Tempe City Code 33-109 lets the department discontinue water to a premises when a required backflow assembly is not installed, tested and maintained, has been removed or bypassed, or a cross-connection exists. Service is not restored until the defect is corrected. Section 33-110 adds retrofit orders and 33-111 makes violations misdemeanors, each day a new violation.
“Service of water to any premises may be discontinued by the department if a backflow prevention assembly required by this article is not installed, tested and maintained”
- Applies to:
- Owners and water account holders of Tempe commercial properties with backflow assemblies, and the testers and plumbers who service them
- Official fee:
- none; a plumbing permit applies if an assembly is replaced or relocated (see 33-107)
- In force:
- Tempe City Code Chapter 33, Article V (33-110 last amended by Ord. O2024.19, 2024-09-05; 33-109 by Ord. 2004.15)
- Last verified:
- October 4, 2026, against the official page
Three sections of Tempe's backflow article carry the enforcement: one lets the department shut the water off, one lets it order an old assembly replaced, and one makes a violation a daily misdemeanor. The surprise is that they have different triggers.
What does Tempe City Code 33-109 say?
Section 33-109 allows discontinuing service for three conditions: a required assembly "is not installed, tested and maintained"; a backflow prevention assembly "has been removed or bypassed"; or "a cross-connection exists on the premises." It adds that service "will not be restored until such conditions or defects are corrected." The same section says the City "may also terminate a user's service upon twenty (20) days' notice in writing in non-emergency." That sentence is not tied to backflow by its wording, but it sits in the backflow article.
Section 33-108 backs it with entry. The user's system "must be open for inspection at all reasonable times, and in all emergencies" to the department's representatives. When a cross-connection or other hazard "becomes known the department may deny or immediately discontinue service to the premises by providing a physical break in the service line until the user has corrected the condition."
Section 33-110 has two parts. In (a), "If the department determines that a user's backflow prevention assembly does not meet current standards, the user shall retrofit the assembly so that it will meet current standards." In (b), when the Public Works Director or a representative determines a water service "poses an actual or potential threat to the physical properties of the water system or potability of the public water system," an assembly complying with the article "shall be installed."
Section 33-111 says violations may be enforced as under Chapter 12, Article VI, Division 4, that the Public Works Director may develop an enforcement response plan and penalty policy for Council approval, and that "Any violation of this article shall constitute a misdemeanor." Remedies "are not exclusive," and "Each day's noncompliance constitutes a new violation."
What do the key terms mean?
- Cross-connection. Section 33-102 defines it as a physical connection between two otherwise separate piping systems, one with potable water and one with nonpotable water or industrial fluids, through which backflow may occur.
- Backflow prevention assembly. An assembly designed to prevent the reversal of normal flow caused by backpressure or backsiphonage.
- Retrofit. Replacing or upgrading the assembly so that it meets current standards. The article does not define "current standards" in 33-110; the department decides.
- User. The code uses it for the customer. The city's program page sends test letters to "the user paying for the water service."
Who does this cover?
Water customers whose premises are required to have an assembly (33-105 lists the premises), plus any premises the department finds poses a threat under 33-110(b). The program page says test letters go to the user paying for the water service.
It does not apply to a single family residence used solely for residential purposes under the state rule the city's FAQ describes, though the FAQ says residences used for other purposes, and commercial and industrial customers, must install and maintain assemblies.
Quick check: what can the city do?
| Situation | City action | Section |
|---|---|---|
| Required assembly never installed | Water may be discontinued | 33-109 |
| Assembly removed or bypassed | Water may be discontinued | 33-109 |
| Annual test not done | Overdue notice, then enforcement up to termination | Program page, 33-109 |
| Cross-connection found | Service denied or immediately discontinued by a physical break | 33-108 |
| Old assembly no longer meets current standards | Retrofit order | 33-110(a) |
| Service poses a threat to the public system | Compliant assembly must be installed | 33-110(b) |
| Violation continues for days | Each day is a new violation | 33-111(e) |
What does this look like in real life?
A restaurant misses its test date. The program page says an initial test notice goes out 45 days before the due date and an overdue notice follows if the test is not completed and posted. The city "may initiate enforcement action up to and including termination of water service" if it is still not done by the date in the overdue notice.
