High-Rise and Booster Pump Building Backflow Testing
Height and booster pump rules by city, parallel assemblies that keep water on during the test, and domestic assembly testing for towers.
Tall buildings and buildings with booster pumps or water storage tanks need backflow protection at the service in most Valley cities. Mesa and Scottsdale draw the line at 34 feet, Tempe at more than three stories or 34 feet, and Phoenix lists multi-story buildings with booster pumps or storage. Each assembly is tested every year.
The rules that apply
Each rule links to the official text we read it from. Cities change these, so check the source before a big decision. Last checked 2026-10-04.
Height
MesaBuildings greater than three stories or 34 feet in height from curb level need an RP assembly.
Source: Mesa City Code 8-1-8Height, pumps and tanks
ScottsdaleBuildings with plumbing or fixtures more than 34 feet above the service connection need an RP. So do buildings with house pumps or potable water storage tanks.
Source: Scottsdale Revised Code 49-62(a)(9), (10)Pumps and tanks
PhoenixMulti-storied buildings with booster pumps or above-ground storage tanks need an air gap, RP or double check.
Source: Phoenix City Code 37-144Height, pumps and tanks
TempeBuildings greater than three stories or 34 feet, and buildings with booster pumps or potable water storage, are on the list of premises that need an approved assembly, rated by low or high hazard.
Source: Tempe City Code 33-105Water that can't go off
Scottsdale and TempeWhere the supply can't be interrupted for testing, two assemblies are installed in parallel. Scottsdale requires their combined cross-section to at least equal the supply line.
Source: Scottsdale Revised Code 49-63(c)Also: Tempe City Code 33-104(b)Annual test
ArizonaEach required assembly is tested at least annually and after installation, relocation or repair.
Source: A.A.C. R18-4-215(F)Why height and pumps trigger the rules
It comes down to backpressure. Phoenix's code defines it as pressure in the building's piping that rises above the supply pressure at the meter "by pump, elevation of piping, or steam and/or air pressure" (City Code 37-1). A tall building has both. Water standing in the risers presses down toward the street, and a booster pump can push building pressure above the city's. Either can try to drive water back through the service. Storage tanks add a pool of water the city no longer controls.
So the cities write buildings like these into their lists.
| City | Trigger | Assembly |
|---|---|---|
| Mesa | More than three stories or 34 feet from curb level | RP |
| Scottsdale | Plumbing more than 34 feet above the service connection | RP |
| Scottsdale | House pumps or potable storage tanks | RP |
| Phoenix | Multi-story building with booster pumps or above-ground storage | Air gap, RP or double check |
| Tempe | More than three stories or 34 feet; booster pumps or potable storage | Listed, rated low or high hazard |
Mid-rise offices, condo buildings, hotels and medical office buildings all fall in here. Phoenix's list also names hospitals and medical buildings separately, so a medical tower is on Phoenix's list for that reason, whatever its height.
Testing without shutting off the building
Here's the problem with a tower. Testing the service assembly closes its shutoff valves, and every floor above loses water while the gauges are read. For a hotel or a building with residents, that's a big ask.
The code answer is parallel assemblies. Tempe requires two sets installed side by side "if the water supply cannot be temporarily interrupted for the testing of assemblies" (City Code 33-104(b)). Scottsdale requires two or more in parallel when a user "requires a continuous water supply," and their combined cross-section must at least equal the supply line (Revised Code 49-63(c)). With a parallel pair, we close and test one while the other carries the building, then switch.
If your building has a single assembly, the test still happens. It just needs an outage window, posted notice to tenants or residents, and someone on site who can confirm the booster pumps are handled before the valves close. Adding a parallel assembly is an installation with a permit. See backflow installation for the permit path.
Booster pumps and the assembly
A booster pump sits downstream of the service assembly, and the two affect each other. Watts' manual for its large RP assemblies lists fluctuating inlet pressure as a cause of relief valve discharge. A booster pump that cycles hard can contribute to that kind of swing. If an RP on a pumped building spits water between tests, look at the pump controls along with the assembly. Our backflow assembly repair page covers the parts side.
