Commercial gas lines

Gas Line for a New Commercial Appliance

Load math, a pressure reading under full fire and a look at the meter, before you buy the equipment, not after it shows up.

Short answer

Before a business adds a gas appliance, someone has to add its Btu rating to everything already on the line and check three limits: the pipe size over its longest run, the meter's capacity and the supply pressure under full load. If all three have room, it's a new branch. If not, the pipe, the meter or both get upsized.

The rules that apply

Each rule links to the official text we read it from. Cities change these, so check the source before a big decision. Last checked 2026-10-04.

The new load counts in full

Phoenix (2024 IFGC)

Piping is sized for the sum of the maximum input of every appliance served, assuming all run at full capacity at once. A diversity of load may be used only where it can be established.

Source: IFGC 402.2

A bigger load is permit work

Phoenix

An appliance upgrade with an increase in Btu consumption that requires piping capacity calculations needs a city permit, a city inspection and a city clearance.

Source: Phoenix Gas Clearance Requirements (TRT/DOC/00930)

Tell the utility when your load changes

Southwest Gas, Arizona

It is the customer's responsibility to notify Southwest Gas of changes in load. Larger meter capacity or higher delivery pressure is made at the utility's option if it is not detrimental to other customers, and the customer may be required to reimburse it.

Source: Southwest Gas Arizona Gas Tariff No. 7, Rules No. 3 and 7

Only the new branch is pressure tested

Phoenix (2024 IFGC)

Where new branches are installed to new appliances, only the newly installed branches need a pressure test. The connections between new and existing piping are checked with a noncorrosive leak-detecting fluid.

Source: IFGC 406.1.3

Generators get their own gas pipe

Glendale

Whenever a generator is installed, a separate fuel gas pipe serves only the generator, with a listed valve at the meter locked open and labeled as the generator supply.

Source: Glendale Technical Guideline, Fuel Gas Piping to Generators

Engine-driven equipment is never hard-piped

Phoenix (2024 IFGC)

Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping.

Source: IFGC 616.2

The three limits every new appliance runs into

Every gas system has three ceilings, and a new appliance can hit any of them first.

  1. 1The pipe. Each section of pipe carries a set volume over a set length. The fuel gas code's sizing tables show how fast that falls off: at standard pressure, Table 402.4(1) rates 1-inch steel at 215 cubic feet per hour over 50 feet but only 148 over 100 feet.
  2. 2The meter. Southwest Gas owns the meter and sized it for the load you had when it was set. Its Central Arizona commercial package lists capacities by model; an AL 425, for example, is rated for 425 cubic feet per hour at standard delivery pressure.
  3. 3The pressure under load. Even if the math looks fine, a long or restricted line can drop pressure when everything fires at once.

Natural gas carries roughly 1,000 Btu per cubic foot for sizing, so a 199,000 Btu water heater adds about 199 cubic feet per hour. Southwest Gas's tariff puts the average heating value at not less than 900 Btu per cubic foot, so when the margin is close we use the utility's number.

It's not only kitchens

The question comes up anywhere a business adds gas equipment:

How we check whether your line can carry it

We start with what's actually there, not what the drawings from ten years ago say.

Inventory. Every appliance on that meter and its input from the rating plate, plus the new one.

Measure the run. The length from the meter to the farthest appliance, and the pipe size of each section along the way.

Measure the pressure. A.O. Smith's commercial water heater handbook gives the field test: read supply pressure static, then with every appliance on the main firing at full capacity. If it drops more than 1.5 inches of water column as gas starts to flow, the handbook says the supply system, including the gas line or regulator, "may be restricted or undersized."

Read the meter. The model on the meter tells us its rated capacity, which we compare against the new total.

The result is one of three answers. It fits, and you get a new branch. The pipe is short, and a section gets upsized or a dedicated line runs from the meter. Or the meter is the limit, and Southwest Gas has to make a change before the new appliance can run at full fire.

When the meter is the bottleneck

A bigger meter is Southwest Gas's call, not ours. Its tariff says the customer must tell it about load changes, and a larger meter or higher delivery pressure is made at the utility's option, with the customer possibly reimbursing it. Its commercial package adds that a load over 1,000 cubic feet per hour may need a rotary meter designed and built, which takes a minimum of 2 weeks.

That's why we check the meter before you buy the equipment. A wait on a meter change is a scheduling problem if you know about it in advance and a crisis if you find out after the dryers arrive. Our page on getting a bigger Southwest Gas meter covers the request, and 2 psi delivery is the other lever for large loads.

Permits, testing and the tie-in

In Phoenix, adding Btu load that requires piping capacity calculations is permit work with a city inspection and a city clearance. The good news is the testing. Section 406.1.3 says only the newly installed branch needs the pressure test, while the joint where it ties into the old pipe is checked with leak-detecting fluid. So the existing system usually stays in service while the new branch is built and tested, with a short shutdown for the tie-in. Other Valley cities set their own test pressures; see commercial gas pressure testing.

When you can skip all of this

If you're replacing an appliance with one of the same or lower input in the same spot, with no piping changes, Phoenix's clearance table says no permit is needed and no capacity check is triggered. That's a kitchen equipment hookup or a straight swap. And a load calculation on paper is something your mechanical engineer or equipment dealer can run first; we're happy to check their numbers against what's in the wall.

What HQ does

We inventory the load, measure pressure under full fire, read the meter, size the new branch or the upsized section, pull the permit, build and test it, and send the clearance to Southwest Gas. We're licensed and insured, and the estimate is free with an upfront price before work starts. Related: commercial gas line service, commercial water heaters and commercial plumbing.

FAQ

Gas Line for New Commercial Equipment: common questions

Anything else, call (602) 675-1555.

Can my restaurant's gas line handle a new fryer or range?

Only if the pipe, the meter and the hose all have room for it. Add the new appliance's Btu rating to everything already on the line, then check that total against the pipe size and the longest run in the code's sizing tables. If the total outgrows the pipe or meter, burners run weak when the kitchen is busy.

Read full answer: Can my restaurant's gas line handle a new fryer or range?
How do I get a bigger Southwest Gas meter for my business?

Ask Southwest Gas early, with a load list: every gas appliance and its Btu input, the delivery pressure you need, and your plans. The utility owns the meter, picks its size and may charge for the change. Your plumber resizes and permits the pipe on your side, and the city clearance goes to Southwest Gas.

Read full answer: How do I get a bigger Southwest Gas meter for my business?
Does a bigger commercial water heater need a bigger gas line?

Often, yes. A water heater or boiler with a higher Btu input burns more gas every hour, and the pipe and meter must carry that on top of every other appliance running at once. A same-size swap usually needs no gas work. An upgrade that raises the total load needs a pipe sizing check and, in Phoenix, a permit.

Read full answer: Does a bigger commercial water heater need a bigger gas line?
What gas line does a commercial standby generator need?

A natural gas standby generator needs a line sized for its full-load gas flow, ideally serving the generator alone. At the unit it needs a regulator sized for that flow, a flexible connector, a shutoff, a sediment trap and a test port. The meter must carry the generator's load too, so tell Southwest Gas early.

Read full answer: What gas line does a commercial standby generator need?
What is the longest length method for sizing gas pipe?

The longest length method sizes every section of a gas system from one table row: the length of the longest run from the meter to the farthest appliance. Each section then gets the pipe size for the gas load it carries. Equivalent length adds footage for fittings, so bends and tees count as pipe.

Read full answer: What is the longest length method for sizing gas pipe?