FAQRPZ vs double-check backflow assembly: what's the difference?
- Commercial Plumbing