At least 12 inches below grade for metal gas pipe and 18 inches for plastic. El Mirage's amendment to fuel gas code Section 404.12 also strikes the cross-reference to the 8 inch allowance for a single line to an outdoor grill or light.
“Underground piping systems shall be installed a minimum depth of 12 inches (305 mm) below grade and 18 inches (457mm) for plastic piping.”
- Applies to:
- Homeowners, builders and licensed contractors burying natural gas or propane piping inside El Mirage city limits, for a pool heater, grill, fire pit, detached garage or a commercial building
- In force:
- 2018 International Fuel Gas Code and 2018 International Residential Code with El Mirage amendments, adopted by Resolution R23-05-10 (passed May 2023, effective July 1, 2023), since July 1, 2023
- Last verified:
- November 14, 2026, against the official page
In El Mirage, AZ, you bury a gas line at least 12 inches deep, and plastic gas pipe at least 18 inches deep. The city wrote that into Section 404.12 of its fuel gas code when it adopted the 2018 codes in 2023, and in the same edit it struck the line that points to the code's 8 inch allowance for a single pipe to an outdoor grill or light. So under El Mirage's fuel gas code, a shallow grill line is not the easy answer it is in Phoenix.
What does El Mirage's gas burial rule say?
El Mirage enforces the 2018 International Fuel Gas Code, listed on the city's Building Safety page, with local changes adopted by Resolution R23-05-10 and in force since July 1, 2023. The change to Section 404.12, "Minimum burial depth," reads: "Underground piping systems shall be installed a minimum depth of 12 inches (305 mm) below grade and 18 inches (457mm) for plastic piping."
The city struck the words that followed "below grade" in the model code, ", except as provided for in Section 404.12.1." Section 404.12.1 is the model code's allowance for individual lines to outdoor lights, grills or other appliances to sit 8 inches below finished grade where approved and safe from damage. With that cross-reference gone, the depth rule in El Mirage's fuel gas code carries no 8 inch exception.
How deep are natural gas lines typically buried?
Across the Phoenix area, the floor is 12 inches of cover for metal pipe. The model codes allow 8 inches for one outdoor appliance line, and several cities, El Mirage among them, ask for 18 inches on plastic pipe. Our Valley gas pipe burial depth comparison puts the cities side by side. Those depths are for customer piping past the meter. The utility's own mains and service lines follow the utility's standards, not this section.
What do the key terms mean?
- Below grade. Measured down from the finished ground surface to the top of the pipe, after the landscaping is done. Gravel or pavers added later do not count toward a trench that was dug short.
- Plastic piping. Polyethylene (PE) gas pipe, usually yellow. The fuel gas code lets it run outdoors underground only, and it needs a yellow insulated copper tracer wire of at least 18 AWG laid beside it so the line can be found later.
- Metal piping. Coated steel pipe or other approved metal pipe. Buried steel needs a factory applied, corrosion resistant coating.
- Customer buried piping. Everything past the gas meter. It belongs to the owner, not the utility.
Who does this cover?
Anyone burying gas piping inside El Mirage city limits: a homeowner adding a pool heater, an outdoor kitchen or a fire pit, a builder running gas to a detached garage, and a business piping gas to a rooftop unit or a new building. It covers natural gas and propane piping alike once the piping falls under the fuel gas code. The propane supplier's own rules govern the tank and its first connections, so ask them about the run from the tank.
One caution for houses. One and two family homes are built under the International Residential Code, which has its own gas chapter, and El Mirage's residential amendments do not change that chapter's burial depth section, G2415.12. Ask Development Services which depth the inspector will hold a house to. A trench dug to 18 inches meets both codes either way.
Quick check: is the trench deep enough?
| Pipe and job | El Mirage fuel gas code depth |
|---|---|
| Steel or other metal gas pipe | At least 12 inches below grade |
| Plastic (PE) gas pipe | At least 18 inches below grade, with an 18 AWG yellow tracer wire |
| Single line to a grill, fire pit or light | No 8 inch allowance in the city's fuel gas code; dig to 12 inches for metal or 18 for plastic |
| Plastic pipe coming out of the ground | Ends on an approved riser, not bare plastic above grade |
| Pipe under a building slab | Not bare: only in a sealed, vented conduit |
What does a buried gas line look like?
New plastic gas pipe is usually yellow, sometimes black with a yellow stripe, with a copper tracer wire taped or laid beside it. Older metal lines are often steel pipe wrapped in a black, green or yellow coating. Under a house you may also see yellow jacketed CSST, a flexible stainless tubing, which our CSST and black iron comparison explains. If you dig up something you are not sure of, stop and treat it as a gas line until someone qualified says otherwise.
What should you do if you hit a gas line while digging?
Southwest Gas tells anyone who smells gas to leave the area first, then call 911 and the gas company from a safe place. Do not try to plug the pipe or bury the damage. A nicked coating or a dented pipe that is not leaking still needs repair before the trench is filled, because the damage can corrode or crack later.
What does this look like in real life?
A pool heater line. The line runs from the house to the equipment pad in PE pipe. The trench goes to 18 inches with the tracer wire beside the pipe, the pipe comes up on a riser at each end, and the trench stays open until the inspector signs off.
An outdoor kitchen grill. In Phoenix this run can sit 8 inches down where approved. Under El Mirage's fuel gas code it gets the full 12 inches for coated steel or 18 for PE, so plan the trench for that before the pavers go in.
