Stolen or moved backflow assembly in Tempe: replacement and permit

Verified September 29, 2026
In Short

If a Tempe backflow assembly is stolen, report the theft to Tempe Police, then replace it promptly with the same type of assembly. Replacing or relocating one needs a plumbing permit, and after any repair, overhaul or move the city inspects it and a certified tester retests it under City Code 33-107(e).

Official Source
City of Tempe: Backflow Prevention Program (Environmental Services)
Tempe Backflow Prevention Program; City Code 33-107(e)
“a plumbing permit is required if the assembly is replaced and/or relocated.”
Applies to:
Commercial property owners, HOAs, property managers and their plumbing contractors in Tempe
Official fee:
not published on the program page; the permit is issued by Building Safety under the city fee schedule
In force:
Tempe City Code 33-107(e); program page read 2026-09-29
Last verified:
September 29, 2026, against the official page

Backflow assemblies have brass bodies, and brass gets stolen. When it happens on a Tempe commercial or HOA property, three clocks start at once: the police report, the water utility's testing requirement and the permit for the replacement.

What does Tempe's backflow program say about a stolen assembly?

The city's Backflow Prevention Program page tells users to report the theft to Tempe Police on the non-emergency line, 480-350-8311. It asks for the make, model, size and serial number of the stolen assembly. It says the city "aggressively investigates thefts of assemblies and arrests have been made."

The same page sets the replacement rules. The user must replace the stolen assembly "in a timely manner", and it must be replaced with the same type of assembly. It says to increase security with a cage, a locking mechanism or a style of assembly with less brass. Then comes the permit line: "To be in compliance with Tempe City Code Chapter 33, Section 107(e), a plumbing permit is required if the assembly is replaced and/or relocated. If the assembly is relocated, it may no longer be serving as containment."

Read the code text next to it. Section 33-107(e) says: "Following the repair, repiping, overhaul or relocation of an assembly, the user shall have it inspected by the department and tested by a certified tester." The permit requirement appears on the program page and the Backflow FAQ ("Permits are required to install or replace these assemblies"), not in the 33-107(e) sentence itself.

What do the key terms mean?

  • Same type of assembly: a reduced pressure assembly replaced with a reduced pressure assembly, a double check with a double check. The program page gives no timeline beyond "timely."
  • Containment: protection at the service connection that keeps the whole property's water from flowing back into the city main. The program page says a relocated assembly may lose that role.
  • Less-brass style: the city's suggestion for theft-prone sites. It does not say which models qualify.

Who does this cover?

It covers any Tempe water user with a required backflow assembly, usually commercial, industrial and HOA accounts. The city notices go to the person who pays the water bill. It does not cover a single-family home used only as a home, which the city's FAQ says state rules exempt from assembly requirements.

Quick check: what does each event trigger?

EventPolice reportPermitInspection and retest
Assembly stolenYes, 480-350-8311Yes, to replaceYes
Assembly replaced after failingNoYesYes
Assembly movedNoYesYes, and check it still protects the whole property
Assembly repaired or overhauledNoNot statedYes, 33-107(e)
Assembly tested onlyNoNoAnnual test under 33-107(b)
Replaced with a different typeNoYesThe city says the same type must go back

What does this look like in real life?

An HOA irrigation assembly disappears overnight. The board reports it to the police with the serial number from its maintenance records, then orders the same type back. The gap matters because the landscape line is unprotected until it is replaced.

A shopping center moves its assembly. The owner shifts the RP to a new equipment yard. Relocation needs a permit, the city inspects, and a certified tester retests. The program page warns a moved assembly may stop serving as containment.

The edge case: the stolen assembly is on a fire line. Fire lines have their own rows in 33-105(b): a double check when the connection does not contaminate, RP when there is a pump, a storage tank or an auxiliary supply. Call Environmental Services first so the replacement matches what the city approved.

What should you do next?

  1. 1Call Tempe Police non-emergency at 480-350-8311 and give the make, model, size and serial number.
  2. 2Call Environmental Services at 480-350-2678 and tell them the assembly is gone.
  3. 3Pull a plumbing permit from Tempe Building Safety for the replacement. The Backflow FAQ lists 480-350-8341 for permit questions.
  4. 4Install the same type of assembly, in a compliant location. The FAQ says the assembly may be installed by a property owner, plumbing contractor or general contractor, subject to Registrar of Contractors rules.
  5. 5Have the city inspect it and a certified, Tempe-registered tester test it and post the results.
  6. 6Add a cage or lock, and ask about a lower-brass style.

What do people get wrong?

  • "I can swap in a different type of device." The city says the same type goes back.
  • "A like-for-like swap needs no permit." In Tempe the program page and FAQ say a permit is required to replace. Phoenix exempts small secondary assemblies, so a Phoenix rule does not carry over.
  • "Water is on, so I am fine." A missing required assembly is a shutoff ground under 33-109.
  • "Once it is replaced, it is done." It must be inspected and tested.

How Do Other Valley Cities Handle It?

WhereWhat appliesSource
PhoenixNo permit for repair or replacement of an existing secondary backflow assembly 2 inches or smaller, but a certified tester's report goes to the city at the time of the work.Phoenix Building Construction Code, Sec. 105.2, Plumbing item 6
Verified September 29, 2026
GlendaleBackflow installation permits are required for all new installations, including retrofits and replacement of existing assemblies.Glendale Water Services, Backflow Tester Policy
Verified September 29, 2026
GilbertA permit is required when replacing an existing assembly that has failed and cannot be repaired. New construction installs do not need a separate permit.Gilbert Development Services, Backflow Prevention FAQ
Verified September 29, 2026

This page explains the rule. The official text at the source above governs.

Sources