Commercial Backwater Valve Installation in Phoenix

If your lowest drain sits below the next upstream manhole, the code wants a one-way valve in the building drain. Here is how it gets there.

Short answer

A backwater valve is a one-way flap in the building drain that stops sewage from flowing back into a building when the public sewer surcharges. The plumbing code requires one on fixtures set below the next upstream manhole cover. HQ installs commercial backwater valves, with access, and tells you which fixtures they protect and which they must not serve.

The rules that apply

Each rule links to the official text we read it from. Cities change these, so check the source before a big decision. Last checked 2026-10-04.

The elevation test: below the upstream manhole cover

2024 IPC

Fixtures on a floor with a finished floor elevation below the next upstream manhole cover in the public sewer are protected by a backwater valve in the building drain or the horizontal branch serving them. Fixtures above that elevation may not discharge through a backwater valve, except in existing buildings.

Source: 2024 IPC Sec. 714.1 (Sewage backflow)

Approved valves, and access to the working parts

2024 IPC

Backwater valves comply with ASME A112.14.1, CSA B181.1 or CSA B181.2, and are installed so access is provided to the working parts.

Source: 2024 IPC Sec. 714.2 and 714.3

Mesa uses a 12-inch margin

Mesa

Privately owned backwater valves on private property are provided on service connections where the finished floor is less than 12 inches above the upstream manhole. If the adopted plumbing code is more stringent, the code governs.

Source: Mesa Engineering and Design Standards (Aug. 2025), Sec. 433.15

Scottsdale puts the valve on private property, accessible

Scottsdale

A backwater valve is provided on service connections where sewer gas could migrate into the service line and where the finish floor is not 12 inches higher than the upstream manhole. Valves are located on private property and are accessible for maintenance by the property owner.

Source: Scottsdale Design Standards and Policies Manual (2018), Sec. 7-1.409

A backwater valve does not replace an indirect connection

2024 IPC

Floor drains inside walk-in refrigerators or freezers in food service must be indirectly connected to the drainage system through an air gap. Where such a drain is protected by a backwater valve, it must still be connected through an air break or air gap.

Source: 2024 IPC Sec. 802.1.2

Cutting into the building drain is permitted work

Phoenix

Installing new drain piping or a new device is new work, not a leak stop, and needs a permit and an inspection before the work is concealed. Building service equipment is not connected until the building official authorizes it.

Source: Phoenix PBCC, IBC Sec. 105.2 and 110.3.10.1

When does a commercial building need a backwater valve?

When any drain sits below the next upstream manhole cover in the public sewer. The 2024 IPC Section 714.1 puts it plainly: fixtures on a floor with a finished floor elevation below that manhole cover are protected by a backwater valve in the building drain or the horizontal branch serving them. The reasoning is simple. If the city main fills past capacity, sewage rises to its lowest outlet, and the lowest outlet in your building is the first to flood. Valley cities add their own measures. Mesa asks for a valve where the finished floor is less than 12 inches above the upstream manhole, and Scottsdale asks for one where the floor is not 12 inches higher. Both sit on private property. Our FAQ on when a backwater valve is required covers the rule in more detail.

Section 714.1 also contains a restriction that surprises owners: fixtures above that elevation may not discharge through a backwater valve in new work. A valve that is closed during a surcharge shuts off drainage for everything behind it, so upper fixtures are piped separately. Existing buildings are excepted from that restriction.

How is a backwater valve installed in an existing building?

The installer cuts into the building drain and sets the valve in line, with access to the working parts. First, an elevation check settles whether the valve is required and which fixtures sit behind it. Second, the installer finds the drain and its slope, usually with a camera (see sewer camera inspection). Third, the slab is opened over the drain, the line is cut and the valve is set level with an access box or cover so the flap can be inspected and cleaned. A cleanout is often added upstream. The valve must be ASME- or CSA-listed, and the code requires that access be provided to its working parts. After the valve is set the line is tested, the slab is patched, and the permit is inspected. In Phoenix, new drain piping is permitted work and concealed piping may not be covered until it is inspected.

What do tenants and owners need to know about a shared building drain?

A valve protects everything upstream of it, and it also blocks drainage upstream of it when it closes. In a multi-tenant building one valve on the main building drain can serve every suite below the manhole line, so ownership and maintenance should be written down, because a valve that nobody opens and cleans is a valve that fails. The sequence after a backup is covered in multi-tenant sewer backups. Cleanouts, camera runs and routine cleaning keep debris from holding the flap open. The code says access must be provided to the working parts, so treat the access cover as a maintenance item, not a decoration.

Insurance is a separate question; see commercial water leak versus sewer backup coverage before you assume a policy pays for a sewer backup.

What fixtures does it protect, and what does it leave out?

It protects fixtures that drain through the building drain below the valve's location. Floor drains, restroom fixtures, floor sinks and mop sinks on a low floor are the usual ones. It does not protect upper fixtures routed separately, and it does not replace indirect connections: a walk-in cooler floor drain protected by a valve must still discharge through an air break or air gap under Section 802.1.2. See floor sink versus floor drain for the difference.

When a backwater valve is the wrong answer

A valve does not clear a stoppage in your own line. If the backup comes from a clog on your side of the cleanout, a valve changes nothing, and the answer is drain cleaning or a camera run. If every fixture is above the upstream manhole cover, the code does not call for a valve and may not allow new fixtures to drain through one. If the fixtures are too low for gravity drainage at all, the answer is an engineered pumped system, which is separate design work and not part of this service. And if the sewer is backing up often, ask the city about the main; a valve limits the damage but not the cause.

How to book

HQ installs backwater valves with free estimates and upfront pricing before work starts. Send us the address, the lowest floor drain location, your city and any as-built drawings with the street manhole elevation. Related: commercial plumbing, commercial sewer lateral repair and our sewer repair page.

FAQ

Commercial Backwater Valve Installation: common questions

Anything else, call (602) 675-1555.

Do I need a backwater valve, and when does code require one?

You need a backwater valve when any drain or fixture in your home sits below the next upstream manhole cover of the public sewer. Code requires one there because those low fixtures flood first if the city sewer backs up. Fixtures above that line must not drain through the valve.

Read full answer: Do I need a backwater valve, and when does code require one?
Sewer backup in a multi-tenant building: what first?

First keep people away from the sewage and stop water use in the building so the backup stops growing. Then call a commercial plumber to find the blockage, notify the city if it is coming from the public main, and tell tenants in writing. Photograph everything before cleanup starts.

Read full answer: Sewer backup in a multi-tenant building: what first?
How do business property policies distinguish leaks, sewer backup and flood?

Business property coverage depends on the actual policy’s covered causes, exclusions and endorsements. A supply leak, sewage backup and surface-water flood are different events to describe accurately, not interchangeable coverage labels. Have a licensed commercial insurance professional check each scenario and any separate flood or backup terms; the plumber documents the source and repair rather than deciding coverage.

Read full answer: How do business property policies distinguish leaks, sewer backup and flood?
What's the difference between a floor sink, floor drain, and mop sink?

A floor sink is a recessed receptor that catches indirect waste from equipment through an air gap. A floor drain is a direct, trapped drain in the floor for washdown water. A mop sink is a low basin for filling and dumping mop buckets. Each serves a separate code purpose.

Read full answer: What's the difference between a floor sink, floor drain, and mop sink?