Youngtown Town Code 13.12.060 lists the premises that need an approved backflow assembly as the minimum at each service connection, including food processing, car washes, medical and dental buildings and shopping centers. Section 13.12.080 requires a yearly test by an approved tester and 15 days notice. The town's page says it does not own its water.
“An approved backflow preventive assembly of the type specified in this section shall be the minimum installation of each service connection (whether from a fire hydrant, temporary, regular or other water service connection)”
- Applies to:
- Owners and tenants of commercial, institutional and irrigated properties in Youngtown, certified testers, and contractors building or repairing service connections
- Official fee:
- none stated in the code section
- In force:
- Youngtown Town Code Ch. 13.12, Cross-connection control (Ord. 94-03; penalty section amended by Ord. 17-02)
- Last verified:
- October 4, 2026, against the official page
Youngtown's backflow chapter is short and complete: a list of premises, an installation section, a testing section and a penalty. The twist is on the town's Public Works page, which says Youngtown does not own its water. That changes who you call.
What does Youngtown Town Code 13.12 say?
Section 13.12.060 sets the floor: "An approved backflow preventive assembly of the type specified in this section shall be the minimum installation of each service connection (whether from a fire hydrant, temporary, regular or other water service connection)." A table then marks the assembly for each premises type.
Section 13.12.080 covers testing and records:
- (A), records: the user keeps accurate records of tests and repairs on forms the department approves, with the list of materials or replacement parts used.
- (B), tests: testing, maintenance and repairs are at the customer's expense by a certified tester the department approves. The user sees that tests are made "at the time of the initial installation and at least once a year, on the anniversary date, of the initial inspection."
- (C), notice: "The user shall notify the department fifteen (15) days in advance when the annual tests are to be done, so that an official representative of the department may witness the tests if so desired."
- (D) and (E), new and repaired work: after installation the department inspects before the certificate of occupancy is issued. After repair, repiping, overhaul or relocation the department inspects and a certified tester tests.
What do the key terms mean?
- The department: Section 13.12.020 names the public works department.
- User: the code does not define it. The ordinary reading is whoever takes water at the connection.
- Minimum: the table sets a floor, not a ceiling.
- DC, RP, PVB, air gap: the table's four columns. Section 13.12.020 defines each by how it is built. A double check valve assembly is "two independently operating approved check valves" with shutoff valves and test cocks. A reduced pressure principle assembly adds a "differential pressure relief valve located between the check valves". A pressure vacuum breaker assembly has "an independently operating loaded check valve and an independently operating loaded air inlet valve located on the discharge side of the check valve." An air gap is "the unobstructed vertical distance through the free atmosphere" between the supply opening and the vessel's flood level rim. Youngtown's chapter does not rank the four; its table decides which one a premises gets.
- Health hazard vs pollution hazard: Youngtown's chapter does not sort devices by hazard, but Surprise City Code 58-261 does. Where a health hazard is possible, Surprise requires "an approved, fixed proper air gap separation, or an approved reduced pressure principle backflow prevention assembly". It allows a double check valve assembly only where the hazard is "a pollution hazard not dangerous to health."
Who is the "town water" in town code?
The chapter's purpose clause in Section 13.12.010 is to protect "the public water supply of the town".
Now the other half. The Public Works page says: "Youngtown does not own its water and utilities, so these services are provided by private utility companies," and lists EPCOR Water at (623) 815-3100. Neither source says who enforces Chapter 13.12 for an EPCOR customer. Treat the chapter as the rule on the books, because Section 13.12.120 makes a violation a Class 1 misdemeanor, and ask both Town Hall and EPCOR which one expects the paperwork.
Who does this cover?
Anyone with a service connection to premises on the table. Section 13.12.110 reaches existing users too: if the department decides an assembly does not meet current standards, the user must retrofit it, and a device is required where the public works director finds a service poses an actual or potential threat to the water system.
Quick check: what does the table mark?
| Premises | Assembly marked |
|---|---|
| Food processing | DC |
| Medical and dental buildings; sanitariums, rest and convalescent homes | DC |
| Shopping centers | DC |
| Buildings over three stories or 34 feet; buildings with house pumps or potable storage | DC |
| Commercial laundries; car washes; animal clinics | RP |
| Hospitals and mortuaries | RP |
| Automotive repair with steam, acid or solvent facilities | RP |
| Irrigation systems with non-potable piping one inch and larger | RP and PVB |
| Any premises where a cross-connection is maintained | RP |
| Restaurants | Not listed by name |
What does this look like in real life?
A dental office on a commercial strip. Medical and dental buildings are on the table at DC. The tenant's first test is at installation, then yearly on the anniversary of the first inspection.
