How does Phoenix size a water meter for a new building?

Verified October 4, 2026
In Short

Phoenix sizes water meters from the table in its Water Meter Sizing Guideline (TRT 00142). Each meter size has a maximum flow and fixture unit count, from 20 gpm for a 3/4-inch meter to 1,600 gpm for an 8-inch compound meter. A design over the limit moves up a size, and new building taps start at 1 inch.

Official Source
City of Phoenix Planning & Development: Water Meter Sizing Guideline, TRT/DOC/00142 (Rev. 08/26)
Phoenix Water Meter Sizing Guideline (TRT 00142)
“Project designs which exceed the listed gpm unit values must be upsized to the next larger meter.”
Applies to:
Designers, contractors, developers and owners sizing a new or upsized Phoenix water meter, commercial and residential
Official fee:
Impact fees, Water Resource Acquisition and Development Occupation Fees are based on meter size, not tap size, and vary by area (TRT 00142 note 10); the guideline sends fee questions to the Impact Fee Team
In force:
TRT 00142, Rev. 08/26, issued with the 2024 UPC 610.1, 2024 IPC 604.1 and 2024 IRC P2903.1
Last verified:
October 4, 2026, against the official page

A water meter is a flow limit as much as a measuring device. Size it too small for the fixtures and the city's table says it has to go up a size, and Phoenix ties development fees to meter size. The surprise in the city's table: a 3/4-inch meter is rated for zero flush valve fixture units, so a restroom with flushometer toilets can't run off one at all.

What does the Phoenix sizing guideline say?

The Water Meter Sizing Guideline, TRT 00142, is a joint Planning & Development and Water Services document, revised 08/26 and tied to UPC 610.1, IPC 604.1 and IRC P2903.1 in the 2024 codes. Its policy opens with "Water meters shall be sized in accordance with the following table." The table lists, for each meter, a maximum flow in gallons per minute and a maximum number of fixture units. The rule for a design that doesn't fit: "Project designs which exceed the listed gpm unit values must be upsized to the next larger meter."

MeterMax gpmFlush tank FU (UPC / IPC-IRC)Flush valve FU (UPC / IPC-IRC)
3/4" x 3/4"2030 / 210 / 0
1"50127 / 12948 / 50
1-1/2"100380 / 375245 / 245
2"160692 / 696631 / 625
3" compound3201,926 / 1,9551,926 / 1,955
4" compound5003,620 / 3,7283,620 / 3,728
6" compound1,0008,300 / see note8,300 / see note
8" compound1,60014,500 / see note14,500 / see note

The note on the two largest sizes says the IPC design method is limited to 593 gpm.

The other parts of the guideline, in short:

  • Fire flow vs fixture units. "Select the larger meter when comparing meters based on fire flow to ones based on fixture units." The gpm column is used for fire sprinkler or domestic demand.
  • Minimum tap. New service taps for buildings, including single-family lots, are at least 1 inch. New 3/4-inch taps are for landscape irrigation or other approved special uses only.
  • Existing 3/4-inch service. Existing 3/4-inch taps and meters may stay as long as they meet the fixture unit limit in the table.
  • Big meters. Meters 6 inches and larger need advance consultation with Water Services on availability, cost and delivery. Turbine meters are case by case.
  • Main limits. A new service connection is limited to 50% of the service main's diameter.
  • No combination meters. Fire, domestic and landscape demands each get their own service connection, except that a combined fire and domestic meter is allowed for a single-family home on a single lot.

What do the key terms mean?

  • Fixture unit (FU): a load value the plumbing code assigns to each fixture. You add them up for the building and compare the total to the column for your code and fixture type.
  • Flush tank vs flush valve: column 3 is for buildings where toilets and urinals are mostly tank type; column 4 is for mostly flushometer (flush valve) type. Flush valves draw a lot of water fast, which is why their limits are lower on small meters.
  • Compound meter: a meter built to read both low and high flows, listed for the 3-inch and larger sizes.
  • Tap: the connection to the city main. The guideline treats tap size and meter size separately, and it bases fees on the meter.