The edge case. A house built under the residential code gets a short metal grill line at 8 inches. That may pass under the residential code's own section, but ask Development Services before you count on it. Digging to 12 inches settles the question.
What should you do next?
- 1Confirm the address is inside El Mirage city limits. An unincorporated address goes to Maricopa County, which also asks for 12 and 18 inches.
- 2Pick the pipe material and plan the trench depth from the table above: 12 inches for metal, 18 for plastic.
- 3Pull the permit before you dig. El Mirage's Building Permits page says permits are required for repair or replacement work on systems related to mechanical, electrical or plumbing, and applications go through ELM Online Permits.
- 4Call 811 at least two working days before digging. Arizona law requires the locate; see our page on A.R.S. 40-360.22 and Arizona 811. Southwest Gas warns that customer buried piping cannot be located by calling 811, so keep a drawing of where your new line runs.
- 5Leave the trench open for the inspection, with the pipe, tracer wire and risers in view, and have the new piping pressure tested before gas goes in. Our gas line pressure test guide explains the test.
HQ Plumbing & Air installs and repairs gas lines across the West Valley. HQ pulls the permit and gets the work through the city inspection. When HQ hunts for a leak, it caps every gas fixture at its flex line and pressurizes the system at the meter for an air test, and when the gas company has shut a home's gas off, HQ finds and fixes the leak and gets the gas clearance so the gas can be turned back on. See gas line repair and installation or gas leak inspection. For a grill line, read our guide to a natural gas line for a grill, and for the water side of an El Mirage job, see who installs water taps and service lines in El Mirage.
What do people get wrong?
- "A grill line only needs 8 inches." That is the model code's allowance, and El Mirage struck its cross-reference from the fuel gas code's depth rule.
- "12 inches is enough for any pipe." Plastic gas pipe needs 18 inches in El Mirage.
- "811 will find my old gas line." It marks the utility's lines. Piping past the meter is yours to locate.
- "El Mirage is on the 2024 codes like Phoenix." El Mirage still enforces the 2018 editions with its 2023 amendments.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Surprise | Surprise, El Mirage's neighbor, also asks for 12 inches on metal and 18 on plastic. It went further: it struck the 8 inch outdoor appliance exception from both its fuel gas code and the residential code's gas chapter (G2415.12). 2024 IFGC. | Surprise Code 105-19 local amendments (Ord. 2025-14), 2024 IFGC 404.12 and 404.12.1 (deleted) Verified September 29, 2026 |
| Phoenix | Phoenix does not amend Section 404, so the base rule applies: 12 inches below grade, or 8 inches for an individual line to an outdoor light, grill or other appliance where approved and not exposed to damage. There is no separate 18 inch figure for plastic. 2024 IFGC. | 2024 IFGC 404.12 and 404.12.1 (Phoenix amends Chapter 1 and 403.11 only) Verified September 29, 2026 |
| Maricopa County | In unincorporated Maricopa County, metal pipe goes at least 12 inches deep and plastic 18 inches with a tracer, and the county addenda strike the 8 inch outdoor appliance exception. The inspector sees the pipe exposed on a firm bed of soil, free of rocks and debris. 2018 IFGC as amended. | Maricopa County Local Additions and Addenda, IFGC 404.12; Inspection Services Guide Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
- City of El Mirage: Resolution R23-05-10 and its exhibits, Adopted Codes and Amendments (PDF; IFGC 404.12 is on page 20 of the plumbing, fuel gas and energy amendments)
- City of El Mirage: Building Safety (current adopted codes, 2018 International Fuel Gas Code)
- City of El Mirage: Building Permits and Inspections
- Southwest Gas: Call 811 Before You Dig, and customer buried piping
- Arizona Revised Statutes 40-360.22: Excavations; determining location of underground facilities
Need this done to El Mirage code?
We pull the permit when the job needs one and do the work to the code on this page. For restaurants, offices and rental properties, we schedule it around your hours.
- 24/7 emergency service
- Licensed and insured
- Upfront pricing
- Free estimates
Gas Lines in Other Cities
- ChandlerChandler City Code 29-7: International Fuel Gas Code Adopted
- Fountain HillsCan you put in a wood burning fireplace in Fountain Hills?
- Cave CreekGas line inspection checklist: what Cave Creek inspectors check on fuel gas piping
- ChandlerDo you need a permit to add a gas line in Chandler?
- ChandlerWhat pressure test does Chandler require on new gas piping?
- ChandlerWhat are Chandler's rules for underground gas pipe?
More El Mirage Codes and Permits
- Permits and InspectionsWhat are the construction hours in El Mirage, and can a plumber work after hours?
- Water Supply and PipesEl Mirage City Code 50.066: who installs water taps and service lines?
- Backflow PreventionDoes El Mirage require a permit to install a backflow assembly?
- Commercial PlumbingWhat are El Mirage's grease interceptor requirements?
- Drains, Traps and VentsWhat rainfall rate does El Mirage use to size roof drains and storm drains?
Related Rules and Questions
- Valley-WideGas Line Burial Depth Rules in Each Valley City
- Valley-WideGas Line Permits in Each Valley City
- Valley-WideGas Line Pressure Test Rules in Each Valley City
- FAQCan I run a natural gas line to my grill?
- FAQHow do you run a gas line to a fire pit?
- FAQHow does a gas line pressure test work?
- FAQCSST vs black iron gas pipe: which is better?
- FAQCan a gas line be replaced without digging?
- Underground Commercial Gas Line Repair
- Gas Line Repair & Installation
- /services/gas-leak-inspection