Chandler sizes gravity grease interceptors by total drainage fixture units: 0 to 21 DFU needs 750 gallons, 22 to 35 needs 1,000, 36 to 90 needs 1,250, and so on up to 3,000 gallons at 308 to 342 DFU. Above 342 DFU, an Arizona registered professional engineer must design it.
“The required capacity of gravity grease interceptors and gravity grease interceptors with fats, oils, and greases disposal systems shall be sized per the City of Chandler DFU Conversion Chart”
- Applies to:
- Restaurant, commercial kitchen and food service owners, designers, engineers and plumbing contractors
- Official fee:
- not applicable
- In force:
- 2024 IPC 1003.3.7 as amended by Chandler (Ord. 5108, effective 2025-07-01), since July 1, 2025
- Last verified:
- September 28, 2026, against the official page
Two restaurants with the same kitchen can need different interceptors depending on which city they are in. In Chandler the answer comes from a chart in the city code, not from a formula, and the chart starts at 750 gallons.
What does Chandler's amendment say?
The 2024 International Plumbing Code (IPC) has its own sizing language for gravity grease interceptors in Section 1003.3.7. Chandler City Code 29-4.4 deletes the first sentence of that section and replaces it with a rule that the capacity "shall be sized per the City of Chandler DFU Conversion Chart." The chart is printed in the ordinance.
| Total drainage fixture units (DFU) | Interceptor volume |
|---|---|
| 0 to 21 | 750 gallons |
| 22 to 35 | 1,000 gallons |
| 36 to 90 | 1,250 gallons |
| 91 to 172 | 1,500 gallons |
| 173 to 216 | 2,000 gallons |
| 217 to 307 | 2,500 gallons |
| 308 to 342 | 3,000 gallons |
A footnote adds that establishments "resulting in total DFU's > 342 shall be designed by a professional engineer, registered in the State of Arizona."
What do the terms mean?
- Gravity grease interceptor: a large in-ground or below-floor tank that slows kitchen wastewater so grease floats and solids settle. It is different from a small hydromechanical trap under a sink.
- Drainage fixture unit (DFU): a number the plumbing code assigns to each fixture for how much it can discharge. The city's sizing worksheet (Form UDM-062) converts by drain size, using IPC Table 709.2: a drain of 1 1/4 inches or less is 1 DFU, 1 1/2 inches is 2, 2 inches is 3, 2 1/2 inches is 4, 3 inches is 5 and 4 inches is 6.
- Total DFU: only the fixtures that drain to the interceptor count, not the whole building. The worksheet lists what to include: three-compartment and two-compartment sinks, food prep sinks, mop sinks, floor sinks, trench drains, floor drains, ice cream dipper wells and trash compactor washouts, among others.
- Dishwashers: the worksheet counts a dishwasher as 2 DFU for every gallon per minute of the manufacturer's flow rate, and asks for the make, model and a cut sheet.
Does this apply to you?
It applies to gravity interceptors at any Chandler food service business that needs one. The chart does not size small hydromechanical grease traps, and the ordinance text does not say how the city sizes those. It does not apply outside Chandler city limits, and neighboring cities use their own sizing rules (compared below).
Quick check: what does the chart give you?
| Situation | Result | Why |
|---|---|---|
| Small cafe, 12 DFU to the interceptor | 750 gallons | Anything up to 21 DFU lands in the first row |
| Same cafe adds a 6 gallon per minute dishwasher (12 DFU) and a prep sink with a 2 inch drain (3 DFU), now 27 DFU | 1,000 gallons | Crossing from 21 to 22 DFU jumps one size |
| Full-service kitchen, 120 DFU | 1,500 gallons | Falls in the 91 to 172 row |
| Large commissary, 320 DFU | 3,000 gallons | Top row of the chart |
| Food hall, 400 DFU | Engineer-designed | Over 342 DFU the chart stops |
| Kitchen plans a garbage disposer draining to the interceptor | Not allowed, see the FOG page | The city says disposers cannot discharge to the device |
| Commercial dishwasher rated at 10 gallons per minute | Adds 20 DFU | The worksheet counts 2 DFU per gallon per minute |
What does this look like in real life?
