Not without written approval from the Water Services Director. Phoenix bars any connection between city water and another water source, such as a well, cooling loop or reclaimed line. Where an auxiliary supply is approved, the service needs an air gap or reduced pressure (RP) assembly at the meter.
“No person may cause a connection to be made or allow a connection to exist for any purpose between the City water supply and any other source of water without the approval of the Director.”
- Applies to:
- Commercial, industrial and multifamily owners, designers and contractors with a well, reclaimed water, cooling loop, tank system or other non-city source on a Phoenix property
- Official fee:
- not applicable; a plumbing permit and the backflow inspection ($195 first device, $98 each additional) apply to the assembly (PDD Fee Schedule, eff. 2026-01-20)
- In force:
- Phoenix City Code Chapter 37, Article XII (Ord. G-6741, 2020); 2024 IPC as amended (PBCC eff. 2025-08-01)
- Last verified:
- September 29, 2026, against the official page
Tying a well, a storage tank or a process loop into city plumbing looks like a convenience. In Phoenix it is a regulated act, because a second water source is the most direct way for contaminated water to reach the public main.
What does the Phoenix code say?
Section 37-142 is a single sentence: "No person may cause a connection to be made or allow a connection to exist for any purpose between the City water supply and any other source of water without the approval of the Director." Two parts matter. It reaches anyone who makes the connection and anyone who lets an existing one stay. And it applies "for any purpose," so a connection for a good reason still needs approval.
The neighboring section, 37-144, tells you what protects the city system when an auxiliary source exists. Its list names "Auxiliary water systems (air gap or RP)" and "Chemically contaminated water systems (air gap or RP)." It also lists reclaimed water and sewage and storm drain facilities (air gap or RP), interconnected multiple services (air gap, RP or double check) and industrial fluid systems interconnected with the public supply (RP or double check).
The 2024 plumbing code amendment repeats the point from the building side. Under IPC 608.7.2 as Phoenix amends it, auxiliary water systems and construction water services are among the uses that "shall have a Secondary Reduced Pressure Principle Backflow Prevention assembly installed as close as practicable to each point of service delivery." The base code text that Phoenix reproduces in that amendment also says cross connections between a private water supply and a potable public supply "shall be prohibited."
What do the key terms mean?
- Auxiliary water supply: any water source other than the city system. A private well is the usual example.
- Cross connection: any physical link that could let something other than city water into the city system.
- Air gap and RP: the two strongest protections. An air gap is an open space at least double the supply pipe diameter and never under an inch, and an RP is an assembly with two check valves and a relief valve.
Who does this cover?
Anyone on Phoenix city water who also has, or wants, another source: a commercial well, a nursery with irrigation wells, a cooling system with a tank, reclaimed water on site, or any system that could push water back toward the meter. Single-family homes used solely for residential purposes are exempt from the article unless a cross connection problem is specifically identified. A house that ties its well into the city plumbing has exactly that problem.
Quick check: what do I need for a second water source?
| Situation | What Phoenix requires |
|---|---|
| Any physical connection between city water and another source | Approval of the Water Services Director first (37-142) |
| Auxiliary water system or chemically contaminated system on site | Air gap or RP at the service (37-144) |
| Reclaimed water or storm drain facility on the property | Air gap or RP (37-144) |
| Several city services interconnected on site | Air gap, RP or double check at each service, and at least a double check under the 2024 IPC note |
| Construction water | Air gap or RP, and a secondary RP under IPC 608.7.2 |
| Well kept entirely separate, no physical link | No 37-142 connection; keep the piping clearly separate |
What does this look like in real life?
- A nursery has a well for irrigation and a city meter for the office. The two systems must not be joined. If the owner wants the city line as a backup for the well, that is a connection needing the director's approval, and an air gap or RP at the service.
- A car wash adds a reclaimed water tank. Car washes are on the backflow list already, and the reclaimed line adds an auxiliary water system, which the list also names for air gap or RP.
- A building has a cooling loop topped up from the city line. A connection already in place is covered too, because the section bars allowing one to exist.
- The same property drops the well and caps it at the meter. The answer flips: with no physical link to another source, 37-142 has nothing to approve.
What should you do next?
- 1List every water source on the property and how each one is piped.
- 2Confirm nothing links a well, tank or process loop to the city side of the meter.
- 3If a link is wanted, apply for the Water Services Director's approval before any piping is done.
- 4Install the air gap or RP the code requires at the service, with a plumbing permit and a certified tester's first test.
- 5Keep the yearly test records on file for three years.
What do people get wrong?
- "A check valve at the well is enough." The code names an air gap or RP for auxiliary systems.
- "It is my water, so I can tie it in." The section bars a connection between city water and any other source without approval, whoever owns the source.
- "An old connection is grandfathered." The code also bars allowing a connection to exist.
- "Only businesses are covered." The section says "no person." The only carve-out is 37-144(e), which exempts single-family homes unless a cross connection problem is found.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | Mesa handles it through its definition and its list. An auxiliary water supply is any source other than the city system, including a well, spring, river, stream or canal, and any premises with auxiliary water supply capability needs a reduced pressure assembly at the service. | Mesa City Code 8-1-1 and 8-1-8 Verified September 29, 2026 |
| Chandler | Chandler protects the public system with an approved air gap or RP device where a premises has an auxiliary supply that is not acceptable to the Public Works director, and its service can be discontinued if the required device is missing or bypassed. It sets the rule by hazard and the director's judgment, not by a flat ban on any connection. | Chandler City Code 52-36(A), (C) and (D) Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- GlendaleGlendale City Code 33-92: backflow devices on fire sprinkler services
- GlendaleGlendale City Code 33-94: annual backflow test, records and shutoff
- MesaMesa City Code 8-1-10: backflow rules for fire sprinkler systems
More Phoenix Codes and Permits
- Backflow PreventionDo you need a permit to install or replace a backflow preventer in Phoenix?
- Backflow PreventionWhat backflow duties does a Phoenix property owner have?
- Backflow PreventionWhere must a backflow preventer be installed at a Phoenix property?
- Backflow PreventionWhich Phoenix businesses need a backflow preventer, and which type?
- Backflow PreventionWhat happens if you skip your backflow test in Phoenix?
- Permits and InspectionsWhich building and plumbing codes does Phoenix enforce?