Mesa City Code

Which equipment needs its own backflow device in Mesa? City Code 8-1-9 point-of-use rules

Verified September 29, 2026
In Short

Mesa requires a backflow device at the equipment itself, not only at the meter. Section 8-1-9 lists the device for each item: an RPA for dental chairs, boilers, car wash gear and carbonated beverage dispensers, a DCVA or dual check for ice makers, and an air gap for sewage pumps. Devices must be tested each year.

Official Source
Mesa City Code, Title 8, Chapter 1, Section 8-1-9: Point of Use Protection (Municode)
Mesa City Code 8-1-9, Point of Use Protection
“The customer must install and maintain point of use backflow protection at each such connection, as required by this section. The customer must have the backflow prevention assembly tested annually”
Applies to:
Restaurants, dental and medical offices, salons, car washes, labs, building owners, designers and plumbers in Mesa's water service area
Official fee:
not published in this section
In force:
Mesa City Code Title 8, Chapter 1 (Ord. 5909, 12-9-24)
Last verified:
September 29, 2026, against the official page

A backflow device at the meter protects the city. Mesa also wants protection at the equipment that can foul the water inside your building. Section 8-1-9 is the list, and it reads like a shopping guide for your kitchen, dental suite or salon.

What does Mesa City Code 8-1-9 say?

Every piece of equipment connected to a customer water system is "subject to evaluation for cross-connection potential and the degree of hazard." The customer must install and maintain point-of-use protection at each connection, have the assembly tested annually and make sure reports reach the Department. Four installation rules follow:

  • Height and access (B). Install no more than five feet above finished floor, accessible for testing. Removing an access panel or door is allowed.
  • No copper downstream (C) of a point-of-use assembly where the water is carbonated, deionized, distilled or treated by reverse osmosis.
  • RPA drains (D). A point-of-use RPA needs an air-gapped drain line for its relief valve, at least as large as the RPA, properly secured and routed to a floor sink, mop sink or other appropriate wastewater outlet. Flexible hose is not permitted.
  • One device, one use (E). Multiple uses downstream of one point-of-use device are prohibited unless the Department approves. It may approve one assembly for a group of similar items, such as pedicure stations.

Subsection (E) also holds the equipment list. A sample:

EquipmentAcceptable protection
Dental chairs and dental vacuum pumpsRPA
Carbonated beverage dispensersRPA
Non-carbonated beverage dispensersDCVA or dual check
Ice makersDCVA or dual check
Commercial dishwashersAG, PVB, RPA, SVB or AVB
Boiler make-up linesRPA
Boilers with chemical additives or closed loopsRPA
Reverse osmosis treatmentRPA
Car wash equipmentRPA
Autoclaves and sterilizersRPA
Pedicure stationsAG, PVB, RPA or SVB
Sewage ejectors and pumps, trap primersAG
Irrigation systemsPVB or RPA (RPA if chemicals are added)

What do the key terms mean?

  • Point of use. The equipment connection itself, downstream of the meter.
  • AG, AVB, PVB, SVB. Air gap, atmospheric vacuum breaker, pressure vacuum breaker and spill-resistant vacuum breaker. Lighter devices for lower hazards.
  • RPA, DCVA. Reduced pressure and double check assemblies. See which uses need an assembly.
  • Dual check. Defined in 8-1-1 as two independent check valves with an atmospheric vent, for non-health or low hazard uses only. Those non-testable devices "can only be installed on ice makers and non-carbonated beverage dispensers."

Who does this cover?

Any Mesa customer with listed equipment: restaurants, coffee shops, dental and medical suites, salons, car washes, labs, pools and boiler rooms. Equipment that does not appear on the list can still be evaluated based on the degree of hazard.

Quick check: what does your equipment need?

SituationProtectionWhy
Dental office with chairs and a vacuum pumpRPA at eachListed as RPA
Café with ice maker and soda gunDCVA or dual check for ice, RPA for carbonatedDifferent rows
Salon with six pedicure stationsOne approved assembly for the group, if the Department allows8-1-9(E)
RO system on a coffee machineRPA, and no copper downstreamListed, and (C)
Water heater or hose reel not on the listDepartment evaluates(E)
RPA relief valve dumping to a flex hoseNot allowed(D)

What does this look like in real life?

A coffee shop. The soda dispenser needs an RPA because the water is carbonated, and the line downstream cannot be copper. The ice maker takes a lighter device.

A dental suite. Each chair has an RPA, its relief drain runs air gapped to a floor sink, and the devices are within five feet of the floor so the tester can reach them.

The edge case. A nail salon installs six pedicure chairs on one device without asking. The section prohibits multiple uses downstream unless approved, so the group approval has to come first.

What should you do next?

  1. 1List every piece of water-using equipment and match it to the 8-1-9 table.
  2. 2Show the devices on the plumbing plans. See backflow on plans.
  3. 3Set each device within five feet of the floor, with access and an air-gapped drain for any RPA.
  4. 4Keep copper out of the line after carbonated, RO, distilled or deionized water.
  5. 5Add each device to the annual test schedule.

What do people get wrong?

  • "The meter device covers everything inside." Point-of-use devices are on top of it.
  • "A hose is fine for the RPA drain." Flexible hose is not allowed.
  • "The list only applies to restaurants." It covers labs, salons, car washes, mortuaries and more.
  • "One device can serve any group of equipment." Only with Department approval, and only for similar items.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
TempeTempe's table sets the minimum service-connection assembly by type of premises, such as medical and dental buildings and beverage bottling plants. It is a list of premises, not a list of equipment inside them.Tempe City Code 33-105
Verified September 29, 2026
GlendaleGlendale also assigns an RP or DC by activity, for example an RP for beverage or chemical bottling plants and for medical and dental buildings. Its list is by premises and activity, so a dental chair or ice maker inside is not separately named.Glendale City Code 33-90
Verified September 29, 2026

This page explains the rule. The official text at the source above governs.