A theft. A brass assembly is stolen from the front of a shopping center. "Removed" is on the 33-109 list. The city's page says the assembly must be replaced in a timely manner with the same type, and that a plumbing permit is required if it is replaced or relocated. See the stolen assembly page.
The edge case: the working assembly that fails the standard. An older assembly is installed, tested every year and passing. The department decides it does not meet current standards. That is a 33-110(a) retrofit order, not a 33-109 shutoff condition, but ignoring the order is a violation under 33-111 and each day counts.
A cross-connection found on inspection. A hose from a process tank is linked to a potable line. Section 33-108 lets the department deny or immediately discontinue service with a physical break in the line until it is corrected.
What should you do next?
- 1Find the date on the test notice or the compliance notice. The city's FAQ says a backflow assembly must be in compliance within 45 days of the initial compliance notification, unless other arrangements are made.
- 2Hire a certified tester from the city's list. Reports are entered through the city's tester site or sent to backflow@tempe.gov.
- 3If the assembly fails, repair or replace it and have a certified tester retest and submit the results. A permit applies if it is replaced or relocated.
- 4If you cannot make the date, call Environmental Services at 480-350-2678 before it passes. The FAQ says to contact them immediately to make special arrangements.
- 5If service has been discontinued, correct the condition. Under 33-109 service is not restored until it is.
What do people get wrong?
- Waiting for the shutoff to call. The city's FAQ says to contact Environmental Services immediately if a deadline cannot be met.
- Believing a passing test ends the matter. Section 33-110(a) separately requires retrofit when the department finds an assembly no longer meets current standards.
- Expecting the letter to go to the building owner. The city sends test letters to the user paying for the water service.
- Treating the shutoff as the only penalty. Under 33-111 a violation is a misdemeanor and each day is a new violation.
The city's code text governs; this page explains it.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Scottsdale | Scottsdale sends a first notice giving 30 days to remedy a missing, bypassed or improperly tested assembly, then a certified-mail notice of disconnection in 10 days. It may disconnect without notice if the user's water system is contaminating the public supply, and a fire sprinkler supply line is not subject to disconnection under that section. | Scottsdale City Code 49-66 Verified October 4, 2026 |
| Mesa | Mesa may terminate water service if backflow protection is not installed, has been removed or bypassed, is not functioning as designed, has not been tested annually or test records were not timely provided, and may issue an Immediate Notice of Termination if the condition presents an imminent hazard. Service is not restored until the condition is corrected and penalties, fees and charges are paid. | Mesa City Code 8-1-13 Verified October 4, 2026 |
This page explains the rule. The official text at the source above governs.
Backflow Prevention in Other Cities
- AvondaleAvondale City Code 24-10: annual backflow test, 7-day records and the 20-day shutoff clock
- AvondaleAvondale City Code 24-6 and 24-7: which backflow assembly you need and where it goes
- BuckeyeBuckeye City Code 17-4-3: backflow assemblies, yearly tests, 10-day repairs and shutoff
- ChandlerHow long do you have to install a backflow device after a Chandler notice?
- ChandlerWhich backflow device does a Chandler business need?
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
More Tempe Codes and Permits
- Backflow PreventionStolen or moved backflow assembly in Tempe: replacement and permit
- Backflow PreventionTempe City Code 33-103 and 33-104: backflow assemblies on plans and how to install them
- Backflow PreventionTempe City Code 33-105: which commercial properties need a backflow assembly?
- Backflow PreventionTempe City Code 33-107: backflow assemblies must be tested every year
- Backflow PreventionTempe IPC 608.7.2: which facilities need a secondary backflow assembly?
- Commercial PlumbingWhat can a Tempe business not put down the sewer? City Code 27-10
Related Rules and Questions
- MesaCan Mesa shut off your water for backflow violations? City Code 8-1-13
- ScottsdaleCan Scottsdale shut off your water for a backflow violation?
- FAQWhat happens if I miss my Phoenix backflow test deadline?
- FAQMy backflow assembly failed its test. What happens next?
- FAQWho pays for backflow testing: landlord or tenant?
- Commercial Plumbing