A tenant improvement in a retail center. The landlord's plans show a 500-gallon interceptor left by a previous tenant. That is below the chart's smallest size of 750 gallons, and if the new kitchen has more than 21 DFU draining to it the chart calls for at least 1,000. Whether an existing tank can stay in a tenant improvement is decided at plan review.
One fixture flips the size. A kitchen at 21 DFU needs 750 gallons. Adding a single 3-DFU sink moves it to 24 DFU and 1,000 gallons. That is why the fixture count matters before you finalize the layout.
A build-out copied from another city. A restaurant group reuses a Phoenix set of plans with a 500-gallon interceptor. Phoenix's own manual sizes by flow (an example there multiplies 12 DFU by 3 gallons per minute by a 12-minute retention time to get 432 gallons and rounds up to 500). In Chandler, the same 12 DFU sits in the first row of the chart and needs 750 gallons.
What should you do next?
- 1Have your plumber or designer fill out the city's Gravity Grease Interceptor Requirements worksheet (Form UDM-062): list each fixture that drains to the interceptor, its drain size and quantity, and multiply by the DFU value.
- 2Read the size off the chart above. Over 342 DFU, hire an Arizona registered professional engineer.
- 3Submit the fixture count and plumbing plan to Chandler Development Services when you apply for the plumbing permit. The city's Food Service Establishments page asks for exactly that.
- 4Add the dishwasher make, model and flow rate, and attach the tank manufacturer's cut sheet, both of which the worksheet asks for.
- 5Plan the maintenance access and the pumping records now. The city keeps the owner responsible for cleaning and repairs.
What do people get wrong?
- "The IPC formula decides the size." In Chandler the ordinance chart replaces the first sentence of IPC 1003.3.7.
- "Bigger is wasted money." The city says correct sizing costs less over time because a smaller device "will require more frequent cleanings."
- "500 gallons is the standard." Mesa's minimum is 500 gallons. Chandler's chart starts at 750.
- "The chart covers every device." It covers gravity interceptors.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | Sized by drainage fixture unit value, minimum 500 gallons and maximum 2,500 gallons, at least two chambers. | Mesa City Code 8-4-22(E) Verified September 28, 2026 |
| Phoenix | Flow based: DFUs times gallons per minute times retention time, rounded up. The manual's worked example gives 500 gallons. | Phoenix FOG Best Management Practices Manual, June 2024 Verified September 28, 2026 |
This page explains the rule. The official text at the source above governs.
- City of Chandler: Gravity Grease Interceptor Requirements worksheet (Form UDM-062)
- Chandler City Code 29-4.4, IPC amendments (Municode)
- City of Chandler: Food Service Establishments (Industrial Pretreatment Program)
- Mesa City Code 8-4-22, traps and interceptors (Municode)
- City of Phoenix FOG Best Management Practices Manual (June 2024)
Commercial Plumbing in Other Cities
- PhoenixCan a Phoenix business get an annual permit for plumbing alterations?
- PhoenixPhoenix City Code 28-12: Which businesses must install a grease or oil interceptor?
- PhoenixWhich minor commercial plumbing jobs can be permitted online in Phoenix?
- PhoenixWhat permit does a Phoenix business need for a plumbing remodel or tenant improvement?
- PhoenixDo you need plan review to replace a grease interceptor in Phoenix?
- PhoenixPhoenix restaurants: When do you need an outdoor gravity grease interceptor instead of a grease trap?
More Chandler Codes and Permits
- Commercial PlumbingCan a Chandler business get an annual permit for repeat plumbing alterations?
- Commercial PlumbingHow long does a commercial tenant improvement permit take in Chandler?
- Commercial PlumbingDoes a Chandler restaurant need a grease trap or interceptor?
- Backflow PreventionChandler City Code 52-36: backflow assemblies on commercial building plans
- Permits and InspectionsWhich plumbing and gas codes does Chandler enforce?
Related Rules and Questions
- UPCUPC Grease Interceptor Sizing: How Code Sizes a Grease Trap
- ArizonaPhoenix City Code Chapter 28: The FOG (Grease) Program for Food-Service Businesses
- FAQWhat size grease interceptor does my restaurant need?
- FAQHow often should a restaurant grease trap be pumped?
- FAQWhat is FOG (fats, oils, and grease) in plumbing?
- Commercial Drain Cleaning
- Commercial Plumbing