A car wash. The table marks car wash facilities RP, where it marks shopping centers DC. An RP must go above ground under Section 13.12.050.
The edge case: who sends the reminder. The code puts the duty on the user, not on the department. If the water bill comes from EPCOR, a reminder may never come from the town. Put the anniversary date on your own calendar.
What should you do next?
- 1Find your premises type in the table. Check the cross-connection row if it is not listed.
- 2Call Town Hall at 623-933-8286 (Monday to Friday, 8 a.m. to 4 p.m.) and ask whether the department or EPCOR approves testers and receives reports.
- 3Put the assembly where Section 13.12.050 says: at the service connection or near the property line, before the first branch line, and accessible. An RP goes above ground, with no bypass around it.
- 4Use a certified tester the department approves, and keep the test report and any repair records.
- 5Send the 15-day notice before each annual test.
- 6For new work, get the department's inspection before the certificate of occupancy.
What do people get wrong?
- Assuming no town water means no town rule. The chapter is still on the books, and a violation is a Class 1 misdemeanor under 13.12.120.
- Assuming the Tolleson or Tempe version applies. Youngtown's table marks several categories DC where Tolleson marks RP, and Youngtown's certificate of occupancy clause asks only for inspection.
- Missing the daily penalty. Section 13.12.120 says each day a violation continues is a separate offense.
- Assuming the town will remind you. The code puts the notice on the user.
What happens if you skip it?
Section 13.12.100 lets the department discontinue water service if a required assembly is not installed, tested and maintained, removed or bypassed, or a cross-connection exists, and "service will not be restored until such conditions or defects are corrected." Section 13.12.120 sets a fine of not less than $500 and not more than $2,500, or imprisonment up to six months, or both.
Full text and source
The rules are Youngtown Town Code 13.12.060 and 13.12.080 on Municode. HQ tests and repairs domestic backflow assemblies. This page is an explanation, and the code text governs.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Tolleson | Tolleson's table uses the same layout but marks food processing, medical and dental buildings, shopping centers and buildings over three stories RP, where Youngtown marks them DC. | Tolleson City Code 10-7-5(A) Verified October 4, 2026 |
| Tempe | Tempe requires the installed assembly to be tested by a certified tester and the results sent to Community Development with an inspection request before the certificate of occupancy. Youngtown's matching clause asks only for the department's inspection. | Tempe City Code 33-107(d) Verified October 4, 2026 |
| Glendale | Glendale lists restaurants and bakeries as RP and shopping centers as DC. Youngtown's table has no restaurant line and also marks shopping centers DC. | Glendale City Code 33-90(a) Verified October 4, 2026 |
This page explains the rule. The official text at the source above governs.
- Municode: Youngtown Town Code 13.12.060, Premises or systems requiring approved backflow preventive devices
- Municode: Youngtown Town Code 13.12.080, Maintenance, testing and records
- Municode: Youngtown Town Code Ch. 13.12, Cross-connection control
- Dept page: Youngtown Public Works
- Tolleson Municode: City Code 10-7-5, Premises or systems requiring approved backflow preventive devices
- Tempe Municode: City Code Sec. 33-107, Maintenance, testing and records
- Glendale Municode: City Code Sec. 33-90, Backflow prevention device required for specified activities
- Surprise Municode: City Code Sec. 58-261, Type of protection required
Backflow Prevention in Other Cities
- AvondaleAvondale City Code 24-10: annual backflow test, 7-day records and the 20-day shutoff clock
- AvondaleAvondale City Code 24-6 and 24-7: which backflow assembly you need and where it goes
- BuckeyeBuckeye City Code 17-4-3: backflow assemblies, yearly tests, 10-day repairs and shutoff
- ChandlerHow long do you have to install a backflow device after a Chandler notice?
- ChandlerWhich backflow device does a Chandler business need?
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
Related Rules and Questions
- TollesonWhich Tolleson businesses need a backflow assembly?
- TollesonTolleson City Code 10-7-7: backflow testing and the 15-day notice
- GlendaleGlendale City Code 33-90: which businesses need a backflow device
- TempeTempe City Code 33-107: backflow assemblies must be tested every year
- Valley-WideWhich Businesses Need a Backflow Assembly in Each Valley City
- ArizonaArizona Administrative Code R18-4-215: Backflow Prevention and Annual Testing
- FAQHow often does a commercial backflow preventer need testing in Arizona?
- FAQWho pays for backflow testing: landlord or tenant?
- FAQDoes a new tenant or change of use require a new backflow assembly?
- Commercial Plumbing