Glendale requires a backflow device on a fire sprinkler service where Sec. 33-90 calls for one, installed at the service connection to the city's standard specification. If the city wants uninterrupted water during testing, two devices go in parallel. Modifying an existing fire-only service brings the whole system up to current rules.
“Modifications of an existing service connection supplying water solely to a fire sprinkler system shall require the entire system to comply with the requirements of Section 33-18 and Section 33-90.”
- Applies to:
- Owners, property managers and designers of buildings with fire sprinkler systems on a Glendale water service; fire protection contractors
- Official fee:
- not published in this section
- In force:
- Glendale City Code Ch. 33, Art. II, Div. 5 (Ord. 3003, 2016)
- Last verified:
- September 29, 2026, against the official page
A fire sprinkler line is a water line that mostly sits still. That is why the city wants a device on it: it keeps anything in the sprinkler pipe from flowing back into the drinking water main. This page explains what Glendale requires. Fire line design and installation belong to a licensed fire protection contractor and the fire department.
What does Glendale City Code 33-92 say?
Section 33-92 has three parts. Subsection (a): when a backflow device is required on a service that supplies only a fire sprinkler system, it is installed at the service connection to the city's standard specification. Subsection (b): if the city decides the sprinkler system needs continuous water that "may not be interrupted during testing of the backflow prevention device," the customer installs two devices in parallel at the customer's expense, each with a diameter at least equal to the service connection. Subsection (c): "Modifications of an existing service connection supplying water solely to a fire sprinkler system shall require the entire system to comply with the requirements of Section 33-18 and Section 33-90."
Section 33-90 decides which device. Fire systems in AWWA classes 1, 2 and 3 need a double check assembly. That also applies to any fire system 6 inches or larger, or built of piping not approved for potable water use. Classes 4, 5 and 6 need a reduced pressure assembly. If the same premises has an industrial or domestic service that needs protection, both services get protection for the highest hazard of either system.
Section 33-96(b) adds a limit: water service to a fire sprinkler system is not disconnected under the backflow shutoff rules. The city can still cite a misdemeanor if a required fix is ignored past the notice.
What do the key terms mean?
- Fire sprinkler service: a water connection that supplies only the sprinkler system, as opposed to a combined fire and domestic line.
- AWWA classes: a classification of fire systems used in the 33-90 list. Glendale's code cites the classes without defining them, so ask your fire protection contractor which class your system is.
- Parallel devices: two assemblies side by side so one can be tested while the other keeps water flowing.
Who does this cover?
Buildings with a fire sprinkler system on a Glendale water service. It does not cover the sprinkler design itself, which follows the fire code. It also does not cover a fire service the city has not required a device on.
Quick check: what does your fire service need?
| Situation | Device or action | Why |
|---|---|---|
| Class 1 to 3 sprinkler service | Double check | 33-90 item 22 |
| Class 4 to 6 sprinkler service | Reduced pressure | 33-90 item 23 |
| System 6 inches or larger | Double check | 33-90 item 22 |
| City wants water during testing | Two devices in parallel | 33-92(b) |
| Existing fire-only service is modified | Whole system meets current rules | 33-92(c) |
| Fire line plus a domestic service on one property | Protect for the highest hazard | 33-90 item 24 |
| Overdue backflow test on a fire line | Not disconnected; can be cited | 33-96(b) |
What does this look like in real life?
A retail center upsizes or replaces its fire service. Subsection (c) applies to "Modifications of an existing service connection", so a new or upsized fire service is the kind of change to raise with the city. Whether sprinkler work inside a tenant suite counts is not something the section says, so ask Cross Connection Control before assuming either way.
A building whose sprinkler class is unclear. The 33-90 list gives a double check for classes 1 to 3 and a reduced pressure assembly for classes 4 to 6. The wrong class means the wrong device on the plans, so get the class in writing from the fire protection contractor first.
The edge case: an overdue test on a fire line. For a domestic line the city can shut off water after notices. For a fire-only service it cannot use disconnection, so the enforcement path is the misdemeanor citation instead.
What should you do next?
- 1Have your fire protection contractor state the AWWA class of the system and the pipe size.
- 2Match it to the 33-90 device: double check for classes 1 to 3, reduced pressure for classes 4 to 6.
- 3Ask Glendale Water Services Cross Connection Control (623-930-4138) whether the city wants a parallel pair for continuous water.
- 4Show the device on the plans. Section 33-99 requires city approval before the permit.
- 5After installation, request inspection at the permit line, 623-915-3263, code 238 for a backflow fire line.
- 6Schedule the yearly test with a city-certified tester.
What do people get wrong?
- "A fire line is exempt from backflow rules." It is not. It is exempt only from the water shutoff remedy.
- "A small change is just a small change." Modifying a fire-only service triggers compliance for the entire system under 33-92(c).
- "One device is always enough." The city can require two in parallel when water must not be interrupted.
Full text and source
The rules are Glendale City Code Secs. 33-90, 33-92 and 33-96 on Municode. This is a summary of three short sections. The code text and the fire department's requirements control your project.
How Do Other Valley Cities Handle It?
| Where | What applies | Source |
|---|---|---|
| Mesa | A fire sprinkler system with no additives gets a double check; additives such as antifreeze or a combined fire and domestic service need a reduced pressure assembly. Existing systems are exempt until modified, a check valve fails or occupancy becomes more hazardous. | Mesa City Code 8-1-10 Verified September 29, 2026 |
| Scottsdale | A double check is required on new commercial construction, modified Class 1 or 2 systems or a failing single check; the fire chief can require two in parallel. Existing single checks are inspected yearly and defects reported within 24 hours. | Scottsdale Revised Code 49-64 Verified September 29, 2026 |
This page explains the rule. The official text at the source above governs.
- Glendale City Code Sec. 33-92, Fire sprinkler systems (Municode)
- Glendale City Code Sec. 33-90, Backflow prevention device required for specified activities (Municode)
- Glendale City Code Sec. 33-96, Discontinuance of water service (Municode)
- Mesa City Code 8-1-10, fire sprinkler systems (Municode)
- Scottsdale Revised Code Sec. 49-64 (Municode)
Backflow Prevention in Other Cities
- ChandlerChandler City Code 52-36: backflow assemblies on commercial building plans
- GilbertGilbert Town Code 10-92(c): which backflow assembly does your kind of property need?
- MesaMesa City Code 8-1-10: backflow rules for fire sprinkler systems
- MesaMesa City Code 8-1-11: annual backflow testing, repair deadlines and who can test
- MesaWho can test backflow assemblies in Mesa? City Code 8-1-12 recognized testers
- MesaCan Mesa shut off your water for backflow violations? City Code 8-1-13
More Glendale Codes and Permits
- Backflow PreventionGlendale City Code 33-90: which businesses need a backflow device
- Backflow PreventionGlendale City Code 33-94: annual backflow test, records and shutoff
- Backflow PreventionGlendale City Code 33-99: backflow devices must be on your building plans
- Permits and InspectionsWhat plumbing and gas code does Glendale use?
- Sewer LinesGlendale City Code 33-217: who repairs the sewer line from the building to the street
- Commercial PlumbingGlendale City Code 33-238: grease interceptors must be pumped every 180 days