Several assemblies, one building
Tall buildings rarely have just one. A typical mid-rise can carry the domestic service RP, a landscape PVB or RP, point-of-use devices in a ground-floor restaurant, and fire line assemblies. Each has its own report. Phoenix's report form records whether an assembly serves a fire system, landscaping or potable water, and whether it's primary or secondary protection. Keep an inventory so nothing goes untested. Our FAQ on how long to keep backflow test records covers the file.
When it's not a backflow problem
Low pressure on upper floors is usually a pump, pressure regulator or piping issue, not the backflow assembly, unless the assembly is the wrong size. An undersized replacement is the one way the assembly itself can starve the upper floors, which is why Mesa and Scottsdale tie its diameter to the service connection. See water booster pumps for low pressure. And fire line and standpipe assemblies are tested by fire protection contractors: fire backflow assemblies and fire sprinkler work are outside what HQ does.
What HQ does
HQ tests, repairs and replaces the domestic backflow assemblies on mid-rise and high-rise buildings and files the results with the city. On parallel installations we test each leg without dropping the building. On single-assembly buildings we plan the outage window with your engineer or manager. You get an upfront price before work starts and 24/7 emergency service. Related: hotel plumbing, medical and dental plumbing, multifamily plumbing and commercial backflow testing.
Services and tools
How often does a commercial backflow preventer need testing in Arizona?
At least annually. Arizona rules require a certified tester to check each commercial backflow assembly once a year, and again after any install, relocation, or repair. In Phoenix you file results by the date the city sets, and fire system results are due within 30 days.
Read full answer: How often does a commercial backflow preventer need testing in Arizona?How long should I keep backflow test records in Arizona?
At least three years in Phoenix. City Code 37-143 counts from the date a copy went to the city, while the city's TRT 00636 guidance counts from the test date, so count from the later date. Arizona's state rule makes water systems keep their records three years. Mesa, Scottsdale and Tempe require records but set no period, so keep them for the assembly's life.
Read full answer: How long should I keep backflow test records in Arizona?Do I need a water booster pump for low pressure?
Maybe, but measure pressure both with fixtures off and while water is running before choosing a booster. A normal static reading does not prove the supply can meet demand. Rule out restricted valves, filters and pipes, then have a plumber check available supply, elevation and fixture pressure requirements.
Read full answer: Do I need a water booster pump for low pressure?Why is my RPZ backflow preventer spitting water?
An RPZ spits from its relief valve when pressure between its two check valves gets too close to the supply pressure. A short spit when street pressure dips can be normal. Steady or repeated discharge usually means a fouled first check, a leaking second check with backpressure, or a worn relief valve. It needs a test and repair.
Read full answer: Why is my RPZ backflow preventer spitting water?Sources
- Phoenix City Code 37-1, Definitions
- Phoenix City Code 37-144, Backflow prevention methods
- Mesa City Code Title 8 Chapter 1, Backflow Prevention (2025)
- Scottsdale Revised Code Chapter 49, Article II, Division 3, Backflow Prevention
- Tempe City Code Chapter 33, Article V, Cross-Connection Control
- Arizona Administrative Code R18-4-215, Backflow Prevention
- City of Phoenix TRT 00335: Backflow Assembly Test Report Instructions
- Watts (Ames) 2000DCA, 3000DCDC, 4000RP, 5000RPDA installation and maintenance manual
Related commercial services
Who may test, what the report must show, how long the water is off, and where each Valley city wants the results.
Which kitchen and bar connections carry a testable assembly, which cities require one at the meter, and how to test without losing a service.
Master meter rules by city, the assemblies a typical complex carries, who the city holds responsible, and how to batch the yearly tests.
When a PVB is allowed on landscape water, when the city requires an RP instead, and what fails most on irrigation assemblies.
Who may repair an assembly in Phoenix and Scottsdale, the parts that usually fail, and each city's clock for repair and retest.
Repair or replace, picking the assembly type the hazard calls for, and how permits differ for a replacement across the Valley.
Testing a Tall Building?
Talk to a real dispatcher who knows commercial work. Upfront pricing before work starts, 24/7 for emergencies.