Who does this cover?

Anyone sizing a new Phoenix meter or asking for a bigger one: architects and engineers on commercial and multifamily jobs, contractors on tenant improvements that add fixtures, and owners of houses on a new lot. It also matters when a business adds restrooms or a kitchen and the existing meter's fixture unit limit gets crossed.

This does not apply to a property served by another water provider, or to private submeters downstream of the city meter. It also does not decide backflow, which comes from City Code Chapter 37.

Quick check: which meter fits?

SituationOutcomeWhy
New house on a new lotTap at least 1 inchNote 5 sets the 1-inch minimum for all new building taps
Existing house on a 3/4-inch meter, adding a bathroomCan stay if the new total is within 30 UPC or 21 IPC/IRC flush tank FUNote 3 lets existing 3/4-inch service remain if it meets the table
Office restroom with flushometer toiletsAt least a 1-inch meterThe 3/4-inch meter lists 0 flush valve FU
Design needs 110 gpm2-inch meterOver the 1-1/2 inch limit of 100 gpm, so upsize
Sprinkler demand points to a bigger meter than fixtures doUse the larger meterGuideline: select the larger of the two
Landscape irrigation only3/4-inch tap and meter can be allowedIrrigation is the named use for new 3/4-inch taps

What does this look like in real life?

  • A café moves into a strip center suite. The plans add a hand sink, a three-compartment sink and two tank toilets. The engineer totals the fixture units under the code the plans use (UPC or IPC) and checks the 1-inch row. Under the limit, the meter stays.
  • A medical office uses flushometers. The same fixture count that fit a 1-inch meter with tank toilets may not fit with flush valves, because the flush valve column for 1 inch is 48 UPC or 50 IPC. The answer flips to a 1-1/2 inch meter.
  • An older home on 3/4-inch service gets a casita. If the added fixtures push the total past 30 UPC flush tank units, the meter has to be upsized, and the new meter size sets the development fees.

What should you do next?

  1. 1Count fixture units for the whole building under the code your plans follow, UPC or IPC/IRC, and note whether toilets are mostly tank or flush valve.
  2. 2Find the gpm demand, including any fire sprinkler demand, and pick the larger meter of the two methods.
  3. 3Check the table in TRT 00142 and move up a size if any limit is exceeded.
  4. 4For meter sales, tap and service fees, contact the Planning & Development Engineering Counter at (602) 262-6551, as the guideline directs.
  5. 5For impact fee estimates, email impactfees@phoenix.gov or call the Impact Fee Manager at (602) 495-5455.
  6. 6For 6-inch and larger meters, start the Water Services consultation early.

What do people get wrong?

  • "Fees follow the tap size." The guideline says impact fees, WRA and DOF "are based on the water meter size, not the tap size."
  • "A 3/4-inch meter is fine for a small office." Not with flush valve toilets: the table gives 3/4-inch meters 0 flush valve units.
  • "One meter can serve the fire line and the building." Combination fire, domestic and landscape meters are prohibited; only a single-family home on a single lot may combine fire and domestic.
  • "New homes can still get a 3/4-inch tap." New building taps start at 1 inch; 3/4-inch is for irrigation or approved special uses.
  • "Any size reducer works." The Water Services design manual says a service connection "can only be reduced one size," for example 2-inch to 1.5-inch.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
GlendaleGlendale does not publish its own meter table in the code. It sizes meters from the tables in the Uniform Plumbing Code as the city adopted and amended it.Glendale City Code 33-24
Verified October 4, 2026
ScottsdaleScottsdale sizes a meter so it does not exceed the anticipated maximum normal daily operating flow under the city's design standards and policy manual. Single-family homes get one meter per parcel, and two or more meters in a manifold are prohibited.Scottsdale City Code 49-27
Verified October 4, 2026

This page explains the rule. The official text at the source above governs.